Descrierea sistemului şi domeniile de utilizareDescrierea sistemului.....................................................4
Domenii de utilizare........................................................5
Flexibilitate şi stabilitate datorită unei construcţiiunice a ţevi............................................................................7
Tipuri de produseUponor Thermo...............................................................8 Uponor Aqua...................................................................9 Uponor Quattro.............................................................10
Accesoriile sistemului
Sistemul de racordare...................................................11Căciuli de capăt............................................................13 Setul de izolare.............................................................14Căminele Uponor..........................................................15Accesorii pentru traversarea pereţilor ..........................16Accesorii suplimentare ................................................18
ProiectareBazele proiectării..........................................................19 Proiectarea traseului ţevii ...........................................20 Exemple de instalare ...................................................21
Dimensionarea ţevilor de încălzireTabele pierdere de presiune ........................................23 Diagrama pierderi presiuni...........................................25 Bazele dimensionării instalaţiilor...................................26 Tabele de dimensionare rapidă.....................................27 Pierderea de căldură.................................................... 29
Dimensionarea ţevilor pentru apă caldăTabel pierderi de presiune.............................................31 Diagramă pierderi de presiune .....................................32
InstalareGhid valori pentru procesul de instalare........................33 Manipularea ţevii ......................................................... 34 Instrucţiuni de montaj................................................... 38
Testarea la presiune şi la scurgeriTestarea la presiune şi scurgeri conform cuDIN 1988 Part 2............................................................48
Înregistrarea testelor de presiune conform cu
DIN 1988 Part 2 pentru ţevile de apă...........................49 Testarea la presiune şi scurgeri pentru ţevile de încălzire
conform cu DIN 18380........................................................50 Înregistarea testelor de presiune conform DIN 18380
pentru ţevi de încălzire .......................................................51
Specicaţii tehniceProprietăţile ţevilor Uponor PE-Xa................................52Proprietăţile pe termen lung..........................................53 Proprietăţile materialului învelişului ţevii.......................54 Proprietăţile materialului izolator ..................................54
AnexeTabele...........................................................................55
Toate informaţiile tehnice şi legale conţinute în acest catalogau fost selectate cu atenţie, conform cu cele mai bunecunoştinţe ale noastre.Nu putem făcuţi răspunzători pentru orice eroare aşa cumele nu pot excluse complet. Ghidul tehnic, incluzând toatesecţiunile este protejat prin copyright. Toate utilizările în afara celor permise de legea copyrightului,nu sunt permise fără aprobarea Uponor.Aceasta se aplică în special la reproducere, reprintare, proce-sare, stocare şi procesare în sisteme electronice, traduceri şimicrolmare. Conţinutul ghidului tehnic poate modicat fără
înştiinţare prealabilă.
Copyright 2011Uponor
Cuprins
R E Ţ E L E T E H N I C
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
4/58
4 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Descrierea sistemului şi domeniile de utilizare
Descrierea sistemuluiDe la teorie la practică
Aceasta este ideea fundamentalădin spatele sistemului nostru de ţevipreizolate exibile. Flexibilitateamaterialului, tehnica de conectare,durata serviciului de viaţă şirobusteţea, bine testate, ale ţeviinoastre preizolate, asigură în nal,că dvs. ca expert, puteţi îndepliniproiectele rapid, economic şi sigur.Acelaşi lucru, e că discutaţi despreo reţea extinsă sau despre o conec-
tare a unei clădiri.
Conectare uşoară,permanentă şipractică.
Flexibil şi rapid intro-dus prin pereteleexterior la punctulcentral de distribuţie.
Livrat la lungimeacerută şi instalatdirect din colac.
Apa caldă, apa de băut, apa de răcire şi apa reziduală sunttransportate sigur, ca şi alte multemateriale lichide pentru aplicaţiileindustriale.Serviciile pe care le oferim în aso-ciere cu sistemele de ţevi preizolateoferă de asemenea, suport completla orice fază a proiectului dvs.
Calitate, semnată şi parafată
Calitate fără compromisuri, este politi-ca noastră de bază.Controlul calităţii extins al producţieieste doar unul din aspectele sistemuluinostru de management al calităţii.Şi noi ne asigurăm în mod regulat căorganismele de inspecţie independ-ente certică faptul că produsele noas-tre întrunesc cele mai riguroase stand-arde. Aprobările şi certicările Kiwa KOMOCompatibilitatea între componente(Thermo Single, Thermo Twin, Căciulide capăt, gama de tin-guri cu colier de strângere şi setu-rile de izolare) este examinată de douăori pe an conform sistemului de apro-bare BRL 5609.Aprobarea certică durata de viaţă a
sistemului de cel puţin 30
ani şi absenţa scurgerilor la o presi-une a apei de 0.3 bar şi o temperaturăa mediului de 30 °C. În plus, pierderilede căldură, rezistenţa la sarcini staticeca şi comportamentul ţevilor, sunt ver-icate conform cu specicaţiile.
