Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)Pompa de caldura aer / apa
Subject to modifications, 1.7.2015 5
Hoval Belaria® SRMHoval Belaria® compact SRMSistem modular pompa de caldura pen-tru incalzirea si racire
Sistem split format din unitate interioara si unitate exterioara.Interval de modulare 30% pana la 100%
Unitate interioara Belaria® SRM• Unitate compacta pentru instalarea pe
perete• Carcasa facuta din tabla de otel vopsita si
galvanizata. Culoarea alb pur (RAL 9010)• Condensator din otel inoxidabil/Cupru• Pompa de circulatie de eficienta mare cu
control de viteza• Vas de expansiune, volum10 litri• Manometru• Senzor de tur• Robineti de separare pentru tur si retur
inclusi (livrati separat)• Incalzire de urgenta
Hoval Belaria® SRM (4) 3 kW Hoval Belaria® SRM (6-16) 3/9 kW (vezi date tehnice) cu termostat de sigu-ranta, supapa de siguranta
• Filtru, separator de aer, supapa de siguranta• Automatizare cu functie de incalzire, racire si
boiler (unitatea de operare inclusa separat)• Cu functie de racire prin inversarea ciclului• Intrerupator electric• Senzori tur si retur• Robinet de umplere si golire
Unitate interioara Belaria® compact SRM• Unitate compacta situata pe podea• Carcasa facuta din tabla de otel vopsita si
galvanizata. Culoare alb pur RAL9010.• Condensator otel inoxidabil/Cupru• Boiler din otel inoxidabil inclus
Hoval Belaria® compact SRM (4): 180 litri Hoval Belaria® compact SRM (6-16): 260 litri
• Pompa de circulatie de eficienta mare cu control de viteza
• Vas de expansiune, volum10 litri• Manometru• Senzor de tur• Robineti de separare pentru tur si retur
inclusi (livrati separat)• Incalzire de urgenta
Hoval Belaria® compact SRM (4) 3 kW Hoval Belaria® compact SRM (6-16) 3/9 kW (vezi date tehnice) cu termostat de sigu-ranta, supapa de siguranta
• Filtru, separator de aer, supapa de siguranta• Automatizare cu functie de incalzire, racire si
boiler (unitatea de operare inclusa separat)• Cu functie de racire prin inversarea ciclului• Intrerupator electric• Senzori tur si retur• Robinet de umplere si golire
Unitate exterioara• Unitate compacta pentru instalare exterioara• Carcasa facuta din tabla de otel vopsite si
galvanizate. Culoarea bej/gri (similar cu RAL 7044)
• Compresor cu reglare viteza• Ventilatoare controlate la viteza1 / 2• Vaporizator din tevi cu lamele Alu/Cu, vopsit• Ventil de laminare electronic• Vana cu patru cai• Umplut cu agent de frigorific R 410 A
• Robineti de inchidere fortata pe partea de agent frigorific
• Senzor de exterior instalat• Tava de scurgere condens incalzita instalata
Hoval Belaria® SRM (11-16) Hoval Belaria® compact SRM (11-16)
Racorduri, incalzire / racire• Racorduri incalzire
Unitate interioara Hoval Belaria® SRM (4-16) jos, unitate interioara Hoval Belaria® com-pact SRM (4-16) sus
• 2 robineti de separare inclusi, livrati separat
• Racorduri, circuit frigorific• Unitate interioara Belaria® SRM (4-16) jos,
unitate interioara Belaria® compact SRM (4-16) sus
• Unitate exterioara pe partea dreapta• Circuit de vapori fierbinti 15.9 mm (⅝″)
circuit de lichid: Belaria® SRM, compact SRM (4-8) 6.4 mm (¼″) Hoval Belaria® SRM, compact SRM (11-16) 9.5 mm (⅜″)
Scurgere de condens• Evacuarea libera a condensului• O tava optionala pentru condens pentru
evacuarea colectiva a condensului este disponibila
Conexiuni electrice• Unitate exterioara cu conexiunea pe partea
dreapta Belaria® SRM, compact SRM (4-8) 230 V, Belaria® SRM, compact SRM (11-16) 3 x 400 V
• Unitatea interioara este alimentata electric de la unitatea exterioara
• Incalzirea de urgenta este conectata la unitatea interioara separat.
• Conexiune legare rezistenta electrica boiler extern 1 x 400 V (Belaria® SRM (4-16))
Livrare• Unitatea interioara si unitatea exterioara
sunt livrate ambalate separat• Ambii robineti de separare sunt livrati cu
unitatea interioara• Senzor pentru boiler livrat in unitatea interio-
ara (Belaria® SRM (4-16))
La fata locului• Instalarea setului de izolatie
(Hoval Belaria® SRM)• Instalarea placii de alarma colectiva• Treceri prin perete pentru conductele de
agent frigorific• Circuit electric dintre unitate exterioara si
unitatea interioara
Unitate exterioara
Unitate interioaraHoval Belaria® SRM
Unitate interioaraHoval Belaria® compact SRM
AutorizatiiElvetia / AustriaCertificat de aprobare FWS 26.6.2013Hoval Belaria® SRM (6) Test Nr. WPZ-LW-207-13-10Hoval Belaria® SRM (14) Test Nr. WPZ-LW-124-08-05Hoval Belaria® SRM (16) Test Nr. WPZ-LW-208-13-11Seria Belaria® SRM (4-16) este certificata de comisia de autorizare din Elvetia.
Hoval Belaria® SRM Hoval Belaria® compact SRM Putere de incalzire Putere de racire
tip cu A-7W35 cu A2W35 cu A35W1835 °C 55 °C kW kW kW
A+ A+ (4) 4.6 4.8 5.9A+ A+ (6) 5.3 6.4 7.3A+ A+ (8) 6.4 7.7 8.4A+ A+ (11) 8.8 9.1 15.1A+ A+ (14) 11.7 10.9 16.1A+ A+ (16) 12.3 11.4 16.8Eticheta pachetului include controller-ul
Set conectarepentru Belaria® SRM (11-16)Previne vibratii asupra circuitului de incalzireContine:2 bucati furtune flexibile DN 32, L=1.5 m2 bucati niplu redus R 1 ¼″ x RG 1″2 bucati garnituri
6024 913
6 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
■ Coduri articole
Coduri articoleHoval Belaria® SRMHoval Belaria® compact SRMSistem pompa de caldura aer / apa
Sistem modular pompa de caldura pentru in-calzire si racire. Format din unitatea interioara si unitatea exterioara.Belaria® compact SRM cu boiler integrat in unitatea interioara.
Hoval Belaria® SRMSistem pompa de caldura
Tip Putere de incalzire kW
Putere de racire kW
A-7W35 A2W35 A35W18
(4) 4.6 4.8 5.9(6) 5.3 6.4 7.3(8) 6.4 7.7 8.4
(11) 8.8 9.1 15.1(14) 11.7 10.9 16.1(16) 12.3 11.4 16.8
Hoval Belaria® compact SRMSistem pompa de caldura cu boiler integrat
Tip Volum boiler Putere de incalzire
kW
Putere de racire kW
A2W35 A35W18
(4) 180 4.8 5.9(6) 260 6.4 7.3(8) 260 7.7 8.4
(11) 260 9.1 15.1(14) 260 10.9 16.1(16) 260 11.4 16.8
7013 709 7013 710 7013 711 7013 712 7013 713 7013 714
7013 715 7013 716 7013 717 7013 718 7013 719 7013 720
Clasa eficienta energeticavezi descriere
Statie de camera
Automatizare suplimentara cu functia de statie de camera, aceeasi functie precum controller-ul de pe unitate (conexiune prin cablu)
6031 248
Senzor temperatura exterioaraSenzor aditional temperatura exterioara, necesar daca unitatatea exterioara este situata intr-o pozitie nefavorabila (expusa la lumina solara)
2053 179
Placa electronica suplimentara (A4P/A7P)circuit digital pornit/oprit pentru:- Iesire alarma- Schimbare la sursa externa de caldura
6019 357
Tava de scurgere condens pentru unitatea exterioarapentru Belaria® SRM (4-16),Compact SRM (4-16) si SHM (11-16)pentru colectarea condensului de sub unitatea exterioaraMaterial: Plastic rezistent la UVRezistenta electrica 120 W, 230 V cu termostatIesire condens: Ø (exterior) 38 mmDimensiuni: L=960 mm, W=420 mm, D=40 mmIn cazul instalarii pe o baza, suportii antivibranti trebuie comandati suplimentar.
