1:100 Sef proiect ing. Mihai FARA Registrul Comertului: F35/284/2015 C.U.I.: 34152674 Sediu profesional: sat Bacova, nr. 374, jud. Timis tel/fax: 0256-323531; 0722-646157 e-mail: [email protected] Autorizatie ANRE III A Desenat Ie Verificator 9.1/2017 -02-E Faza: PTh PLAN PARTER Viorel DAIA Proiectat Volum 1. INSTALATII ELECTRICE. ing. Mihai FARA FARA MIHAI PERSOANA FIZICA AUTORIZATA Categoria TTD-3 TTD 6xAI1;a,b TTD-1 a a a b b b c c c TTD-10; 2 3xAI1;c TTD-1 2 2 2 2 2 TGD-10; 1,5 2 2 16A 3 2 2 2 16A 3 2 2 a b c b a a a a b b b 2 TGD TM2 TTD-3 TTD-3 TTD-4 TTD-2 TTD-8 TTD-2 TTD-2 TTD-4 TTD-4 TTD-5 TTD-7 TTD-6 TTD-6 TTD-6 2 TTD-9 TTD-9 TTD-9 TM3-6; 2 TTD-11; 2 3xAI1;b TM2-1 3xAI1;a TM2-1 TM2-2 TM2-2 TM2-2 TM2-2 TM2-3 TM2-3 TM2-3 TM2-4 TM2-4 TM2-4 TM2-5 TM2-6 TM2-9; 2 a AI4;2xAI5;a,b TM2-1 AI5;a TM2-1 3xAI5;a TM2-1 TM3 a a a 3xAI1;a TM3-1 a a a LS3;TM2-1 LS3;TM2-1 16A 3 TM3-4 16A 3 TM3-5 2 2 TM3-2 TM3-3 2 2 TM3-2 TM3-3 2 TM3-3 TM2-8; 2 16A 3 2 2 2 2 2 c a TM1 TM1-7; 2 2 2 TM1-6; 2 AI3;a TM1-1 3xAI1;c TM1-1 3xAI1;b TM1-1 b c c c b b b 2 2 TM1-5 TM1-2 TM1-2 TM1-2 TM1-2 TM1-3 TM1-3 TM1-4 TM1-4 TM1-4 d din TM1-1 la subsol din TM1-8 la subsol TED 2 2 2 2 TED-2 2 2 2 2 2 2 2 2 TED-7; 2 TED-6; 2 TED-5; 2 a c b 3xAI1;a TED-1 3xAI1;a TED-1 3xAI1;a TED-1 TED-2 TED-2 TED-3 TED-3 TED-3 TED-4 TED-4 TED-4 TED-5 TED-5 TED-5 tip aparat iluminat nume tablou numar circuit element de comanda nume tablou numar circuit inaltime de montare AI3; e1,e2 TCP-2 TCP-6; 1,5 ABREVIERI PENTRU MONTAJ APARATE a LS2: corp de iluminat securitate pentru evacuare; cu LED-uri; montat suspendat de tavan, cu eticheta conform pictograma de pe plansa; pe ambele fete; IP20; clasa protectie II, autonomie min. 1h LS1: corp de iluminat securitate pentru evacuare; cu LED-uri; montat pe perete sau suspendat, cu eticheta conform pictograma de pe plansa; pe o singura fata; IP20; clasa protectie II, autonomie min. 1h AI1: aparat de iluminat, cu optica din aluminiu dublu parabolica; cu surse tubulare LED - echivalent fluo 2x36 W; min. IP 20; clasa protectie I; montat aplicat pe tavan AI2: aparat de iluminat, cu optica din aluminiu simplu parabolica; cu surse tubulare fluo; 2x36 W; min. IP 20; clasa protectie I; montat aplicat pe tavan AI3: aparat de iluminat, cu optica din aluminiu; cu surse tubulare fluo; 2x18 W; min. IP 20; clasa protectie I; montat aplicat pe tavan LEGENDA Intrerupator simplu; ST; 10 A; 250 V; IP40; montat in plinta PVC autoportanta. Intrerupator simplu; PT; 10 A; 250 V; IP40; montat aparent la inaltimea h=1,3..1,5m fata de cota pardoselii finite. Kit emergenta pentru corp de iluminat cu surse tubulare fluo, autonomie min. 1h; capacitate adaptata la puterea surselor. Intrerupator simplu; PT; 10 A; 250 V; IP44; montat aparent la inaltimea h=1,3..1,5m fata de cota pardoselii finite. Intrerupator dublu, in aceeasi carcasa; PT; 10 A; 250 V; IP40; montat aparent la inaltimea h=1,3..1,5m fata de cota pardoselii finite. Priza SCHUKO; simpla; PT; 16 A; 250 V; IP40; culoare alba. Priza 3P+N+PE; 16 A; 500 V; IP40; montata in plinta autoportanta. 16A 3 Traseu circuite electrice pozate in plinta PVC autoportanta, cu dimensiunile 60x110 mm. Traseu circuite electrice. Traseu circuite de iluminat. Traseu circuite electrice pozate pe jgheab metalic perforat,cu dimensiuni conform plansa. Tablou electric nou proiectat Priza date dubla RJ45 cat.6, montata in plinta PVC autoportanta 4. Toate instalatiile electrice din parter se executa cu cabluri din cupru cu tensiuni nominale U0/U=0,6/1 kV si tensiune de incercare 4000 V, izolatie cu rezistenta la propagarea flacarii, cu emisie redusa de gaze toxice si corozive, montate in jgheabul metalic; si/sau in plinte PVC cu dimensiuni cf. schemelor si antemasuratorii. 