Certicarea DIN CertcoCerticarea anuală conform VDI 2055verică valorile pierderilor de căldură.
Gracele pierderilor de căldură pentruţeava prerizolată exibilă sunt realizatepe această bază . Certicarea sebazează pe cerinţele denite, şi
înseamnă că valorile sunt o bunăreectare a condiţiilor reale.
Certicarea la sarcini staticeCerticarea bazată pe ATV DVWK-A127, demonstrează că ţevile noas-
tre, instalate în conformitate cu
condiţiile denite, suntindicate pentru încărcare cu tra-c greu, (SWL 60 = 60 t) conform cufoaia de lucru ATV-A 127. Rigiditateainelului mantalei exterioare deprotecţie a ţevii este certicată con-form EN ISO 9969.
Conductivitatea termică minimăneschimbată a izolaţiei
Testele de material conformEN 15632 la 80 °C demonstrează cămaterialul nostru izolator, absoarbemai puţin de 1 % apă din volum.Această absorbţie redusă înseamnăcă proprietăţile izolatoare sunt prac-tic neschimbate.
4
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
5/58
5R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Domeniile de utilizare
Este o marcă a unui sistem de ţevi de calitate care oferă soluţii profesionale unui mare număr de posibile utilizări cu numai câteva componente.Performanţele ţevilor preizolate exibile de la Uponor, le recomandă pentru o gamă variată de aplicaţii.
Calitate nu cantitate. Uponor vă oferă produse inteligente pentru aproape toate tipurile de aplicaţii
Uponor ThermoŢeavă simplă (Single Thermo) saudublă (Twin Thermo) pentru încălzire.Versiunea Thermo Twin include turulşi returul într-un sistem cu o singurăţeavă.
Uponor QuattroSoluţia toate într-o singură ţeavă, pentruapă potabilă şi încălzire, într-o singurăţeavă exibilă. Ideale, economice şipractice.
Uponor AquaŢevi simple sau duble pentru apă şi
încălzire. Versiunea Aqua Twininclude un circuit integrat de recircu-lare a apei.
Pentru transportul agentului termic.
Varianta cu o ţeavă (single) sau cu două
ţevi (twin) pentru tur şi retur. Pentru transpotul
apei calde şi reci, la versiunea cu două ţevi
se foloseşte apă caldă recirculată
Informaţii rapide şi esenţiale despre produs
Uponor Thermo Uponor Aqua Uponor Quattro
Aplicaţii 1)
Apă caldă şi rece
Agent termicAgent termic pentru răcire
Variante
Opţional cablu de încălzire (numai pentru ţevi single )
Material
Material ţeavă interioară PE-Xa cu EVOH PE-Xa PE-Xa şi PE-Xa cu EVOH
Material izolaţie PE reticulată PE reticulată PE reticulată
Material manta exterioară de protecţie PE-ÎD PE-ÎD PE-ÎD
1) pentru alte aplicaţii şi uide (ex. chimicale, produse alimentare sau apă reziduală) contactaţi-ne !
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
6/58
6 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Manipulare uşoarădatorită exibilităţiiextraordinare: nu numaila derulare într-un şanţdar în mod special lacăminul de racordare,unde clientul apreciazăaceste avantaje.
Fără sudură, fără scule specialeFlexibilitatea şi masa redusă a ţe-vilor noastre preizolate, le face uşorde manipulat şi procesul de montaj sederulează rapid.Ele sunt compatibile de asemenea cuo gamă largă de accesorii.De la o diversitate de treceri prinpereţi, seturi de izolare, la gamacunoscută de tinguri.
Flexibilitate - de la punctul termic şi până în casă
Serviciul de tăiere : lungimilecolacilor, adaptate la cerinţele dvs.
Atât lungimile standard cât şi celeparţiale sunt livrate în cel mai scurttimp.
Suport complet oferit de tehnicieniinoştri cu experienţă în proiectare şimontaj
Suport pentru proiectare şi instruirepe şantier
Cele mai importante avantaje alemontajului şi racordării
Fără dicultăţi la montaj în jurul colţurilor şi obstacolelor
Instalarea a până la 200metri de ţeavă fără racorddintr-o singură bucată
Structura ţevilor preizolatenu necesită montarea decompensatoare de dilatare
Execuţie rapidă a construcţiei
/timp scurt de montajMetodă uşoară şi sigură deracordare, inclusiv a izolaţiei racor-durilor şi ramicaţiilor
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
7/58
7R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Flexibilitate şi stabilitate datorită unei construcţii unicea ţevii
Calitatea ridicată a ţevilor preizo-late exibile Uponor este consecinţarezistenţei elementelor individuale.Combinaţia dintre mantaua exterioară
de protecţie, rezistentă la îmbătrânire,stratul izolator şi robust din polietilenăreticulată stabilă dar exibilă, cu dura-ta îndelungată de viaţă şi ţeava PE-Xa
cu durată de viaţă îndelunga-tă, crează sistemul de ţevi care poate uşor şi rapid instalat şi carefuncţionează în siguranţă.