6028 145
Banda de incalzire electricapentru incalzire unei conducte de scurgere condens (la fata locului)cu termostatPutere: 40-80 W, 230 VLungime: cablu 1.5 m; banda de incalzire 2 m
6033 374
Modul interfata RTD-LT/CApentru controlul puterii externePORNIT/OPRIT, 0-10 V, MOD busFunctii Smart Gridinclude adaptor principal 230 V
6015 363
■ Coduri articole
Coduri articole
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 7
Accesorii
Termostat de cameraRS-W (conexiune cu cablu)
RS-R (cu transimisie radio)
6023 044
6023 045
Acoperis protector pentru unitatea exterioarapentru Belaria® SRM, Compact SRM (4-8)Tabla de otel vopsita electrostaticCuloare: gri matase RAL 7044De semenea compatibil cu consola de perete pentru unitatea exetrioara.
6032 511
Acoperis protector pentru unitatea exterioarapentru Belaria® SRM (11-16),Compact SRM (11-16) si SHM (11-16)Tabla de otel vopsita electrostaticCuloare: gri matase RAL 7044De semenea compatibil cu consola de perete pentru unitatea exetrioara
7006 360
Grilaj protector pentru unitatea exterioarapentru Belaria® SRM si Compact SRM (4-8)grilaj robust pentru protejarea vaporatoruluiMaterial: otel inoxidabil vopsit (RAL 7044)Montare la fata locului
6031 613
Grilaj protector pentru unitatea exterioarapentru Belaria® SRM (11-16),Compact SRM (11-16) si SHM (11-16)grilaj robust pentru protejarea evaporatoruluiMaterial: otel inoxidabil vopsit (RAL 7044)Montare la fata locului
6028 144
Grilaj protector pentru unitatea exterioarapentru Belaria® SRM (11-16),compact SRM (11-16) si SHM (11-16)grilaj robust pentru protejarea vaporatorului (in fata)Material: otel inoxidabil vopsit (RAL 7044)Montare la fata locului
6028 243
Consola de perete pentru unitatea exterioarapentru montarea unitatii pe perete2 suporti facuti din otel inoxidabilinclude suporti antivibranti si materialul de fixareAtentie:Nu poate fi folosit in aceasta forma pe pereti termoizolati!Nu este adecvat pentru pereti subtiri.
6031 530
Baza pentru unitatea exterioarapentru Belaria® SRM (4-8) si Compact SRM (4-8)Contine:2 suporti in forma de "U", vopsitiTrebuie folosit doar pentru instalarea pe un soclu de ciment(vezi planurile bazei de sustinere)
6031 247
Suporti antivibrantipentru instalarea unitatii pe un soclu din ciment (la fata locului)4 bucati, include dibluri HKD-S M8x30,saibe si piulite.
6022 489
■ Coduri articole
Coduri articole
8 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Set izolare (inauntrul unitatii)pentru Belaria® SRM (4-16)Necesar pentru prevenirea scaderii de temperatura sub punctul de roua in modul racire, cu temperaturi de tur sub 20°C
6031 249
Separator de impuritati magneticDirtmag 25 - 1″Carcasa, capac si elemente interioare facute din plastic HDPEInterval de temperatura 0-90 °CPresiune maxima operare: 3 barIndex Kvs debit: 10.5Fractie maxima glicol: 30 %separator de aer manualracorduri 1″ filet inerior
2054 376
■ Coduri articole
Coduri articole
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 9
Accesorii
Pentru productie de apa calda
Vana motorizata de deviatietip R3..BL/LR230A, NR230A Racord cu filet interior, inclusiv servomotor
Tip DN Racord filet kvs 1
R3025-BL2/LR230A 25 Rp 1″ 10.0R3032-BL3/NR230A 32 Rp 1¼″ 15.0
1 Debit in m3/h la o deschidere de 100 % sipierdere de presiune de 1 bar
Service
Punere in functiune
Punerea in functiune prin departamentul de service al Hoval sau printr-o firma specializata autorizata, constituie o premisa pentru acord-area garantiei.
Pentru punerea in functiune si alte sevicii varugam sa va adresati catre Hoval.
6027 411 6027 412
2057 249
Reflex V40Vas intermediar din otel, Pentru presiuni de lucru pana la 10 bar.
Reflex Ø D H h Atip mm mm mm
V 40 409 562 113 R 1″
Ø D
H
h
A
A
■ Date tehnice
10 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Hoval Belaria® SRM (4-16) Hoval Belaria® compact SRM (4-16)Tip SRM (4) SRM (6) SRM (8) SRM (11) SRM (14) SRM (16)• Putere de incalzire A-7W35 2 kW 4.60 5.43 6.40 8.80 11.70 12.10• Putere de incalzire A2W35 2 kW 3.27 4.69 5.80 8.56 10.30 11.70• Putere de incalzire A10W35 2 kW 4.47 6.29 7.39 11.20 14.30 17.50• COP A-7W35 2 2.71 2.93 2.77 2.92 2.75 2.63• COP A2W35 2 4.02 3.80 3.67 3.65 3.45 3.40• COP A10W35 2 5.12 5.23 4.91 4.86 4.71 4.51• Putere de racire A35W18 1 kW 5.90 7.30 8.40 15.10 16.10 16.80• Putere de racire A35W7 1 kW 4.50 5.50 6.40 11.70 12.60 13.10• EER A35W181 3.16 3.20 2.92 3.39 3.01 2.77• EER A35W71 2.22 2.18 1.98 2.78 2.51 2.32Dimensiuni• Unitate exterioara H/W/D mm 735/832/307 1345/900/320• Unitate interioara H/W/D Belaria® SRM mm 890/480/344• Unitate interioara H/W/D Belaria® compact
SRM mm 1732/600/728
Masa• Masa neta a unitatii exterioare kg 54 56 56 113 113 113• Masa neta a unitatii interioare
Belaria® SRM kg 44 48 48 48 48 48Belaria® compact SRM kg 115 126 126 129 129 129
• Masa bruta a unitatii exterioare kg 57 59 59 128 128 128• Masa bruta a unitatii interioare
Belaria® SRM kg 47 51 51 51 51 51Belaria® compact SRM kg 128 140 140 142 142 142
• Compresor ermetic, compresor de viteza variabila• Agent de refrigerare R 410A kg 1.45 1.6 1.6 3.4 3.4 3.4• Ventilator axial, viteza variabila 2 x axial, viteza variabila• Vaporizator conducte de cupru cu aripioare de aluminiu• Tip condensator schimbator de caldura in placi din otel inoxidabil sudat cu cupru• Continut de apa al condensatorului litri 0.9 1.3 1.3 1.0 1.0 1.0• Conexiuni conducte debit/retur R 11/4″ 11/4″ 11/4″ 11/4″ 11/4″ 11/4″• Volum debit maxim m3/h 1.5 2.0 2.0 3.1 3.1 3.1• Volum debit minim m3/h 0.4 0.7 0.7 0.7 0.7 0.7• Presiune operare max. pe partea de incalzire bar 3.0 3.0 3.0 3.0 3.0 3.0• Volum vas de expansiune litri 10 10 10 10 10 10• Continut total de apa Belaria® SRM litri 3 5 5 5 5 5• Continut total de apa Belaria® compact SRM litri 4.4 5.8 5.8 5.5 5.5 5.5• Boiler / Belaria® compact SRM litri 180 260 260 260 260 260• Temperatura maxima apa calda °C 65 65 65 65 65 65• Presiune de operare / Presiune de test bar 8/13 8/13 8/13 8/13 8/13 8/13• Material boiler Otel inoxidabil (EN 1.4521)• Material izolatie termica EPS• Pierderi in regim “stand-by” (EN 12897) kWh/24 h 1.4 1.9 1.9 1.9 1.9 1.9Conexiuni, conducte de refrigerare• Dimensiunea conductei de lichid Inch/mm 1/4 / 6.4 1/4 / 6.4 1/4 / 6.4 3/8 / 9.5 3/8 / 9.5 3/8 / 9.5• Dimensiunea conductei de vapori Inch/mm 5/8 / 15.9 5/8 / 15.9 5/8 / 15.9 5/8 / 15.9 5/8 / 15.9 5/8 / 15.9• Lunigme maxima circuit de refrigerare m 30 30 30 30 30 30• Lungime minima circuit de refrigerare m 3 3 3 3 3 3• Diferenta de inaltime maxima unitate ext./int. 20 20 20 30 30 30• Vezi diagramele pentru valorile de lucru pentru incalzire si racire.Date electrice• Consum de energie maxim in timpul incalzirii• Pompa de caldura kW 2.4 2.6 3.3 4.8 6.2 7.1• Incalzire de urgenta kW 3 2 trepte 3/9 2 trepte 3/9 2 trepte 3/9 2 trepte 3/9 2 trepte 3/9Tensiune• Compresor V 230 230 230 3 x 400 3 x 400 3 x 400• Ventilator V 230 230 230 230 230 230• Incalzire de urgenta V 230 3 kW si 9 kW 3 x 400 Volti• Frecventa Hz 50 50 50 50 50 50• Interval de alimentare +/- 10% +/- 10% +/- 10% +/- 10% +/- 10% +/- 10%Curent de operare maxim• Compresor A 15 15 15 16 16 16• Curent la pornire A 11 11 11 8 8 8• Siguranta A 16T 16T 16T 16T 16T 16T1 Putere de racire si EER in operatie de incarcare totala (Eurovent 6/C003-2006)2 Putere de incalzire si COP in sarcina partiala (EN 14511)
■ Date tehnice
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 11
• Diagramele pentru valorile de lucru pentru incalzire si racire.