5. La trecerea prin pereti si plansee circuitele se protejaza obligatoriu in tuburi PVC executie grea. 6. Se va utiliza exclusiv sistemul de legare la pamant TN-S. Carcasele metalice ale utilajelor actionate electric si conductele metalice se vor lega la centura de impamantare existenta (vezi si memoriul tehnic). 7. Traseele precise ale circuitelor si pozitia definitiva a corpurilor de iluminat si aparatelor se va stabili in santier, de catre beneficiar, proiectant si executant, in functie de traseele altor instalatii si de pozitia utilajelor si mobilierului. La amplsarea circuitelor se vor respecta prescriptiile din normativul I7 - 2011, cap.3.0.3; NTE 007/08/00, cap. VII.1 si VII.2; I 18/1, cap.6, referitoare la pozitionare si distante minime. 8. Aceasta plansa se consulta impreuna cu schemele tablourilor din care pleaca circuitele si memoriul tehnic. NOTA: 2. La executie se vor respecta in totalitate prevederile normativelor si standardelor indicate in piesele scrise ale proiectului. Executantul nu va face modificari, completari sau reduceri ale instalatiilor, fara acordul scris al proiectantului si beneficiarului (prin DS). In caz contrar, proiectantul isi declina ori ce raspundere. 3. Beneficiarul si executantul vor respecta caracteristicile corpurilor de iluminat indicate in plansa si antemasuratoare (optica DP-unde este cazul, putere, grad si clasa de protectie). 1. Inainte de inceperea lucrarilor, executantul va studia acest proiect in totalitate si va solicita proiectantului lamuriri suplimentare (daca este cazul). H LS5: corp de iluminat securitate pentru marcarea hidrantilor; cu LED-uri; montat pe perete la 50 cm deasupra hidrantului, cu eticheta conform pictograma de pe plansa; IP40; clasa protectie II, autonomie min. 1h H TF1 a 2xAI1;b TF1-1 b 2 2 TF1-2 TF1-3 2 2 TF1-2 TF1-3 2 2 TF1-2 TF1-4 2 2 TF1-2 TF1-4 TF1-6; 2 TF1-5; 2 TF2 b a c 2xAI1;c TF2-1 3xAI1;b TF2-1 AI2;a;B1 TF2-2 2xAI5;a TF2-1 2xAI4;b TF2-1 LS3;TM2-1 LS3;TM2-1 LS5;TCP-9 LS3;TF2-1 LS1;TF2-1 LS1;TF2-2 LS2;TF2-2 14xAI1;b;c;B1 TF2-2 b c a TCP b AI2;AI3;a,b TCP-1 2 2 TCP-3 a b AI2;a;B2 TCP-6 4xAI4;a;B2 TCP-6 2xAI2;d;B5 TCP-11 LS2;TCP-7 2xLS1;TCP-7 LS5;TCP-8 2xAI2;AI3;a,b TCP-10 Buton de c-da pentru iluminatul de securitate impotriva panicii; PT; 1 ND; 1 A; 250 V; cu retinere; culoare rosie la etaj 1 din TCP-11 2 TTD-8 2 TTD-8 b b;B1 b b;B1 b b;B1 b c c c c;B1 c la etaj 1 din TCP-8 LS3;TF2-1 LS1;TCP-6 LS1;TCP-6 LS2;TCP-7 AI5;b;B3 TCP-7 7xAI2;b;B3 TCP-7 AI2;b;B3 TCP-7 TGD-10; 1,5 TCP-4; 1,5 TCP-4; 1,5 TCP-5; 1,5 B1 B1 B1 B1 B2 B2 B2 B2 B3 B3 LS1;TCP-7 la subsol+et. din TCP-8 la subsol din TCP-10 LS1;TCP-10 la etaj 1 din TCP-10 c;B1 c;B1 9xAI2;a;B2 TCP-6 de la et. 1 in TCP-10 B4 AI4: aparat de iluminat; cu surse tubulare fluo ; 2x36W ; IP 65; clasa protectie I; cu balast electronic; montat aplicat pe tavan AI5: aparat de iluminat; cu surse tubulare fluo; 2x18W ; IP 65; clasa protectie I; cu balast electronic; montat aplicat pe tavan 2 Priza SCHUKO; dubla; ST; 16 A; 250 V; IP40; montata in plinta PVC autoportanta; culoare rosie, pt. echipamente electronice. 2 Priza SCHUKO; dubla; ST; 16 A; 250 V; IP40; culoare alba, montata in plinta PVC autoportanta. Ɣ Buton de c-da - deconectare alimentare cu e.e.; PT; 1 ND; 1 A; 250 V; carcasa metalica cu geam; IP 55 Ɣ Ɣ Ɣ Bc Bc Bc 400x50 mm 300x50 mm 200x50 mm 400x50 mm 400x50 mm 400x50 mm 200x50 mm Traseu circuite electrice verticale, pozate pe jgheab metalic perforat cu capac, cu dimensiuni cf. plansa. 500x50 mm 300x50 mm Data: 06.2017 Beneficiar: UNIVERSITATEA "POLITEHNICA" TIMISOARA Obiectiv: CORP R. Modificare instalatii electrice si instalatii de securitate Amplasament: Timisoara , bd. Republicii nr. 9, jud. Timis Referat /2017 500x50 mm CONTURUL ZONEI IN CARE SE EXECUTA LUCRARI CONFORM ACESTEI DOCUMENTATII. TGD si spatii comune. ACEST DESEN POATE FI COPIAT, UTILIZAT IN ALTE APLICATII, SAU PUBLICAT NUMAI CU ACORDUL SCRIS AL FARA MIHAI -P.F.A nr. 34201/20.11.2014 2 TCP-2 Spatiu IDSAI

