ATENTIE ! FORMULE DE CALCUL ! NU MODIFICATI PT.CA SE STRICA REZULTATELE ! CALCULUL CADERILOR DE TENSIUNE IN LINII ELECTRICE ( ( SISTEM TRIFAZAT - SARCINI UNIFORM DISTRI DATE INTRARE 1 2 3 4 Nr. Tip conductor L P km kW V 0 1 2 3 4 7 1 0.2 50 AL 0.579 0.61 1.189 0.086 30 400 2 LES jt ACYAbY 3x25+16 1.3 25 1.25 0 1.25 0.274 9 400 NOTA Relatiile de calcul utilizate in tabelul de mai sus sunt urmatoarele: Denumirea liniei Scond. Ro.faza R0.nul Rtotal Xo U L crt . mm 2 W / km W / km W / km W / km LEA j.t. distrib TYIR 3X50AL+ 50 OL-AL

Transcript of Calc.cadere Tens.(Param. LEA-LES)

Page 1: Calc.cadere Tens.(Param. LEA-LES)

ATENTIE ! FORMULE DE CALCUL ! NU MODIFICATI PT.CA SE STRICA REZULTATELE !

CALCULUL CADERILOR DE TENSIUNE IN LINII ELECTRICE ( LEA SAU LES )( SISTEM TRIFAZAT - SARCINI UNIFORM DISTRIBUITE)

DATE INTRARE1 2 3 4 5

Nr. Tip conductor L P I

crt. km kW V A

0 1 2 3 4 7 8

1 0.2 50 AL 0.579 0.61 1.189 0.086 30 400 48.17

2 LES jt ACYAbY 3x25+16 1.3 25 1.25 0 1.25 0.274 9 400 14.45

NOTA

Relatiile de calcul utilizate in tabelul de mai sus sunt urmatoarele:

Denumirea liniei

Scond. Ro.faza R0.nul Rtotal Xo U L

mm2 W / km W / km W / km W / km

LEA j.t. distrib publica

TYIR 3X50AL+ 50 OL-AL

Page 2: Calc.cadere Tens.(Param. LEA-LES)

Caderea de tensiune in volti : DU (3) ( V ) = 3 x 1/2 x L(km) x I(A) x ( R(W)x cosj + X(W)x sinj )

Caderea de tensiune in procente : DU ( % ) = DU ( V ) * U / 100

Page 3: Calc.cadere Tens.(Param. LEA-LES)

CALCULUL CADERILOR DE TENSIUNE IN LINII ELECTRICE ( LEA SAU LES )( SISTEM TRIFAZAT - SARCINI UNIFORM DISTRIBUITE)

DATE INTRARE DATE CALCULATE6 7 8 9

Observatii

V %

9 10 11 12 13

0.9 0.44 9.24 2.31

0.9 0.44 20.25 5.06

cosj sinj DU DU

Page 4: Calc.cadere Tens.(Param. LEA-LES)

ATENTIE ! FORMULE DE CALCUL ! NU MODIFICATI PT.CA SE STRICA …..REZULTATELE !

CALCULUL CADERILOR DE TENSIUNE IN LINII ELECTRICE ( LEA SAU LES )( SISTEM TRIFAZAT - SARCINI CONCENTRATE )

DATE INTRARE DATE CALCULATE1 2 3 4 5 6 7 8 9

Nr. Denumirea liniei Tip conductor L Ro Xo P I

crt. km kW V A V %

0 1 2 3 4 7 8 9 10 11 12

1 LEA j.t. distrib publica 0.1 1.84 0.355 380 25 0.8 0.6 7.30 1.92EMIL 0.4 1.95 0.07 400 15 0.92 0.3919 18.93 4.73

TEST 0.5 1.25 0.275 380 45 0.9 0.4359 48.52 12.77GARDA - JUD ALBA TYIR 50 OL-AL+3X95 AL 0.43 0.308 0.084 50 400 78 0.92 0.3919 18.48 4.62

TEST 0.05 4.5 0.06 4 230 11 0.92 0.3919 3.94 1.71TEST 1 0 0.92 0.3919 0.00 0.00

CYABY 1 kV - 3x10 0.15 0.727 0.0675 12 400 19 0.92 0.3919 3.40 0.85Anisoara 34 0.37 0.37 160 20000 5 0.94 0.3412 137.17 0.69

ACYABY 1 kV - 4X16 0.15 2 0.09 10 400 16 0.92 0.3919 7.64 1.91LES j.t LIT - Reghin 0.06 0.53 0.0637 36 400 56 0.92 0.3919 3.01 0.75

0.3 0.64 0.325 70 400 110 0.92 0.3919 40.87 10.22ACYABY 1 kV - 3 x 150+70 0.222 0.208 0.083 110 400 173 0.92 0.3919 14.86 3.71