1
2
3
4
1 Mantaua exterioară de protecţie din PE-ÎD : rezistentăla şoc, cu durată lungă de viaţă dar exibilă, datorităgeometriei unice
2 Izolaţia din spumă de polietilenă reticulată, proprietăţiizolatoare ideale, rezistentă la îmbătrânire, rezistentăla umiditate şi exibilitate foarte ridicată
3 Prolele de centrare colorate evită confuzia dintreţevile de tur şi retur
4 Ţeava PE-Xa: rezistentă la temperatură şi rezistentăla formarea crustei pe interior şi crăpăturilor datorităstresului termic
Cele mai importante caracteristici dintr-o privire
Manipulare uşoară şi instalarerapidă, datorate exibilităţii excepţionale
Izolaţie rezistentă la îmbătrânire, permanentelastică, datorită spumei de polietilenă reticulată cucelule închise, absorbţia de apă < 1% din volum
Pierderile de căldură 1) monitorizate extern decătre DIN Certco
Ţeava interioară PE-Xa rezistentă la coroziune
şi crusteŢeava interioară realizată din polietilenă reticulată (PE-Xa) oferă rezistenţă excepţională la crăpăturile datorateoboselii, mediilor agresive, îngheţului şi micro-organismelor
Rigiditate optimă a inelului mantalei exterioare, rezistenţăla impact şi presiune iar simultan oferă şi exibilitate ridicată lamontaj şi masă specică redusă.
1) Uponor Thermo
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
8/58
8 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Soluţia ideală pentru distribuţia agen-tului termic în reţelele locale de
încălzi re, sau pentru racordarea com-plexelor de clădiri sau a caselor indi-
Tipuri de produse
Uponor Thermo
viduale. Uponor Thermo în versiuneaTwin combină circuitele de tur şi retur
într-un sistem de ţevi exibile. Clasi-carea sistemului cu ţeavă Thermo
Practic, ideal şi exibil pentru furnizarea de agent termic
Aplicaţie primară Agent termic apă erbinte
Aplicaţie secundarăApă reziduală
Chimicale (sunaţi pentru conrmare)Material ţeavă
PE-Xa cu EVOH, SDR 11 (6 bar)Opţiune
Cablu de încălzireMaterial izolator
Spumă PE reticulată
Material tub exteriorPE-ÎD (PE 80)
Uponor Thermo Single
80°C *max.95°C
6 bar
25–110 mm
Notă:Soluţiile standard vericate pentrudistribuţia agentului termic înreţelele locale de încălzire sau pen-tru racordarea unei singure clădiri.
Uponor Thermo Twin
80°C *max.95°C
6 bar
25–63 mm
Notă:Circuite combinate de tur retur însistemele cu o singură ţeavă,incluzând miezuri izolatoare cu douăculori pentru evitarea confuziei întimpul montajului
*Vă rugăm să parcurgeţi explicaţiile de la pagina 55
este descrisă în EN 15632-T3 ca unsistem necompozit cu ţeavă din masăplastică.
Aplicaţie primară Agent termic apă erbinte
Aplicaţie secundarăApă reziduală
Chimicale (sunaţi pentru conrmare)Material ţeavă
PE-Xa cu EVOH, SDR 11 (6 bar)Opţiune
Cablu de încălzireMaterial izolator
Spumă PE reticulatăMaterial tub exterior
PE-ÎD (PE 80)
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
9/58
9R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Imbatabil pentru instalarea rapidă,sigură, şi totuşi foarte economică în sis-temele de furnizare a apei calde.
Uponor Aqua
În versiunea Twin , vă oferim o soluţiecu o ţeavă de recirculare integrată.Clasicarea materialului ţevii PE-Xa
"Specialistul" dvs. exibil pentru apă caldă şi rece
Aplicaţii primare
Apă caldă şi receAplicaţii secundare
Alimentaţie (sunaţi pentru conr-mare)
Chimicale (sunaţi pentru conrmare)Material ţeavă
PE-Xa, SDR 7,4Opţional
Cablu încălzireMaterial izolator
Spumă PE reticulatăMaterial tub exterior
PE-ÎD (PE 80)
Uponor Aqua Single
70°C *max. 95°C
10 bar
25–110 mm
Notă:Ţeavă sigură, economică pentruinstalaţiile de apă caldă.
Aplicaţii primare Apă caldă cu recirculaţie
Aplicaţii secundare Alimentaţie sunaţi pentru conrmare) Chimicale(sunaţi pentru conrmare)
Material ţeavăPE-Xa, SDR 7,4
Material izolator Spumă PE Reticulată
Material tub exterior
PE-ÎD (PE 80)
Uponor Aqua Twin
70°C *max. 95°C
10 bar
25–50mm
Notă:O ţeavă pentru apă caldă şi unapentru recirculaţie, combinate
întrun singur sistem. Prolul centralizolator în două culori simplicăconectarea corectă a ţevilor cen-trale.