Transcript of LEGENDA - Politehnica University of Timișoara · si conductele metalice se vor lega la centura de...

1:100

Sef proiect

ing. Mihai FARA

Registrul Comertului: F35/284/2015C.U.I.: 34152674

Sediu profesional: sat Bacova, nr. 374, jud. Timistel/fax: 0256-323531; 0722-646157

e-mail: [email protected] ANRE III A

Desenat

IeVerificator

9.1/2017-02-E

Faza: PTh

PLAN PARTER

Viorel DAIA

ProiectatVolum 1. INSTALATII ELECTRICE.

ing. Mihai FARA

FARA MIHAIPERSOANA FIZICA AUTORIZATA

Categoria

TTD-3

TTD

6xAI1;a,b TTD-1

a

a

a

b

b

b

c

c

c

TTD-10; 2

3xAI1;c TTD-1

2

2

2

2

2

TGD-10; 1,5

2

2

16A

3

2

2

2

16A

3

2

2

a b

c

b

a

a

a

a

b

b

b

2

TGD

TM2TTD-

3

TTD-3

TTD-4TTD-2

TTD-8

TTD-2

TTD-2

TTD-4

TTD-4TTD-5 TTD-7

TTD-6

TTD-6TTD-6

2

TTD-

9

TTD-9

TTD-9

TM3-6; 2

TTD-11; 2

3xAI1;b TM2-1 3xAI1;a

TM2-1

TM2-2TM2-2 TM2-2 TM2-2

TM2-

3

TM2-3TM2-3

TM2-4

TM2-4 TM2-4

TM2-5 TM2-6

TM2-9; 2

aAI4;2xAI5;a,b TM2-1

AI5;a TM2-1

3xAI5;a TM2-1

TM3 a

a

a

3xAI1;a TM3-1

a

a a

LS3;TM2-1

LS3;TM2-1

16A

3

TM3-4

16A

3

TM3-5

2

2

TM3-2

TM3-3

2

2

TM3-2

TM3-3

2TM3-3

TM2-8; 2

16A

3

2

2

2

2

2

c

a

TM1

TM1-7; 2

2

2

TM1-

6; 2

AI3;a TM1-1

3xAI1;c TM1-1

3xAI1;b TM1-1

b

c

c

c

b

b

b

2

2

TM1-5

TM1-2

TM1-2TM1-2

TM1-

2TM

1-3

TM1-3TM1-4

TM1-4

TM1-4

d

din TM1-1la subsol

din TM1-8la subsolTED

2

2

2

2

TED-2 2

2

2

2

2

2

2

2

TED-7; 2TED-6; 2TED-5; 2

a

c b

3xAI1;a TED-1

3xAI1;a TED-1

3xAI1;a TED-1

TED-2

TED-2 TED-3 TED-3

TED-3

TED-4

TED-4

TED-4 TED-5 TED-5

TED-5

tip aparat iluminat

nume tablou

numar circuit

element de comanda

nume tablou

numar circuit inaltime de montare

AI3; e1,e2 TCP-2 TCP-6; 1,5

ABREVIERI PENTRU MONTAJ APARATE

a

LS2: corp de iluminat securitate pentru evacuare; cu LED-uri; montat suspendat detavan, cu eticheta conform pictograma de pe plansa; pe ambele fete; IP20;clasa protectie II, autonomie min. 1h

LS1: corp de iluminat securitate pentru evacuare; cu LED-uri; montat pe perete saususpendat, cu eticheta conform pictograma de pe plansa; pe o singura fata; IP20;clasa protectie II, autonomie min. 1h

AI1: aparat de iluminat, cu optica din aluminiu dublu parabolica; cu surse tubulareLED - echivalent fluo 2x36 W; min. IP 20; clasa protectie I; montat aplicat pe tavan

AI2: aparat de iluminat, cu optica din aluminiu simplu parabolica; cu surse tubularefluo; 2x36 W; min. IP 20; clasa protectie I; montat aplicat pe tavan

AI3: aparat de iluminat, cu optica din aluminiu; cu surse tubulare fluo; 2x18 W; min.IP 20; clasa protectie I; montat aplicat pe tavan

LEGENDA

Intrerupator simplu; ST; 10 A; 250 V; IP40; montat in plinta PVC autoportanta.