Belaria® SRM (4-8)Belaria® compact SRM (4-8)Regim incalzire
25
55
-20-25
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C10 25
30
-15
45
50
Leis
tung
nic
ht
gara
ntie
rt
50
-20-25
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C25
25
55
45
35-15
40
Leis
tung
nic
ht
gara
ntie
rt
25
-20-25
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C35
Leis
tung
nic
ht g
aran
tiert
55
50
-20-25
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C5 25
25
55
45
35-15
40
Leis
tung
nic
ht
gara
ntie
rt
48
-20
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C
25
3525
5350
55
-10
Temperatura exterioara°C Temperatura exterioara°C
Temperatura exterioara°C Temperatura exterioara°C
Temperatura exterioara°C
Tem
pera
tura
tur °
C
Tem
pera
tura
tur °
C
Tem
pera
tura
tur °
C
Tem
epra
tura
tur °
C
Tem
pera
tura
tur °
C
Per
form
anta
nu
este
gar
anta
ta
Per
form
anta
nu
este
gar
anta
ta
Per
form
anta
nu
este
gar
anta
ta
Per
form
anta
nu
este
gar
anta
ta
Belaria® SRM (11-16)Belaria® compact SRM (11-16)Regim incalzire
Belaria® SRM (4)Regim apa calda
Belaria® SRM (6-8)Regim apa calda
Belaria® compact SRM (11-16)Regim apa calda
■ Date tehnice
12 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Belaria® SRM (4-8)Belaria® compact SRM (4-8)Regim racire
Belaria® SRM (11-16)Belaria® compact SRM (11-16)Regim racire
10
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C
5
22
4318
13
10
Vorla
ufte
mpe
ratu
r °C
Aussentemperatur °C
5
22
46Temperatura exterioara °C Temperatura exterioara °C
Tem
pera
tura
tur °
C
Tem
pera
tura
tur °
C
Belaria® compact SRM (4)Regim apa calda
Belaria® compact SRM (6-8)Regim apa calda
Belaria® compact SRM (11-16)Regim apa calda
53
-20
War
mw
asse
rtem
pera
tur °
C
Aussentemperatur °C
25
25
50
35-10
Mit eingebauter Elektroheizung
55
60
Temperatura exterioara °C
Tem
pera
tura
tur °
C
Cu incalzitor electric integrat
45
-20-25
War
mw
asse
rtem
pera
tur °
C
Aussentemperatur °C25
25
50
35-15
40
Leis
tung
nic
ht
gara
ntie
rt
Mit eingebauter Elektroheizung
5
48
55
60
Temperatura exterioara °C
Tem
pera
tura
apa
cal
da °
C
Cu incalzitor electric integrat
Perf
orm
anta
nu
este
gar
anta
ta
50
-20-25
War
mw
asse
rtem
pera
tur °
C
Aussentemperatur °C25
25
45
35-15
40
Leis
tung
nic
ht
gara
ntie
rt
Mit eingebauter Elektroheizung60
55
Temperatura exterioara °C
Tem
epra
tura
apa
cal
da °
C
Cu incalzitor electric integrat
Perf
orm
anta
nu
este
gar
anta
ta
■ Date tehnice
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 13
Rezervor expansiune presiune
Unitatea interioara este echipata cu un vas de expansiune (plat) cu un volum de 10l, presiune de preincarcare 1 bar.Setari din fabrica
Pre-incarcare bar 0.5 0.8 1.0 1.2 1.5 1.8 2.1Capacitate l 5.5 4.5 4.0 3.5 2.5 2.0 0.7Inaltime maxima posibila a sistemului Hp2 m 2 5 7 9 12 15 18
1 Pre-incarcare = inaltimea sistemului + 0.3 bar. Pre-incarcarea trebuie ajustata la inaltimea sistemului.2 Presiunea sistemului Hp = presiune hidrostatica a sistemului, de exemplu inaltimea de la centrul vasului pana la cel mai inalt punct de aerisire al sistemului.
Vn = VA x f x X (litri)
Vn = volum expansiune (litri)VA = continut al sistemului la + 10 °Cf = factor expansiune termica (45°), f = 0.01X = factor adaugat, X = 3
Sistem VA Vn
Continut al sistemului (sistem incalzire prin pardoseala) 5 kW 120 l 3.6 l cantitate expansiune6 kW 140 l 4.2 l cantitate expansiune7 kW 160 l 4.8 l cantitate expansiune8 kW 180 l 5.4 l cantitate expansiune9 kW 200 l 6.0 l cantitate expansiune
Hoval Belaria® SRMHoval Belaria® compact SRM• Nivel presiune acustica - nivel putere acustica3
Nivelele de presiune acustica indicate in continuare, se aplica doar daca unitatea exterioara este pozitionata pe fatada unei cladiri. Aceste valori sunt reduse cu 3 dB daca unitatea exterioara este liber asezata. In cazul instalarii intr-un colt, nivelul de presiune acustica creste cu 3 dB.Nivelul de presiune acustica depinde de locul de masurare intr-un camp acustic si masoara intensitatea sunetului in acest punct. In contrast, nivelul de putere acustica este o caracteristica a sursei sunetului, asa ca nu se schimba odata cu distanta; aceasta masoara totalitatea puterii acustice a sursei relevante, radiata in toate directiile.
Sunet structura portanta
Unitatea interioara trebuie sa fie atasata de un perete cu un distantier de izolare fonica cu manson. Bazele si consolele unitatii exterioara trebuie sa fie ridicate/instalate cu suporti antivi-branti contra structurii carcasei.
Belaria® SRM (4) (6) (8) (11) (14) (16) Unitate exterioara• Nivel putere acustica in timpul incalzirii 2, 3 dB(A) 54 55 56 56 56 57• Nivel presiune acustica in timpul incallzirii
la 5 m 1, 2, 3dB(A) 35 36 37 37 37 38
• Nivel presiune acustica in timpul incalzirii la 10 m 1, 2, 3
dB(A) 29 30 31 31 31 32
Unitate interioara• Nivel presiune acustica la 1 m dB(A) 28 28 28 33 33 33
1 Valorile de presiune acustica indicate se aplica daca unitatea exterioara este pozitionata pe fatada cladirii. Aceste valori sunt reduse cu 3 dB. daca unitatea exterioara este de sine statatoare. In cazul instalarii intr-un colt, valorile de presiune acustica se maresc cu 3 dB.
2 Valorile acustice se aplica in modul silentios. Aceste valoril sunt marite la o incarcare maxima, cu 4 dB (A) pentru Belaria SRM (4-8) si cu 6 dB(A) pentru Belaria SRM (11-16).
3 Valorile acustice sunt valabile cu un vaporizator curat. Aceste valori sunt depasite temporar, inaintea degivrarii.
Daca capacitatea vasului de expan-siune instalat nu este suficienta, un vas aditional trebuie instalat in afara unitatii.
■ Date tehnice
14 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Curba caracteristica pompa Belaria® SRM (4-8)
0 161412108642 282624222018 32300
5
50
45
40
35
30
25
20
15
10
70
65
60
55
75
ausschliesslichBelaria SRM (8)
Betriebsbereich
Wassermenge durch das Gerät (Liter/min.)
Exte
rner
sta
tisch
er D
ruck
(kPa
)
0 161412108642 282624222018 32300
5
50
45
40
35
30
25
20
15
10
70
65
60
55
75
Betriebsbereich
Wassermenge durch das Gerät (Liter/min.)
Exte
rner
sta
tisch
er D
ruck
(kPa
)
Min. WassermengeElektr. Notheizung
340 161412108642 282624222018 32300
5
50
45
40
35
30
25
20
15
10
70
65
60
55
75
Betriebsbereich
Wassermenge durch das Gerät (Liter/min.)
Exte
rner
sta
tisch
er D
ruck
(kPa
)
Min. WassermengeElektr. Notheizung
0 2010 4030 500
100
80
60
20
140
120
Wassermenge durch das Gerät (Liter/min.)