*Vă rugăm parcurgeţi explicaţiile de la pagina 55
pentru sistemul de ţevi Aqua estedescris în EN ISO 15875.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
10/58
10 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
„O ţeavă pentru toate aplicaţiile!“Agentul termic tur şi retur, împreună cu apa caldă, inclusiv cu
recirculaţia, în doar o singură ţeavă.
Uponor Quattro
Este cel mai convenabil, mai sigur şimai economic mod de a conecta oclădire individuală sau un complex
de clădiri.
Modul corect de a face un singur racord în clădire
Aplicaţii primare Agent termic Apă caldă, apă caldă cu
recirculaţieMaterial ţeavă
PE-Xa, SDR 7,4 (10 bar) şi PE-Xa cu EVOH, SDR 11 (6 bar)
Material izolator
Spumă PE reticulatăMaterial manta exterioară protecţie
PE-ÎD (PE 80)
Uponor Quattro
70/80°C *max.95°C
6 bar +10 bar
25–32mm
Notă:Ţeava Uponor Quattro este de ase-menea practică şi economică pen-tru racordarea clădirilor auxiliare.Prolul izolator cu două culorisimplică conectarea corectă a ţeviicentrale.
* Vă rugăm parcurgeţi explicaţiile de la pagina 55
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
11/58
11R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Tehnologia de conectare Uponor –pentru produsele noastre Thermo,Aqua şi Quattro
Racordurile Uponor PE-Xa cu colier de strângere, sunt special proiecta-te pentru conectarea ţevilor depolietilenă reticulată produse deUponor, pentru apă caldă şi rece îninstalaţiile casnice şi cele de încălzirecentralizată. Racordurile sunt disponi-bile pentru dimensiunile ţevilor cuprinse
între 25 -110 mm, în două serii, marcatePN 6 (v.5.0) şi PN 10 (v.3.2).Racordurile Uponor PE-Xa cu co-lier de strângere sunt proiectate pentrua oferi o excelentă strângere a racordu-lui pe ţeavă. Forţa de strângere estemai mare decât rezistenţa la rupere aţevii, şi performanţele de etanşare suntneafectate de uctuaţiile detemperatură.Racordurile Uponor PE-Xa cu colier de strângere au un design simplu
şi robust, pot montate foarte rapid şiuşor, chiar şi în locuri înguste şi cuacces dicil.Cheile inelare folosite la xarea racor-durilor când tingurile şi racordurile suntfoarte mici, sunt comod de folosit com-parativ cu mărimea racordului.
Racordul Uponor PE-Xa cu colier destrângere este patentat, testat con-form normelor DVGW (Germania),
NKB (Suedia), CSTB (Franţa), KIWA(Olanda) şi aprobate.
Principalele componente ale tin-gurilor sunt realizate din alamă DR(rezistentă la dezincare).
Inelele O-ring sunt folosite pentru aetanşa racordul cu tingurile ţevii.
Nu este necesar teon sau cânepăpentru etanşeizări suplimentareRacordurile Uponor permit o largă
Racord filetat
Căciulă capăt
Cot cu O-ring
Flanşă filetatăcu O-ring
Niplu reducţiecu O-ring
Rac ord filet exterior cu O-ring
Teu cuO-ring
Racord filetat
Racord filetat
racord filetat
Tehnica de racordare Uponor
Recomandare de proiectare :Când conectăm racordurile UponorPE-Xa cu colier de strângere cucomponente de la alt producător,elementele terminale ale racorduluiUponor trebuie să e un ting (cotsau mufă) cu let interior.
Accesoriile sistemului
Sistemul de conectare
gamă de combinaţii de conectare. Singurele scule necesare sunt
două chei xe plus o perechecleşti.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
12/58
12 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Sistemul este bazat pe proprietăţile unice ale ţevilor Uponor PE-Xa(metoda Engel) şi pe tingulrevoluţionar Q&E. Permite montareaunui ting fără alte scule decât uncleşte de expandare.Doar lărgiţi ţeava Uponor PE-Xa
împreună cu un inel Q&E şi montaţi-odirect pe tingul din alamă sau dinPPSU. Ţeava va reveni la forma iniţialăiar montajul este complet.Tehnica a fost patentată de Uponor şi
este destinată exclusivţevilor Uponor PE-Xa cu dimensiuneade până la 63 mm. Performanţele tin-gurilor au fost testate de câteva labo-ratoare independente acreditate, cumar ATG(Belgia), Kiwa (Olanda), MPA(Germania), SP (Suedia), TGM (Aus-tria), QAS (Australia) ca şi în labo-ratoarele proprii ale Uponor.
Q&E - calea cea mai dreaptă către instalaţii profesioniste
Lărgiţi ţeava cu trusa de expandare
Montarea inelulului Q&E pe ţeavă
Împingeţi ţeava pe ting şi gata !