Intrerupator simplu; PT; 10 A; 250 V; IP40; montat aparent la inaltimea h=1,3..1,5mfata de cota pardoselii finite.

Kit emergenta pentru corp de iluminat cu surse tubulare fluo, autonomie min. 1h;capacitate adaptata la puterea surselor.

Intrerupator simplu; PT; 10 A; 250 V; IP44; montat aparent la inaltimea h=1,3..1,5mfata de cota pardoselii finite.

Intrerupator dublu, in aceeasi carcasa; PT; 10 A; 250 V; IP40; montat aparent lainaltimea h=1,3..1,5m fata de cota pardoselii finite.

Priza SCHUKO; simpla; PT; 16 A; 250 V; IP40; culoare alba.

Priza 3P+N+PE; 16 A; 500 V; IP40; montata in plinta autoportanta.16A

3

Traseu circuite electrice pozate in plinta PVC autoportanta, cu dimensiunile60x110 mm.

Traseu circuite electrice.

Traseu circuite de iluminat.

Traseu circuite electrice pozate pe jgheab metalic perforat,cu dimensiuni conformplansa.

Tablou electric nou proiectat

Priza date dubla RJ45 cat.6, montata in plinta PVC autoportanta4. Toate instalatiile electrice din parter se executa cu cabluri din cupru cu tensiuni nominale U0/U=0,6/1kV si tensiune de incercare 4000 V, izolatie cu rezistenta la propagarea flacarii, cu emisie redusa de gazetoxice si corozive, montate in jgheabul metalic; si/sau in plinte PVC cu dimensiuni cf. schemelor siantemasuratorii.5. La trecerea prin pereti si plansee circuitele se protejaza obligatoriu in tuburi PVC executie grea. 6. Seva utiliza exclusiv sistemul de legare la pamant TN-S. Carcasele metalice ale utilajelor actionate electricsi conductele metalice se vor lega la centura de impamantare existenta (vezi si memoriul tehnic).7. Traseele precise ale circuitelor si pozitia definitiva a corpurilor de iluminat si aparatelor se va stabili insantier, de catre beneficiar, proiectant si executant, in functie de traseele altor instalatii si de pozitiautilajelor si mobilierului. La amplsarea circuitelor se vor respecta prescriptiile din normativul I7 - 2011,cap.3.0.3; NTE 007/08/00, cap. VII.1 si VII.2; I 18/1, cap.6, referitoare la pozitionare si distante minime.8. Aceasta plansa se consulta impreuna cu schemele tablourilor din care pleaca circuitele si memoriultehnic.

NOTA:

2. La executie se vor respecta in totalitate prevederile normativelor si standardelor indicate in piesele scriseale proiectului. Executantul nu va face modificari, completari sau reduceri ale instalatiilor, fara acordulscris al proiectantului si beneficiarului (prin DS). In caz contrar, proiectantul isi declina ori ce raspundere.3. Beneficiarul si executantul vor respecta caracteristicile corpurilor de iluminat indicate in plansa siantemasuratoare (optica DP-unde este cazul, putere, grad si clasa de protectie).