Exte
rner
sta
tisch
er D
ruck
(kPa
)
5 352515 45
Min. WassermengeElektr. Notheizung
Betriebsbereich
90
40
70
50
30
10
130
110
Curba caracteristica pompa Belaria® SRM (11-16)
Curba caracteristica pompa Belaria® compact SRM (6,8)Curba caracteristica pompa Belaria® compact SRM (4)
Curba caracteristica pompa Belaria® compact SRM (11-16)
0 403530252015105 605550450
100
80
60
40
20
120
Min. WassermengeElektr. Notheizung
Wassermenge durch das Gerät (Liter/min.)
Exte
rner
sta
tisch
er D
ruck
(kPa
)
Dis
poni
bilit
ate
inal
time
de p
ompa
re (k
Pa)
Dis
poni
bilit
ate
inal
time
de p
ompa
re (k
Pa)
Dis
poni
bilit
ate
inal
time
de p
ompa
re (k
Pa)
Dis
poni
bilit
ate
inal
time
de p
ompa
re (k
Pa)
Dis
poni
bilit
ate
inal
time
de p
ompa
re (k
Pa)
Debit apa prin unitate (litrii/min) Debit apa prin unitate (litrii/min)
Debit apa prin unitate (litrii/min))
Debit apa prin unitate (litrii/min) Debit apa prin unitate (litri/min)
Interval de operare
Raza de operare
Interval de operare
Interval de operare
Debit minim de apaIncalzire electrica de urgenta
Debit minim de apaIncalzire electrica de urgenta
Debit minim de apaIncalzire electrica de urgenta
Debit minim de apaIncalzire electrica de urgenta
doar Belaria® SRM (8)
■ Date tehnice
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 15
Date de performanta - incalzire
Observati intreruperile zilnice de energie!vezi Proiectare.
Hoval Belaria® SRM (4-8)Hoval Belaria® compact SRMPutere de incalzire maxima ce permite pierderile de la degivrare
Tip (4) (6) (8)tVL tF QHP P COP QHP P COP QHP P COP°C °C kW kW kW kW kW kW
30
-20 2.3 1.5 1.48 3.2 1.9 1.67 3.8 2.4 1.57-15 3.3 1.5 2.16 4.1 1.9 2.22 5.0 2.4 2.08-10 4.2 1.5 2.73 5.0 1.8 2.72 6.0 2.3 2.55
-7 4.7 1.5 3.07 5.5 1.8 3.03 6.6 2.3 2.84-2 4.8 1.4 3.56 6.2 1.8 3.44 7.4 2.3 3.242 4.9 1.2 4.12 6.6 1.8 3.74 7.9 2.3 3.517 5.3 1.0 5.30 8.5 1.8 4.61 10.2 2.4 4.33
12 5.3 0.8 6.87 9.2 1.8 5.05 11.0 2.3 4.7615 5.5 0.8 7.20 10.0 1.8 5.60 12.0 2.3 5.2820 6.0 0.7 8.14 11.5 1.8 6.54 13.8 2.3 6.14
35
-20 2.2 1.7 1.29 3.1 2.1 1.47 3.7 2.7 1.38-15 3.1 1.7 1.80 4.0 2.1 1.94 4.8 2.6 1.82-10 4.0 1.7 2.36 4.8 2.0 2.37 5.8 2.6 2.23
-7 4.6 1.7 2.71 5.3 2.0 2.64 6.4 2.6 2.48-2 4.8 1.5 3.13 6.1 2.0 3.10 7.3 2.5 2.922 4.8 1.3 3.59 6.4 1.9 3.37 7.7 2.4 3.177 5.1 1.1 4.57 8.4 2.0 4.20 10.0 2.5 3.94
12 5.2 0.9 6.05 9.0 2.0 4.60 10.8 2.5 4.3215 5.3 0.8 6.53 9.8 1.9 5.12 11.7 2.4 4.8020 5.9 0.8 7.22 11.2 1.9 5.99 13.5 2.4 5.66
40
-20 2.2 1.9 1.15 2.9 2.4 1.24 3.5 3.0 1.16-15 3.2 1.9 1.67 3.8 2.3 1.64 4.5 2.9 1.54-10 4.0 1.9 2.12 4.7 2.3 2.10 5.7 2.9 1.98
-7 4.5 1.9 2.40 5.3 2.2 2.38 6.4 2.8 2.24-2 4.6 1.7 2.71 6.0 2.1 2.82 7.3 2.7 2.662 4.7 1.5 3.05 6.2 2.1 3.00 7.4 2.6 2.837 5.0 1.3 3.82 8.2 2.2 3.80 9.8 2.7 3.58
12 5.1 1.0 5.00 8.7 2.1 4.14 10.5 2.7 3.8815 5.2 1.0 5.27 9.5 2.1 4.55 11.4 2.7 4.2720 5.7 1.0 5.97 10.9 2.1 5.29 13.0 2.6 4.97
45
-20 2.2 2.1 1.01 2.8 2.5 1.10 3.3 3.2 1.03-15 2.9 2.2 1.36 3.6 2.5 1.47 4.3 3.1 1.39-10 3.8 2.1 1.81 4.6 2.4 1.91 5.5 3.1 1.80
-7 4.3 2.1 2.10 5.2 2.4 2.19 6.3 3.0 2.06-2 4.5 1.9 2.41 5.7 2.3 2.50 6.8 2.9 2.342 4.6 1.7 2.71 6.1 2.2 2.77 7.3 2.8 2.617 4.9 1.4 3.40 8.0 2.3 3.43 9.5 3.0 3.22
12 4.9 1.2 4.06 8.4 2.3 3.66 10.1 2.9 3.4415 5.1 1.2 4.22 9.1 2.3 4.03 10.9 2.9 3.7820 5.5 1.1 4.88 10.4 2.2 4.66 12.5 2.9 4.39
50
-20 2.1 2.3 0.89 2.7 2.6 1.05 3.3 3.2 1.02-15 2.9 2.3 1.22 3.5 2.5 1.40 4.2 3.2 1.32-10 3.6 2.3 1.57 4.5 2.5 1.80 5.3 3.2 1.69
-7 4.1 2.3 1.78 5.0 2.5 2.04 6.0 3.1 1.91-2 4.3 2.1 2.03 5.6 2.4 2.35 6.7 3.0 2.222 4.4 1.9 2.29 6.0 2.3 2.61 7.2 2.9 2.457 4.7 1.7 2.83 7.5 2.4 3.14 9.0 3.1 2.94
12 4.7 1.5 3.22 8.0 2.4 3.35 9.6 3.1 3.1515 4.8 1.4 3.47 8.7 2.4 3.65 10.4 3.0 3.4320 5.2 1.3 3.92 9.9 2.4 4.19 11.9 3.0 3.94
55
-15 2.6 2.4 1.08 3.3 2.6 1.28 3.9 3.3 1.20-10 3.4 2.4 1.39 4.1 2.5 1.61 4.9 3.2 1.52
-7 3.8 2.4 1.58 4.6 2.5 1.82 5.5 3.2 1.71-2 4.1 2.2 1.85 5.1 2.5 2.09 6.2 3.1 1.962 4.3 2.0 2.11 5.5 2.4 2.29 6.6 3.1 2.157 4.5 1.8 2.58 7.1 2.5 2.85 8.5 3.2 2.69
12 4.6 1.5 3.01 7.5 2.5 3.04 9.0 3.2 2.8715 4.6 1.5 3.13 8.1 2.5 3.30 9.8 3.2 3.1020 4.9 1.5 3.37 9.3 2.5 3.77 11.2 3.2 3.55
tVL = Temperatura tur incalzire (°C)tF = Temperatura exterioara (°C)QHP = Putere incalzire la incarcare maxima (kW), masurata conform standardului EN 14511P = Energie consumata (kW) a unitatii per total, incl. pompa integrata, masurata conform standardului EN 14511COP = Coeficient de performanta a unitatii per total, masurata conform standardului EN 14511
■ Date tehnice
16 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Date performanta - incalzire
Observati intreruperile zilnice de energie!vezi Proiectare
Hoval Belaria® SRM (11-16)Hoval Belaria® compact SRM (11-16)Putere de incalzire maxima ce permite pierderile de la degivrare
Tip (11) (14) (16)tVL tF QHP P COP QHP P COP QHP P COP°C °C kW kW kW kW kW kW
30
-20 7.3 3.7 1.98 9.0 4.9 1.82 9.6 5.6 1.71-15 8.8 3.9 2.25 10.3 5.0 2.08 10.6 5.8 1.84-10 9.0 3.4 2.63 11.3 4.7 2.44 11.8 5.3 2.25
-7 9.1 3.1 2.91 11.9 4.5 2.68 12.6 5.0 2.53-2 9.6 2.9 3.29 11.4 3.7 3.06 12.1 4.2 2.862 9.5 2.6 3.71 11.2 3.3 3.46 11.7 3.7 3.217 11.9 2.3 5.21 15.1 3.1 4.92 16.6 3.5 4.81