Fitinguri Q&E PPSU
Benecii:O soluţie totală şi sigură pentruinstalatorii profesionişti
Design simplu şi sigur fărăgarnituri, coliere cu presare sautragere, ceea ce o face uşorşi simplu de folosit şi rapid deexecutat
Prin utilizarea tehnologiei Q&E,un profesionist realizeazăinstalaţia rapid şi ecient.
Odată ce racordul este xat, eleste nedemontabil
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
13/58
13R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Căciulile de capăt
Căciulile de capăt Uponor din cauciucpentru ţeavă, protejează izolaţia ţeviişi oferă o împărţire
între componente. Este important săoferiţi protecţie la pătrunderea
umidităţii sau deteriorării, astfel ca întreg sistemul să poată real iza opt imscopul pentru mai mulţi ani. Ogarnitură tip inel este de asemeneafurnizată pentru a preveni intrarea
Pentru a proteja capetele ţevilor şi pentru împărţirea componentelor
apei.Capacul poate montat uşor şicomod prin împingere la capătul ţevii,după care este complet xat cu uncolier metalic.
Notă: Înainte de xarea căciulii de capăt,izolaţia trebuie înlăturată de pe
ţeavă pe o lungime potrivită. Tre-buie ţinut cont de dimensiunile set-ului de izolaţie.
Notă:Inelele clemă nu trebuie montatecând este folosit setul de izolaţie
Uponor !
Single Twin Quattro
Notă:Capacele de cauciuc Uponor trebuiexate la capetele mantalei exterioarede protecţie înainte de a conectaţeava PE-Xa !
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
14/58
14 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Sunt disponibile seturi de izolarepotrivite pentru izolarea şi etanşareamantalei externe de protecţie de140,175 şi 200 mm, atât la racorduldrept cât şi la cel în T sau pentru co-turi. Ele se potrivesc atât la varianta
cu o singură ţeavă cât şi la două ţeviPE-Xa. Este disponibil de asemeneaşi un set de izolare H pentru conver-sia de la ţeava PE-Xa simplă la ceadublă.Setul izolator constă în două semico-
Seturi de izolare Uponor
chilii care se asamblează folosind ni-turi. Mantaua exterioară de diametru68 şi 90 mm poate adaptată la se-turile izolatoare folosind inelele dereducţie Uponor.
Set de izolare Uponor "T" Set de izolare Uponor pentru cot Set de izolare Uponor drept
Set de izolare Uponor "H" Inel de reducţie Uponor
Notă:Folosiţi căminul Uponor pentruconexiunile Quattro
Notă:Racordurile nu trebuie plasate subdrumuri, deoarece aceasta face di-cil accesul ulterior şi vehiculelegrele pot deteriora racordul.
Dacă racordurile din apropiereadrumurilor sunt inevitabile, trebuieturnată o placă de beton deasupraracordului pentru a distribui sarci-na.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
15/58
15R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Căminele Uponor Căminele de racordare Uponor suntproietate pentru racordurile ţevilorcare nu pot racordate cu un set deizolare Uponor. Acestea includ deexemplu, posibilitatea conectării întreţevile Uponor simple şi cele cu două
sau mai multe ţevi PE-Xa sau ţeviUponor Quattro.Căminul este turnat şi are pereţi dinpolietilenă iar la interior este acoperitcu izolator din PE.Căminul de ramicare permite
racordarea ulterioară a altor circuite.Căminul este etanş şi poate folositpentru toate dimensiunile de ţeavă(diametru exterior 140-200 mm).
Căminele turnate sunt executate dinpolietilenă iar stratul izolator din interi-or reduce pierderile de căldură.
Quattrocasa
Quattrocasa
AquaTwin
ThermoTwin
Aqua Twincasa 1
ThermoTwincasa 2
AquaTwin
ThermoTwin
ThermoTwincasa
ThermoTwincasa
ThermoTwincasa
ThermoTwincasa
ThermoTwincasa
ThermoTwincasa
Încălzire şi apă caldă de la circuitele principale
la casă
Alimentare de la circuitul principal al sursei de încălzire la 4 case
Alimentare de la circuitul principal al sursei de încălzire la 2 case
Încălzire şi apă caldă de la circuitele principale la
2 case folosind ţeavă Uponor Quattro
Notă:Racordurile nu trebuie plasate subdrumuri, deoarece aceasta face dif-icil accesul ulterior şi vehiculele
grele pot deteriora racordul.Dacă racordurile din apropiereadrumurilor sunt inevitabile, trebuieturnată o placă de beton deasupraracordului. pentru a distribui sarci-na.
ThermoSingle
ThermoSingle
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
16/58
16 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Accesorii pentru traversarea pereţilor
Acest tub poate folosit pentru traver-sarea fundaţiilor oriunde nu exista apă cupresiune.Tubul pentru traversare este montat pelocul unde fundaţia este turnată sau este
instalat după execuţia unei găuri înfundaţie. Aceste manşoane termocon-tractabile previn inltrarea de apă prinpicurare din fundaţie în ţeavă prinmanşonul de trecere.