ACYABY 1 kV - 3 x 185+95 0.4 0.169 0.031 110 400 173 0.92 0.3919 5.89 1.47CYABY 1 kV - 3x25+16 0.1 0.74 0.261 20 380 34 0.9 0.4359 2.81 0.74ACYABY 1 kV - 3x300+150 1 0.082 0.031 177 380 299 0.9 0.4359 8.85 2.33ACYABY 1 kV - 3 x 240+120 0.66 0.125 0.031 177 380 299 0.9 0.4359 8.63 2.27

NOTA 0.5 0.077 0.031 196 380 324 0.92 0.3919 6.35 1.67

U L cosj sinj DU DU

W / km W / km

LES jt Sediu M.F Miercurea Ciuc

Page 5: Calc.cadere Tens.(Param. LEA-LES)

Relatiile de calcul utilizate in tabelul de mai sus sunt urmatoarele:

Tip conductor L Ro Xo P I

km kW V A V %

ACYABY 1 kV - 3 x 185+95 0.44 0.169 0.031 84 400 132 0.92 0.3919 16.84 4.21ACYABY 1 kV - 3 x 150+70 0.5 0.208 0.083 28 400 44 0.92 0.3919 8.52 2.13

Caderea de tensiune in volti : DU (3) ( V ) = 3 x L(km) x I(A) x ( R(W)x cosj + X(W)x sinj )

Caderea de tensiune in procente : DU ( % ) = DU ( V ) * U / 100

U L cosj sinj DU DU

W / km W / km

Page 6: Calc.cadere Tens.(Param. LEA-LES)

CALCULUL CADERILOR DE TENSIUNE IN LINII ELECTRICE ( LEA SAU LES )( SISTEM TRIFAZAT - SARCINI CONCENTRATE )

Observatii

13

TYIR 95

Page 7: Calc.cadere Tens.(Param. LEA-LES)

Rezistente active si reactante pt.cabluri trifazate

Al Cu Al Cu1 2 3 4 5 6

10 3.12 0.727 0.05716 1.95 1.16 0.053 0.067525 1.25 0.727 3x25/16 0.038 0.27435 0.894 0.524 3x35/16 0.038 0.26150 0.625 0.387 3x50/26 0.035 0.26370 0.447 0.265 3x70/35 0.035 0.25495 0.329 0.195 3x95/50 0.035 0.253

120 0.261 0.154 3x120/70 0.031 0.25150 0.208 0.124 3x150/70 0.031 0.247185 0.169 0.1 3x185/95 0.031 0.248240 0.125 0.0754 0.031 0.245

300 0.082 0.031 0.242

0.031 0.24

PROVENIENTA DATE CONDUCTOARE CABLURI

4 Linii electrice subterane. 1 - 220 kV.Indrumar de calcul si proiectare.G Ionita, Gh.Mazilu.(pg.316)5 Idem

Sectiune conductoare

(mmp.)

ro (ohm/ km) Sectiune conducto

are (mmp.)

xo (ohm/km)

3x240/120

3x300/150

3x400/185

Page 8: Calc.cadere Tens.(Param. LEA-LES)

Linii electrice subterane. 1 - 220 kV.Indrumar de calcul si proiectare.G Ionita, Gh.Mazilu.(pg.316)

Page 9: Calc.cadere Tens.(Param. LEA-LES)

a distanta medie geometrica intre conductoare (mm).

Rezistenta inductiva (ohm/km), la distanta medie geometrica intre conductoare (mm)

600 800 1000 1250 1500 2000 2500 3000 3500 4000

Al - 16 1.98 0.358 0.375 0.39 0.405

Al - 25 1.28Al - 35 0.92Al - 50 0.64Al - 70 0.46Al - 95 0.34

Al - 120 0.27Al - 150 0.21Al - 185 0.17

Distanta medie geometrica intre conductoare (mm)

D - distanta intre 2 faze

Rezistenta inductiva (ohm/km), la T = +20 0C pentru conductoare de aluminiu, l

Marca conductor

Rezistenta activa (ohm/km)

Coronament triunghi

D = (Drs+Dst+Drt)1/2

Cond. Montate in linie

D = 1.26 * D

Page 10: Calc.cadere Tens.(Param. LEA-LES)

LEA DC D = pag.81(Racoti - 88)

Page 11: Calc.cadere Tens.(Param. LEA-LES)

Caracteristicile conductoarelor electrice trifazate, conform STAS 3032 - 79(1RE - Ip 45 - 90)

mm2 ohm/km ohm/km A

1 3 x 16, AL + 1.802 0.098 7550 OL - AL 0.61

2 3 x 25, AL + 1.18 0.097 9750 OL - AL 0.61

3 3 X 35, AL + 0.833 0.089 11950 OL - AL 0.61

4 3 X 50, AL + 0.579 0.086 14150 OL - AL 0.61

5 3 X 70, AL + 0.437 0.084 18050 OL - AL 0.61

Nr. Crt.

Caracteristici electrice, Sectiune Conductoare

Rezist. conductor de faza (nul)

Reactanta totala de calcul a cond.de faza

(nul)

Curentul maxim admis in regim

permanent