12 12.9 2.2 5.82 16.0 3.0 5.38 17.3 3.4 5.1615 14.0 2.2 6.36 17.3 3.0 5.85 18.8 3.4 5.6020 15.9 2.1 7.43 19.8 2.9 6.75 21.5 3.3 6.43
35
-20 7.3 4.1 1.80 8.9 5.3 1.70 9.7 5.9 1.64-15 8.7 4.3 2.03 10.2 5.3 1.91 10.6 6.2 1.71-10 8.8 3.8 2.34 11.1 5.0 2.20 11.7 5.7 2.04
-7 8.8 3.4 2.57 11.7 4.9 2.40 12.3 5.4 2.28-2 9.2 3.2 2.88 11.1 4.1 2.72 11.8 4.6 2.552 9.1 2.8 3.20 10.9 3.6 3.05 11.4 4.0 2.857 11.4 2.6 4.46 14.6 3.3 4.36 16.1 3.7 4.30
12 12.3 2.5 4.98 15.4 3.3 4.70 16.7 3.7 4.5415 13.3 2.5 5.44 16.7 3.3 5.11 18.2 3.7 4.9220 15.2 2.4 6.33 19.0 3.2 5.88 20.8 3.7 5.64
40
-20 7.3 4.5 1.63 8.8 5.6 1.57 9.6 6.3 1.52-15 8.5 4.7 1.82 9.7 5.6 1.75 9.9 6.2 1.59-10 8.5 4.1 2.07 10.8 5.4 1.99 11.2 6.0 1.87
-7 8.5 3.8 2.26 11.4 5.3 2.14 12.0 5.9 2.05-2 8.8 3.5 2.51 10.8 4.5 2.41 11.5 5.1 2.272 8.6 3.1 2.75 10.5 3.9 2.69 11.1 4.4 2.527 11.2 2.8 3.95 13.9 3.7 3.74 15.5 4.2 3.71
12 12.2 2.8 4.42 14.7 3.6 4.07 16.1 4.1 3.9715 13.2 2.7 4.83 16.0 3.6 4.43 17.5 4.1 4.3020 15.1 2.7 5.60 18.3 3.6 5.10 20.0 4.1 4.94
45
-20 6.8 4.7 1.44 7.2 5.6 1.28 7.7 6.3 1.22-15 7.8 4.7 1.67 8.9 5.6 1.60 9.6 6.3 1.53-10 8.0 4.3 1.87 10.2 5.6 1.83 10.7 6.3 1.71
-7 8.2 4.1 2.01 11.0 5.6 1.97 11.4 6.3 1.82-2 8.6 3.8 2.25 10.5 4.8 2.17 11.4 5.5 2.062 8.9 3.4 2.58 10.7 4.3 2.45 11.4 4.8 2.397 11.0 3.2 3.48 13.6 4.1 3.29 15.2 4.6 3.29
12 12.0 3.1 3.89 14.4 4.0 3.59 15.8 4.5 3.5115 13.1 3.1 4.24 15.6 4.0 3.90 17.1 4.5 3.8120 15.0 3.0 4.93 17.9 4.0 4.48 19.6 4.5 4.35
50
-15 6.9 4.7 1.47 8.2 5.6 1.47 8.8 6.3 1.40-10 7.6 4.6 1.64 9.2 5.6 1.65 9.7 6.3 1.55
-7 8.0 4.6 1.74 9.8 5.6 1.75 10.3 6.3 1.63-2 8.6 4.3 2.00 10.2 5.2 1.95 10.4 5.8 1.812 8.4 3.8 2.21 10.3 4.7 2.19 11.0 5.4 2.047 10.7 3.5 3.03 13.4 4.6 2.93 14.5 5.1 2.86
12 11.7 3.5 3.38 14.2 4.4 3.19 15.1 5.0 3.0515 12.7 3.5 3.69 15.4 4.5 3.46 16.4 5.0 3.3120 14.2 3.4 4.16 17.2 4.4 3.87 18.8 5.0 3.78
55
-15 4.5 4.8 0.94 6.6 6.2 1.06 7.0 7.1 0.98-10 6.3 4.7 1.34 8.2 5.8 1.41 8.6 6.6 1.31
-7 7.1 4.7 1.52 8.7 5.6 1.56 9.2 6.3 1.46-2 7.8 4.6 1.70 8.9 5.2 1.70 9.3 5.8 1.622 7.6 4.2 1.81 9.8 5.2 1.90 10.3 5.8 1.787 10.0 3.9 2.54 12.7 5.1 2.52 13.9 5.6 2.48
12 11.0 3.9 2.84 13.5 4.9 2.75 14.5 5.5 2.6415 12.0 3.9 3.11 14.7 4.9 2.99 15.8 5.5 2.8620 13.5 3.8 3.51 16.4 4.9 3.33 18.1 5.5 3.27
tVL = Temperatura tur incalzire (°C)tF = Temperatura exterior (°C)QHP = Putere incalzire la incarcare maxima (kW), masurata conform standardului EN 14511P = Energie consumata (kW) a unitatii per total, incl. pompa integrata, masurata conform standardului EN 14511COP = Coeficient de performanta a unitatii per total, masurata conform standardului EN 14511
■ Date tehnice
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 17
Date de performanta - racire
Observati intreruperile zilnice de energie!vezi Proiectare.
Hoval Belaria® SRM (4-8)Hoval Belaria® compact SRM (4-8)Putere maxima de racire
Tip (4) (6) (8)tVL tF QHP P EER QHP P EER QHP P EER°C °C kW kW kW kW kW kW
7
20 6.1 1.5 3.94 7.6 2.3 3.23 8.8 3.0 2.9525 5.6 1.7 3.27 6.9 2.4 2.90 8.0 3.0 2.6430 5.0 1.9 2.70 6.2 2.4 2.54 7.2 3.1 2.3135 4.5 2.0 2.22 5.5 2.5 2.18 6.4 3.2 1.9840 3.5 1.8 1.90 3.8 2.2 1.69 4.1 2.5 1.6545 2.9 1.7 1.69 2.8 2.1 1.34 2.8 2.1 1.34
10
20 6.5 1.5 4.30 8.2 2.3 3.57 9.5 2.9 3.2625 5.9 1.7 3.58 7.5 2.3 3.22 8.7 3.0 2.9330 5.4 1.8 2.96 6.7 2.4 2.82 7.8 3.0 2.5735 4.9 2.0 2.46 5.9 2.5 2.42 6.9 3.1 2.2140 3.8 1.8 2.13 4.3 2.2 1.94 4.6 2.4 1.8945 3.2 1.7 1.90 3.2 2.0 1.59 3.2 2.0 1.59
13
20 6.8 1.5 4.65 8.8 2.2 3.96 10.2 2.9 3.5925 6.3 1.6 3.88 8.1 2.3 3.57 9.4 2.9 3.2630 5.8 1.8 3.25 7.2 2.3 3.12 8.4 3.0 2.8535 5.3 2.0 2.70 6.4 2.4 2.69 7.4 3.0 2.4540 4.2 1.8 2.37 4.8 2.2 2.21 5.2 2.4 2.1545 3.5 1.6 2.13 3.8 2.0 1.88 3.8 2.0 1.88
15
20 7.0 1.4 4.87 9.3 2.2 4.20 10.8 2.8 3.8425 6.5 1.6 4.10 8.5 2.2 3.82 9.9 2.8 3.4830 6.0 1.8 3.43 7.6 2.3 3.35 8.8 2.9 3.0535 5.5 1.9 2.88 6.7 2.3 2.88 7.8 3.0 2.6340 4.4 1.7 2.53 5.1 2.1 2.41 5.6 2.4 2.3445 3.7 1.6 2.29 4.2 2.0 2.09 4.2 2.0 2.09
18
20 7.4 1.4 5.26 10.0 2.1 4.66 11.6 2.7 4.2525 6.9 1.6 4.43 9.1 2.2 4.22 10.6 2.8 3.8430 6.4 1.7 3.75 8.2 2.2 3.71 9.5 2.8 3.3935 5.9 1.9 3.16 7.3 2.3 3.20 8.4 2.9 2.9240 4.7 1.7 2.81 5.7 2.1 2.75 6.2 2.3 2.6645 4.0 1.6 2.55 4.8 2.0 2.44 4.8 2.0 2.44
22
20 8.0 1.3 5.96 11.0 2.1 5.32 12.8 2.6 4.8525 7.5 1.5 5.05 10.1 2.1 4.87 11.8 2.7 4.4430 7.0 1.6 4.26 9.1 2.1 4.27 10.5 2.7 3.9035 6.5 1.8 3.65 8.0 2.2 3.70 9.3 2.8 3.3640 5.2 1.6 3.27 6.7 2.0 3.28 7.1 2.3 3.1645 4.5 1.5 3.00 5.8 2.0 2.99 5.8 2.0 2.99
tVL = Temperatura tur incalzire (°C)tF = Temperatura exterior (°C))QHP = Putere incalzire la incarcare maxima (kW), masurata conform standardului EN 14511P = Energie consumata (kW) a unitatii per total, incl. pompa integrata, masurata conform standardului EN 14511EER = Coeficient de performanta a unitatii per total, masurata conform standardului EN 14511
■ Date tehnice
18 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Date performanta - racire
Observati intreruperile zilnice de energie!vezi Inginerie.