Tub Uponor de trecere (etanş la apă fără presiune)
Kitul conţine un tub de trecere cu lungimeade 400 mm şi un manşon termocontrac-tabil.
Etanşează ecient trecerea printr-ostructură de beton, şi previne ca umidi-
tatea să intre în clădire. A fost testatăetanşarea cu Radon. Kitul conţine tu-
Garnitura de etanşare Uponor (etanş la apă fără presiune)
bul de trecere etanşă şi clema inelară.
manşon termocontractibil tub de trecere
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
17/58
17R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Interior
Presetupa de etanşare Uponor PWP
Presetupa de etanşare Uponor PWPtrebuie folosită oriunde se aşteaptăapă sub presiune.Ea poate folosită direct la aplicarepe peretele găurii practicate înbetonul impermeabil sau pe pereteleunei conducte din bră de cimentcare este betonată sau zidită.
Presetupa de etanşare Uponor PWP pentru trecerea prin pereţi (rezistentă la apă sub presiune)
Kitul Uponor suplimentar
Dacă nu este posibil să introducemmantaua exterioară de protecţie per-pendicular pe trecerea din perete ,kitul suplimentar Uponor este folositpentru a dispersa orice efort posibil.
Interior
Răşina epoxy Uponor
Înaintea de montarea unei trecerietanşe Uponor PWP, se practică ogaură în perete care poate acoperităcu răşină Uponor !
Conducta din bră de cimentUponor
Etanşările de perete Uponor PWP potde asemenea să e montate într-oconductă Uponor din bră de ciment.Conducta Uponor din bră de ciment,poate xată în zidărie.
HARDENER
EPOXY RESIN
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
18/58
18 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Manşonul Uponor termocontractabil Banda de avertizare Uponor
Mantaua deteriorată poate fireparată uşor şi sigur cu manşonultermocontractabil de reparaţiiUponor .
Banda de avertizare Uponor esteaplicată peste ţeava flexibilăpreizolată pentru marcarea şi identi-ficarea ei.
Piesele pentru xare ţeavă la coturi Conductă de ghidaj la coturi
Pentru xarea şi ghidarea ţevii exactpe poziţie în pardoseală.Mai multe piese de îndoire în unghipot împreună, cap la cap. Conducta de ghidaj la coturi este
folosită ca o carcasă a ţevii prei-
zolate, dirijând elementele ţevii
preizolate în clădire. Materialul este
PVC plastic.
Accesorii suplimentare
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
19/58
19R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Proiectare
Traseul elementelor
Sistemul de ţeavă exibilă preizolată văpermite să proiectaţi şanţurile exibil şisă ţineţi cont de mediu.Când ţeava este dirijată în clădire,la alegerea locului intrării trebuie ţinutcont de cerinţele de spaţiu ale razei de
îndoire ale elementului respectiv.
RacordareaImplementarea celui mai protabil sis-
tem în termeni de costuri de operare şiinstalare, este cel mai bine realizatăfolosind elemente multiple de ţeavă.Pierderea de căldură este cea maimică la produsele Quattro care suntrecomandate în special pentru imple-mentare la case terasate şi mici clădiride apartamente.Numărul racordurilor din sol poate redus pentru clădiri mici, folosind teh-
nica legării. Tehnica este îndeosebiindicată în locurile unde casele suntaliniate şi dimensiunileproduselor Quattro sunt cele adecvate.Suprafaţa la sol necesară sistemuluiQuattro este foarte mică, permiţând caracordurile de legare să e făcute îninteriorul apartamentelor. De exemplu,baza ridicată a unui hol poate folosităca un spaţiu de legătură.
Linii speciale ale clădirii
Când diferite proprietăţisunt alimentatetermic, de la acelaşi punct, racordăriledrepte de la casă la camera centraleisunt recomandate când camera centra-lei este plasată într-o poziţie centrală.Montajul este foarte uşor, ind un tra-seu fără îmbinări. Şanţurile nu trebuiesă e menţinute descoperite pentru tes-tul de presiune.Bucăţile de ţeavă folosite nu sunt mari
şi aceasta permite utilizarea elemente-lor multiple ale ţevii.
Combinarea produselorSistemele de radiatoare cu apăerbinte pot folosite cu elementelede ţeavă mari de circulaţie ale pro-duselor Quattro şi Aqua Twin. Beneciile oferite de elementele cudouă şi patru ţevi pot luate în calcul
în aceste locuri. Prin combinarea pro-duselor, poate creat un sistem
funcţional şi poate garantatăfuncţionarea ecientă a căminelor
Centrală termică
(încălzi re centralizată)
Quattro
Quattro
Quattro
Quattro
Aqua Twin
Thermo Twin
Bazele proiectării
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
20/58
20 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Acoperire şanţ minimă fără sarcina de trac Acoperire şanţ cu sarcină de trac conform SLW 60
Flexibilitatea ţevilor Uponor permiteadaptarea fără probleme la teren, fărănici o condiţie de traseu. Este posibilsă dirijăm traseul deasupra sau pe subţevi existente în timp ce obstacolelepot simplu ocolite. Chiar şi aşezareasistemului de ţevi sub o pânză de apăfreatică de 3 metri (0.3 bar) estepermisă.