1. Inainte de inceperea lucrarilor, executantul va studia acest proiect in totalitate si va solicitaproiectantului lamuriri suplimentare (daca este cazul).

H

LS5: corp de iluminat securitate pentru marcarea hidrantilor; cu LED-uri; montat peperete la 50 cm deasupra hidrantului, cu eticheta conform pictograma de pe plansa;IP40; clasa protectie II, autonomie min. 1h

H

TF1

a

2xAI1;b TF1-1

b

2

2

TF1-2

TF1-3

2

2

TF1-2

TF1-3

2

2

TF1-

2TF

1-4

2

2

TF1-

2TF

1-4

TF1-

6; 2

TF1-

5; 2

TF2

b

a

c

2xAI1;c TF2-1

3xAI1;b TF2-1

AI2;a;B1 TF2-2

2xAI5;a TF2-1

2xAI4;b TF2-1

LS3;TM2-1

LS3;

TM2-

1

LS5;TCP-9

LS3;TF2-1

LS1;

TF2-

1 LS1;

TF2-

2

LS2;TF2-2

14xAI1;b;c;B1 TF2-2

bc

a

TC

P

b

AI2

;AI3

;a,b

T

CP-1

2

2

TCP-3

a

b

AI2;a;B2 TCP-6

4xAI4;a;B2 TCP-6

2xAI2;d;B5 TCP-11

LS2;TCP-72xLS

1;TC

P-7

LS5;

TCP-

8

2xA

I2;A

I3;a

,b

TC

P-10

Buton de c-da pentru iluminatul de securitate impotriva panicii; PT; 1 ND;1 A; 250 V; cu retinere; culoare rosie

la etaj 1din TCP-11

2

TTD-

8

2 TTD-8

b

b;B1

b

b;B1

b

b;B1

b c

c

c

c;B1

c

la etaj 1din TCP-8

LS3;TF2-1

LS1;TCP-6

LS1;TCP-6

LS2;TCP-7

AI5;b;B3 TCP-7

7xAI2;b;B3 TCP-7

AI2;b;B3 TCP-7

TGD-10; 1,5

TCP-4; 1,5

TCP-4; 1,5

TCP-

5; 1

,5

B1

B1

B1

B1

B2B2

B2

B2

B3

B3

LS1;TCP-7

la subsol+et.din TCP-8

la subsoldin TCP-10LS1;TCP-10

la etaj 1din TCP-10

c;B1

c;B1

9xAI2;a;B2 TCP-6

de la

et.

1in

TC

P-10B4

AI4: aparat de iluminat; cu surse tubulare fluo ; 2x36W ; IP 65; clasa protectie I; cubalast electronic; montat aplicat pe tavan

AI5: aparat de iluminat; cu surse tubulare fluo; 2x18W ; IP 65; clasa protectie I; cubalast electronic; montat aplicat pe tavan

2

Priza SCHUKO; dubla; ST; 16 A; 250 V; IP40; montata in plinta PVC autoportanta;culoare rosie, pt. echipamente electronice.

2

Priza SCHUKO; dubla; ST; 16 A; 250 V; IP40; culoare alba, montata in plinta PVCautoportanta.

(●)

Buton de c-da - deconectare alimentare cu e.e.; PT; 1 ND; 1 A; 250 V;carcasa metalica cu geam; IP 55

(●)

(●)

(●)Bc

Bc

Bc 400x50 mm

300x

50 m

m

200x50 mm

400x50 mm

400x50 mm 400x50 mm

200x

50 m

m

Traseu circuite electrice verticale, pozate pe jgheab metalic perforat cu capac, cudimensiuni cf. plansa.

500x50 mm

300x50 mm

Data:06.2017

Beneficiar: UNIVERSITATEA "POLITEHNICA" TIMISOARAObiectiv: CORP R. Modificare instalatii electrice si instalatii de securitateAmplasament: Timisoara , bd. Republicii nr. 9, jud. Timis

Referat /2017

500x50 mm

CONTURUL ZONEI IN CARE SE EXECUTA LUCRARI CONFORM ACESTEIDOCUMENTATII.

TGD si spatii comune.

ACEST DESEN POATE FI COPIAT, UTILIZAT IN ALTE APLICATII, SAU PUBLICAT NUMAI CU ACORDUL SCRIS AL FARA MIHAI -P.F.A

nr. 34201/20.11.2014

2

TCP-2

SpatiuIDSAI