Hoval Belaria® SRM (11-16)Putere maxima de racire
Tip (11) (14) (16)tVL tF QHP P EER QHP P EER QHP P EER°C °C kW kW kW kW kW kW
7
20 13.0 3.2 4.10 13.9 3.8 3.67 14.6 4.3 3.3825 12.9 3.5 3.70 13.8 4.1 3.34 14.5 4.7 3.0830 12.4 3.8 3.25 13.3 4.5 2.94 14.0 5.2 2.7135 11.7 4.2 2.78 12.6 5.0 2.51 13.1 5.7 2.3240 10.7 4.7 2.31 11.1 4.8 2.32 11.6 5.4 2.1545 9.5 5.1 1.86 9.9 5.3 1.87 9.9 5.3 1.87
10
20 13.8 3.2 4.31 14.9 3.9 3.88 15.7 4.4 3.5725 13.7 3.5 3.88 14.9 4.2 3.53 15.6 4.8 3.2430 13.2 3.9 3.40 14.3 4.6 3.10 15.0 5.3 2.8635 12.4 4.3 2.91 13.5 5.1 2.65 14.1 5.8 2.4540 11.4 4.7 2.42 12.0 4.9 2.46 12.5 5.5 2.2745 10.1 5.2 1.95 10.6 5.4 1.98 10.6 5.4 1.98
13
20 15.2 3.2 4.68 16.5 3.9 4.20 17.2 4.5 3.8425 15.0 3.6 4.22 16.3 4.3 3.80 17.1 4.9 3.4930 14.5 3.9 3.69 15.7 4.7 3.35 16.5 5.4 3.0735 13.7 4.3 3.15 14.8 5.2 2.86 15.5 5.9 2.6440 12.5 4.8 2.62 13.2 5.0 2.65 13.7 5.6 2.4545 11.0 5.5 2.02 11.0 5.5 2.02 11.0 5.5 2.02
15
20 16.1 3.3 4.94 17.5 4.0 4.41 18.3 4.5 4.0325 16.0 3.6 4.44 17.3 4.3 3.99 18.1 5.0 3.6530 15.4 4.0 3.89 16.7 4.8 3.51 17.5 5.4 3.2235 14.5 4.4 3.32 15.7 5.2 3.00 16.4 6.0 2.7640 13.3 4.8 2.76 14.0 5.0 2.78 14.5 5.7 2.5745 11.4 5.3 2.14 11.4 5.3 2.14 11.4 5.3 2.14
18
20 17.8 3.3 5.40 19.0 4.0 4.71 19.9 4.6 4.2925 17.2 3.6 4.73 18.4 4.4 4.16 19.2 5.1 3.7930 16.3 4.0 4.04 17.4 4.9 3.58 18.2 5.5 3.2835 15.1 4.4 3.39 16.1 5.3 3.01 16.8 6.1 2.7740 13.6 4.9 2.78 14.1 5.1 2.75 14.6 5.8 2.5345 11.5 4.9 2.35 11.5 4.9 2.35 11.5 4.9 2.35
22
20 19.8 3.3 5.93 21.2 4.1 5.14 22.2 4.8 4.6525 19.2 3.7 5.20 20.5 4.5 4.52 21.4 5.2 4.1130 18.2 4.1 4.44 19.4 5.0 3.90 20.3 5.7 3.5535 16.8 4.5 3.72 17.9 5.5 3.28 18.7 6.2 3.0040 15.2 5.0 3.05 15.7 5.2 3.01 16.3 5.9 2.7645 12.1 4.4 2.76 12.1 4.4 2.76 12.1 4.4 2.76
tVL = Temperatura tur incalzire (°C)tF = Temperatura exterioara (°C)QHP = Putere incalzire la incarcare maxima (kW), masurata conform standardului EN 14511P = Energie consumata (kW) a unitatii per total, incl. pompa integrata, masurata conform standardului EN 14511EER = Coeficient de performanta a unitatii per total, masurata conform standardului EN 14511
■ Dimensiuni
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 19
Hoval Belaria® SRM (4-16) Unitate interioara(Dimensiuni in mm)
55344 260110
381
15 450380
131
1548
480
881
890
868
788
867
38 41
74
22
90
R210
71
60
5
1
2
34
5
6
100 100
200
500
1150
1 Tur incalzire Rp 1¼″2 Retur incalzire Rp 1¼″3 Circuit frigorific lichid
Belaria® SRM (4-8) ¼″ (6.35 mm)Belaria® SRM (11-16) ⅜″ (9.5 mm)
4 Circuit frigorific vapori ⅝″ (15.9 mm)5 Gauri montare6 Supapa de siguranta Rp ½″
Spatiu necesar pentru mentenanta si ventilatieUnitate interioara(Dimensiuni in mm)
■ Dimensiuni
20 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
R210
1732
1744
1762
761
728
300
600
193 52
301150141 223
4507560
111
45
115
199
7
8
3 6 2 1 5 4
Hoval Belaria® compact SRM (4-16) unitate interioara(Dimensiuni in mm)
1 Circuit frigorific vapori ⅝″ (15.9 mm)2 Circuit frigorific lichid
Belaria® SRM (4-8) ¼″ (6.35 mm)Belaria® SRM (11-16) ⅜″ (9.5 mm)
3 Tur incalzire R 1¼″4 Retur incalzire R 1¼″5 Conexiune apa rece R 1″6 Conexiune apa calda R 1″7 Supapa de siguranta8 Scurgere de condens
(la racire)
Spatiu necesar pentru mentenanta si ventilatie unitate interioara(Dimensiuni in mm)
min. 300
min. 500
min. 100 min. 100
Piulita olandeza
■ Dimensiuni
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 21
Hoval Belaria® SRM (4-8), Hoval Belaria® compact SRM (4-8) unitate exterioara(Dimensiuni in mm)
Spatiu necesar pentru Hoval Belaria® SRM, Belaria® compact SRM unitate exterioara fara acoperis(Dimensiuni in mm)
1 Conexiuni racorduri agent frigorific2 Senzor temperatura exterior3 Gauri pentru hotzsuruburi M8 sau M10
min. 100
min
.150
≥ 300
min
. 150
≥ 300
Spatiu necesar pentru Hoval Belaria® SRM, Belaria® compact SRM, unitate exterioara cu acoperis(Dimensiuni in mm)
min. 200 ≥ 300
min
. 200
min
. 200
≥ 300
Dimensiunile acoperisului de protectie pentru unitatea exterioara.
Belaria® SRMtip
B T
(4-8) 1102 577
Trebuie sa fie un spatiu adecvat pentru evacuare (aprox. 1 m) pentru a opri traseul de aer rece.Unitatea exterioara trebuie sa fie protejata impotriva caderii masive de zapada. Daca este necesar, acoperiti-o (de exemplu acop-eris, vezi Accesorii)Unitatea exterioara trebuie sa fie pozitionata vertical la cel putin 250 mm intaltime. Sub unitate trebuie sa fie pietris, ca sa se elimine acolo condensul (vezi instructiuni baza).
1
22
►
►
735
3
3
■ Dimensiuni
22 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Spatiu necesar
Unitatea exterioara trebuie atasata de baza/fundatie cu suruburi 4 x M8 si dibluri pentru beton! Vezi accesorii!