Sistemul necesită doar excavarea unuişanţ îngust de adâncime mică. Ampla-
sarea nu necesită în mod normal ca unoperator să e în şanţ, cu execpţialocurilor unde se fac racorduri sauramicaţii.La locul racordurilor şi ramicaţiilor, tre-buie creat un spaţiu de lucru potrivitpentru operaţiile respective. Oriundedirecţia ţevii se schimbă, raza decurbură trebuie să nu e mai micădecât minimul permis de diversele sis-teme de ţevi.
Este convenabil să executăm toateexcavaţiile pe o parte a şanţului.Ţeava este apoi derulată de la capătul
liber şi aşezată direct în şanţ. Esteesenţial să evităm deteriorarea manta-lei externe a ţevii. Este necesar un pat de nisip fărăpietriş. Granulaţia nisipului poate
între 0 şi 2/3 mm. Niciodată să nuincludeţi obiecte cu margini tăioasesau ascuţiete în şanţ. Îndoirea ţevii cugrijă, (la cel puţin 10 cm deasupra şidedesuptul mantalei externe,şi pereţilor şanţului) are un efect cru-
cial asupra durabilităţii mantaleiexterne de protecţie. Când decidem oacoperire minimă, trebuie avută învedere posibilitatea deteriorării de lalucrările de construcţie ulterioare, depe parcursul întregii durate de viaţă aconstrucţiei. Materialul de umpleretrebuie compactat în straturi, şi tre-buie folosit un utilaj pentru aceastapentru un strat de acoperire de 500mm grosime. Când acest lucru a fostfăcut, aşezaţi o bandă de avertizare şi
acoperiţi şanţul.Când acoperiţi cu un strat de grosimede la 0.5 metri până la maxim 6 metri,
mantaua externă de protecţie Uponor poate suporta sarci-na solului şi a tracului.Certicarea bazată pe ATV DVWK-A127, demonstrează căţevile noastre, dacă sunt amplasate conform condiţiilor pre-scrise, pot suporta sarcini ale tracului greu (SWL60 = 60t)conform cu pagina de lucru ATV-A 127. Inelele derigidizare ale mantalei externe de protecţie sunt testateconform EN ISO 9969.
Atenţie ! Nu s-a ţinut cont de limitele locale de îngheţ .
Toate dimen-siunile în mm
min. 0,5 m
max 6,0 m
Proiectarea traseului ţevii
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
21/58
21R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Alternativă: Tub perete, rezistent la apăfără presiune (NPW)
Produs Numărnecesar
Kit trecere Uponor NPW 1
Uponor Thermo Twin
Căciuli de capăt Uponor Twin 1
Racord adaptor Uponor 6 bar 2
Racord Uponor let interior 2
CBA
Conectare cu Thermo Twin1
*) optional, vericaţi necesitatea
1
3
5
2
4
7
6
Alternativă: Tub perete , rezistent la apăsub presiune (PWP)
Produs Numărnecesar
Ţeavă Uponor bră ciment *) 1
Uponor Thermo Twin
Garnitură perete Uponor PWP 1
Kit suplimentar Uponor PWP *) 1
Căciuli de capăt Uponor Twin 1
Racord adaptor Uponor 6 bar 2
Racord Uponor let interior 2
Exemple de instalare
Alternativă: Tub perete , rezistent la apăsub presiune (PWP)
Produs Numărnecesar
Uponor Thermo Twin 1
Căciuli de capăt Uponor Twin
Racord cu Uponor 6 bar 1
Racord Uponor flet interior 1
Etanşare trecere Uponor 1
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
22/58
22 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Conectare cu Thermo Single2
Circuit tur pentru încălzire la oclădire auxiliară cu Quattro
3Ramicaţie din Thermo Single cu ţeviThermo Twin ramicaţie cu set de
izolare H
4
*) optional, vericaţi dacă e necesar
Ramicaţii Thermo Twin cu setde izolare T
5 Racorduri Thermo Twin cu set deizolare drept
6 Ramicaţie din Thermo Single laThermo Twin
7
Produs Numărnecesar
Uponor Thermo Twin
Set izolator Uponor în T 1