Indicatii pentru suporti fundatie pentru Belaria® SRM (4-8), Belaria® compact SRM (4-8)(Dimensiuni in mm)
Instalare in gradina
Instalalare pe o suprafata stabila (lespede pavaj, beton, asfalt)
735
580
330
ca.450
430150
ca. 5
00ca
. 250
je n
ach
mög
liche
r Sch
neeh
öhe
Sickerbettgrosse SteineØ ca. 150 mm
Masse in mm
Beton
100
Dimensiuni in mm
Beton
In fu
nctie
de
stra
tul d
e za
pada
Strat de pietrisPietre mari
ø aprox. 150 mm
apro
x. 5
00
Aprox. 450
735
580
330
ca.450
430150
ca. 2
50
je n
ach
mög
liche
r Sch
neeh
öhe
Kondensatwasser muss abfliessen
können
Masse in mm
Beton
100
Condensul trebuie sa se poata scurge
In fu
nctie
de
stra
tul d
e za
pada
Beton
Dimensiuni in mm
Aprox. 450
apro
x.
250
■ Dimensiuni
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 23
Spatiu necesar
• Prevenirea transmiterii sunetului in structura acoperisului este foarte impor-tanta. Ar putea fi necesara consultanta de specialitate, in functie de design-ul specific al acoperisului.
• Unitatea exterioara nu trebuie instalata deasupra dormitoarelor!
• Unitatea exterioara trebuie atasata la baza folosind suporti antivibranti si dibluri de beton! Vezi accesorii.
• Unitatea exterioara trebuie protejata impotriva ninsorii masive. Daca este nec-esar, acoperiti-o.
• Condensul trebuie sa fi inlaturat de la baza astfel incat sa nu inghete.
• Atentie la sarcina maxima permisa pe acoperis! (Masa unitatii, baza de beton si orice cantitate de zapada).
Indicatii postament pentru Belaria® SRM (4-8), Belaria® compact SRM (4-8)(Dimensiuni in mm)
Instalare pe acoperis terasa
735
580
330
ca.600
430150
ca. 2
50
je n
ach
mög
liche
r Sch
neeh
öhe
Kondensatwasser muss abfliessen
können
Masse in mm
Beton
100
vibrations-absorbierendes
Material
4 Sc
hwin
gung
sele
men
te M
8
Aprox. 600
Material absorbant
vibratii
4 s
upor
ti an
tivib
rant
i M8
Condensul trebuie sa se poata scurge
In fu
nctie
de
stra
tul d
e za
pada
Dimensiuni in mm
apro
x.
250 Beton
■ Dimensiuni
24 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Spatiu necesarHoval Belaria® SRM (11-16), Hoval Belaria® compact SRM (11-16) unitate exterioara(Dimensiuni in mm)
Trebuie sa fie un spatiu adecvat pentru evacu-are (aprox. 1 m) pentru a opri traseul de aer rece.Unitatea exterioara trebuie protejata impotriva caderii masive de zapada. Daca este necesar, acoperiti-o.Unitatea exterioara trebuie sa fie pozitionata vertical la cel putin 250mm intaltime. Sub unitate trebuie sa fie pietris, ca sa se elimine acolo condensul (vezi instructiuni baza).
Spatiu necesar pentru Belaria® SRM, Belaria® compact SRM unitate exterioara fara acoperis(Dimensiuni in mm)
min. 100
min
.150
≥ 300
min
. 150
≥ 300
Spatiu necesar pentru Belaria® SRM, Belaria® compact SRM unitate exterioara cu acoperisDimensiuni in mm)
min. 200 ≥ 300
min
. 200
min
. 200
≥ 300
Dimensiuni ale acoperisului protector pen-tru unitatea exterioara
tip Belaria® SRM B T
(11-16) 1180 660
5943
9440
148
1319
1345
24
423
430
54
142
19
182 154 15960
61
320
3030
620 140140
36
1671
99
558454
95
8960
52
35
6780
145
30900
95
89
223
55
350
(345 ~
355)
7
3
2
4
1
65
765
765
8 5
1 Racord vapori refrigerant2 Racord lichid refrigerant3 Deschidere pentru intretinere (sub acoperis)4 Conexiune electrica (in cutia de control)5 Racorduri incarcare refrigerant6 Intrare pentru alimentare electrica7 Intrare pentru comunicare8 Iesire condens
■ Dimensiuni
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 25
Spatiu necesarIndicatii postament pentru Belaria® SRM, Belaria® compact SRM (11-16)(Dimensiuni in mm)
Instalare in gradina
Instalare pe o suprafata stabila(lespede de pavaj, beton, asfalt)
Unitatea exterioara trebuie asezata pe so-clu cu holtzsuruburi 4 x M8 si dibluri! Vezi accesorii.
In cazul in care unitatea exterioara este su-pusa unor vanturi puternice, soclul trebuie extins pana la 700 mm. Se vor monta cabluri de ancorare
1345
620
350
ca.500
470150ca
. 500
> 25
0
je n
ach
mög
liche
r Sch
neeh
öhe
Sickerbettgrosse SteineØ ca. 150 mm
Masse in mm
Beton
Dimensiuni in mm
Beton
In fu
nctie
de
stra
tul d
e za
pada
Strat pietrispietre mari
ø aprox. 150 mm
appr
ox. 5
00
Aprox. 500
1345
620
350
ca.500
470150
> 25
0
je n
ach
mög
liche
r Sch
neeh
öhe
Kondenswassermuss abfliessen
können
Masse in mm
Beton
Dimensiuni in mm
BetonCondensul
trebuie sa se poata scurge
In fu
nctie
de
stra
tul d
e za
pada
Aprox. 500
■ Dimensiuni
26 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Spatiu necesar
• Prevenirea transmiterii sunetului in structura acoperisului este foarte impor-tanta. Ar putea fi necesara consultanta de specialitate, in functie de design-ul specific al acoperisului.
• Unitatea exterioara nu trebuie instalata deasupra dormitoarelor!
• Unitatea exterioara trebuie atasata la baza folosind suporti antivibranti si dibluri de beton! Vezi accesorii.
• Unitatea exterioara trebuie protejata impotriva ninsorii masive. Daca este nec-esar, acoperiti-o.
• Condensul trebuie sa fi inlaturat de la baza astfel incat sa nu inghete.
• Atentie la sarcina maxima permisa pe acoperis! (masa unitatii, baza de beton si orice cantitate de zapada).
• Daca unitatea exterioara exte expusa la vanturi puternice, bazele trebuie extinse cu aproximativ 700mm si cablurile de ancorare reglate. Trebuie instalate deflec-toare de vant.
Indicatii postament pentru Belaria® SRM, Belaria® compact SRM (11-16)(Dimensiuni in mm)
Instalarea pe un acoperis plat
1345
620
350
ca.700
470150
> 25
0
je n
ach
mög
liche
r Sch
neeh
öhe
Kondenswassermuss abfliessen
können
Masse in mm
Sollt
e es
nöt
ig s
ein,
ein
kip
pen
der A
usse
nein
heit
zu v
erhi
nder
n,si
nd H
alte
seile
anz
ubrin
gen
4 Sc
hwin
gung
sele
men
te M
8
vibrations-absorbierendes
Material
Beton
Dimensiuni in mm
BetonCondensul trebuie sa se poata scurge
Aprox. 700
In fu
nctie
de
stra
tul d
e za
pada
4 su
porti
ant
ivib
rant
i M8
In c
azul
in c
are
trebu
ie p
reve
nita
in
clin
area
uni
tatii
ext
erio
are,
treb
uie
inst
alat
e ca
blur
i de
anco
rare
.
Material absorbant
vibratii
■ Proiectare
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 27
Cerinte si directiveSunt valabile cerintele generale si directivele din capitolul Inginerie.
ConfigurareComentarii generale• Distanta dintre unitatea interioara si unitatea
exterioara trebuie sa fie cat mai scurta. Doar o conectare de lungime scurta si simpla a conductelor de refrigerare garanteaza o eficienta a costurilor.
• Lungimea minima pentru lconducte dintre unitatea exterioara si unitatea interioara este de 3m, conductele nu trebuie sa fie mai scurte de 3m. Lungimea maxima permisa a conductelor dintre unitatea exterioara si unitatea interioara este de 30m, aceasta distanta nu trebuie depasita. Diferenta maxima de inaltime permisa dintre unitatea exterioara si unitatea interioara este de 20m. Lungimea maxima permisa dintre boiler si unitatea interioara este de 10m. Cablul senzorului de boiler nu trebuie scurtat. Este esential sa fie clare detaliile legate de locatia instalarii si traseul de conducte cu Hoval.
Unitatea interioara• Unitatea interioara a Belaria SRM Hoval
sistem de pompa de caldura aer/apa poate fi montata pe perete in camera cazanului folosind un diblu izolat fonic, cu guler.
• Locatia de instalare trebuie selectata con-form cerintelor si directivelor valabile.
• Instalarea trebuie sa decurga fara vreo infiltrare a prafului sau a oricarei substante straine ca sa nu contamineze.
• Daca este posibil, locatia de instalare trebuie sa fie in afara zonelor sensibile la zgomot ale cladirii, in camere cu usa ce izoleaza fonic.
• Turul si returul incalzirii trebuie sa fie conec-tate racord flexibil la structurile care sunt sensibile la emisiile acustice (vezi accesorii).
• Accesul pentru mentenanta si operare trebuie asigurat.
• Camerele cu o umiditatea mare a aerului, de exemplu spalatoriile, nu sunt locatii potrivite pentru instalare (punct de roua <10 °C).
Instarea unui separator de impuritati mag-netic este obligatoriu!
Unitate exterioaraUnitatea exterioara trebuie instalata in afara casei. Locatia de instalare trebuie aleasa cu grija. Este esentiala respectarea urmatoarelor conditii auxiliare:
• Substratul de la locatia de instalare trebuie sa fie suficient de stabil pentru a suporta greutatea unitatii si vibratiile sale din timpul functionarii.
• Locatia trebuie sa ofere suficient loc pentru instalare, mentenanta si curatarea unitatii (vezi dimensiuni “Cerinte spatiu”.)
• Deoarece condensul se scurge afara din unitatea exterioara, un strat de pietris este necesar pentru a absorbi condensul. Nu puneti sub unitate, orice ce este sensibil la umezeala.
• Din cauza emisiilor acustice, locatia de instalare nu trebuie sa fie deasupra sufrageriei, sau geamurilor de la dormitor. Ea trebuie sa fie departe de cladirile vecine (faceti calculul).
• Locatia aleasa trebuie aleasa astfel incat, aerul exhaustat de unitate sa nu deranjeze locatarii caldirilor invecinate.
• Fara piese sau plante pe parea de suflare aer. Risc de distrugere prin inghet.
• Instalarea pe un perete subtire nu este permisa. Peretii usori pot mari emisiile acustice si pot transmite zgomot in structura de beton.
• Este esentiala evitarea scurt circuitului aeru-lui. Spatiul necesar pentru intrare si iesire trebuie mereu sa fie suficient. (vezi cerinte).
• Locatia de instalare trebuie aleasa astfel incat intrarea de aer sa nu fie blocata de zapada, frunze etc.
• Instalarea in nise nu este recomandata (scurt circuit aer, ecou).
• Unitatile nu pot fi instalate una peste cealalta.
• Cablurile principale si de comanda trebui-esc pozitionate la cel putin 3m distanta de aparatele TV si radiouri.
• Intrarea trebuie sa fie ferita de substante nocive, precum amoniac, sulf, clor etc.
• Instalati unitatea exterioara astfel incat sa fie cu fata spre perete, nu expusa la vant.
• Nu instalati unitatea exterioara intr-un loc unde intrarea este expusa la vant.
• Montati o placa deflectoare pe partea de refulare a aerului a unitatii exterioare pentru a preveni ca aceasta este expusa la vant.
• In zonele cu caderi masive de zapada dese, selectati o locatie de instalare unde zapada sa nu poate impiedica operarea unitatii. (acoperis protector).
• Instalati unitatea la o inaltime suficienta ast-fel incat unitatea sa nu fie acoperita de za-pada sau de condensul inghetat. (vezi pla-nuri soclu).
Lungime linie dintre unitatea exterioara si unitatea interioaraHoval Belaria® SRM tip (4-8) (11-16)• Lungime linie minima 3 m 3 m• Lungima maxima permisa 30 m 30 m• Diferenta de inaltime
maxima permisa20 m 20 m
8 3
645
7
10
2
9
111
Sectiune transversala a conductelor de conectare
1 Unitate interioara 2 Unitatea exterioara
(vaporizator/ventilator/compresor) 3 Conducte de conectare la refrigerant 4 Conducta vapori fierbinti cu izolatie termi-
ca 5 Cablu conectare electrica (la fata locului))
Belaria® SRM si compact SRM (11-16) 2 cabluri (sursa de alimentare si cablu de control conexiune)
6 Conducta lichid cu izolatie termica 7 Banda sau tub (la fata locului) 8 Carcasa manson plastic ∅ min.100 mm
cu garnitura (la fata locului). Toate car-casele pentru cabluri trebuie sa fie facute fara cot (contactul vizual cu capatul tevii!).
9 Condens 10 Soclu sau lespedea de pavaj trebuie sa fie
asigurata la fata locului. (inaltimea trebuie determinata, in functie de climatul zonei, inaltime recomandata de >250mm).
11 Scurgere (la fata locului)
■ Proiectare
28 Subject to modifications, 1.7.2015
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Condens (unitatea exterioara)• Condensul trebuie sa se poata scurge liber.
• Folositi o tava de scurgere condens in ca-zul in care condensul trebuie sa fie scurs colectiv (optiune).
• Este esential sa izolati furtunul de condens de tava, si daca este necesar, echipati fur-tunul cu banda electrica de incalzire.
Conducte conectare refrigerant• Conductele de conectare refrigant trebuie sa
fie instalate de tehnicieni calificati.
• Dimensiunile conductelor trebuie sa fie pre-cise (vezi sectiunea “Coduri articole”; con-ducte conectare refrigerant.)
• Unitatea interioara si exterioara, cu conduc-ta de vapori fierbinti si conducta de lichid trebuie sa fie potrivite cu izolatie in mod pro-fesional.
Mansoane perete, protectie trecere con-ducte prin peretePeretele orificiului de trecere si canalul de pro-tectie (Ø min. 100 mm) pentru conductele de racordare trebuie sa fie instalate fara modificări de directie, construite si sigilate profesional.Conductele nu trebuie prinse in ciment, deo-
arece vibratiile pot genera zgomot in structu-ra de beton.Regim racire camera• Racirea camerelor poate fi realizata cu ven-
tiloconvectoare si este recomandata. Con-ductele de legatura pentru ventiloconvec-toare trebuie bine izolate. Suplimentar, con-densul de la ventiloconvectoare trebuie evacuat.
• Confortul optim poate fi obtinut cu un aparat aditional HomeVent ventilatie de confort cu optiunea CoolVent.
• Nu recomandam folosirea unui sistem ra-diant de racire pentru racirea camerei. Mai multe criterii trebuie avute in vedere, de ex-emplu temperatura punctului de roua sau profilul de temperatura. Acestea pot duce la daune mari in cazul proiectarii defectuoase sau folosirii incorecte. Va recomandam sa consultati firma Hoval.
Cabluri conectare electrica• Cablurile de conectare electrica ale unitatii
exterioara trebuie sa fie conectate in mod felxibil.
• Profitarea de tarifele reduse ale companiilor energetice pentru sisteme de pompe de cal-dura duce des la intreuperea operarii. De ex-emplu, in orice perioada de 24 de ore, sursa de alimentare poate fi intrerupta de 3 ori, fie-care data cate 2 ore. Acest lucru trebuie luat in considerare in dimensionarea si proiectar-ea pompei de caldura.
• O banda electrica de incalzire trebuie conec-tata extern in conformitate cu regulamentele aplicate si protejata cu o siguranta diferen-tiala.
Alte ghidurivezi capitolul “Inginerie”
■ Exemple
Hoval Belaria® SRM (4-16)Hoval Belaria® compact SRM (4-16)
Subject to modifications, 1.7.2015 29
Hoval Belaria®
Schema hidraulica BEWT020
Hoval Belaria®
Schema hidraulica BEWT060
Version
Hydr. »Verbindungshinweise /Notice / Nota / Remarque:
.
Datei: BEQT060.vsd
Datum Name20.12.12Achtung ! Für die Installation muss das anlagenbezogene Schema verwendet werden!
3.2
BEQT060.VSDAttention! This is just a schematic. For installation please use the detail-plan!Attenzione! Per la messa in opera, utilizzare le schema dettagliato!Attention! Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!
.
+ Leg._LB020
1 / 1
TT
Y 7
Fan coilBR RT
TT
YFc
A F Outdoor unit
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhov
Belaria SRM
M 2
P
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalh
WW
T
KW
S F
~20ltr.
Version
Hydr. »Verbindungshinweise /Notice / Nota / Remarque:
.
Datei: BEQT020.vsd
Datum Name20.12.12Achtung ! Für die Installation muss das anlagenbezogene Schema verwendet werden!
3.2
BEQT020.VSDAttention! This is just a schematic. For installation please use the detail-plan!Attenzione! Per la messa in opera, utilizzare le schema dettagliato!Attention! Pour la réalisation pratique de l'installation, il faut utiliser le schéma détaillé!
.
+ Leg._LB020
1 / 1
TT
Y 7
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhov
Belaria SRM
M 2
P
A F Outdoor unit
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalh
WW
T
KW
S F
~20ltr.