Căciuli de capăt Uponor, Twin 3
Niplu Uponor conversie 6 bar 6
Racord T Uponor 2
Reducţie Uponor *)
Produs Numărnecesar
Uponor Thermo Twin
Kit izolator Uponor drept 1
Căciuli de capăt Uponor , Twin 2
Niplu Uponor conversie 6 bar 4
Mufă Uponor let exterior 2
Produs Numărnecesar
Uponor Thermo Single
Uponor Thermo Twin
Set izolator Uponor H 1
Căciuli de capăt Uponor, Single 4
Căciuli de capăt Uponor, Twin 1
Niplu Uponor conversie 6 bar 6
Racord T Uponor 2
Reducţie Uponor *)
Produs Numărnecesar
Uponor Thermo Single
Uponor Thermo Twin
Cămin Uponor 1
Căciuli de capăt Uponor, Single 4
Căciuli de capăt Uponor, Twin 2
Niplu Uponor conversie 6 bar 8
Racord T Uponor 4
Reducţie Uponor *)
Cot Uponor *)
Conectaţi ţeava dacă este necesar, ţeavă sau
niplu dublu (răspunderea clientului)
Tub pt.doi pereţi, presurizat (PWP), încălzire(tur+retur), apă rece şi caldă sau apă caldă şirecirculată
Produs Numărnecesar
Tub ciment Uponor PWP *) 2
Uponor Quattro
Tub perete Uponor PWP 2
Căciuli de capăt Uponor Quattro 2
Kit suplimentar Uponor DWD *) 2
Niplu Uponor de conversie 6 bar 4
Niplu Uponor conversie10 bar 4
Racord Uponor let interior 8
Tub pt. doi pereţi, nepresurizat la apă(NPW)
Produs Numărnecesar
Uponor Thermo Single
Căciuli de capăt Uponor, Single 2
Niplu Uponor de conversie 6 bar 2
Racord Uponor let interior 2
Kit trecere Uponor 2
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
23/58
23R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Dimensionarea ţevilor de încălzire
Tabel pentru pierderi de presiuneŢeavă încălzire : Bazată pe 50 °C temperatura apei*
DIM: 25 x 2,3 32 x 2,9 40 x 3,7 50 x 4,6 63 x 5,8 75 x 6,8 90 x 8,2 110 x 10 d
i [mm]: 20,4 26,2 32,6 40,8 51,4 61,4 73,6 90,0
Debit Volumetric
l/h l/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s
36 0,01
72 0,02
108 0,03
144 0,04
180 0,05 0,020 0,153
216 0,06 0,028 0,184
252 0,07 0,037 0,214
288 0,08 0,047 0,245
324 0,09 0,058 0,275
360 0,1 0,071 0,306 0,020 0,185
720 0,2 0,244 0,612 0,069 0,371 0,024 0,240
1080 0,3 0,507 0,918 0,143 0,556 0,049 0,359
1440 0,4 0,850 1,224 0,239 0,742 0,082 0,479 0,028 0,306
1800 0,5 1,270 1,530 0,358 0,927 0,122 0,599 0,041 0,382
2160 0,6 1,765 1,836 0,496 1,113 0,169 0,719 0,058 0,459
2520 0,7 2,330 2,142 0,655 1,298 0,223 0,839 0,076 0,535
2880 0,8 2,966 2,448 0,834 1,484 0,284 0,958 0,097 0,612 0,032 0,386
3240 0,9 3,668 2,754 1,031 1,669 0,351 1,078 0,119 0,688 0,039 0,434
3600 1 4,438 3,059 1,247 1,855 0,425 1,198 0,144 0,765 0,047 0,4823960 1,1 5,272 3,365 1,481 2,040 0,504 1,318 0,171 0,841 0,056 0,530
4320 1,2 6,171 3,671 1,733 2,226 0,590 1,438 0,200 0,918 0,066 0,578 0,028 0,405
5040 1,4 8,156 4,283 2,290 2,597 0,779 1,677 0,265 1,071 0,087 0,675 0,037 0,473
5760 1,6 10,388 4,895 2,916 2,968 0,992 1,917 0,337 1,224 0,111 0,771 0,047 0,540
6480 1,8 12,859 5,507 3,609 3,339 1,227 2,156 0,417 1,377 0,137 0,867 0,058 0,608 0,024 0,423
7200 2 15,566 6,119 4,367 3,710 1,485 2,396 0,504 1,530 0,166 0,964 0,071 0,675 0,030 0,470
7920 2,2 18,504 6,731 5,190 4,081 1,764 2,636 0,599 1,683 0,197 1,060 0,084 0,743 0,035 0,517
8640 2,4 21,670 7,343 6,077 4,452 2,065 2,875 0,701 1,836 0,230 1,157 0,098 0,811 0,041 0,564
9360 2,6 25,060 7,955 7,026 4,823 2,387 3,115 0,810 1,989 0,266 1,253 0,114 0,878 0,047 0,611
10080 2,8 28,671 8,567 8,037 5,194 2,730 3,355 0,926 2,142 0,304 1,349 0,130 0,946 0,054 0,658
10800 3 32,500 9,178 9,109 5,565 3,094 3,594 1,049 2,295 0,345 1,446 0,147 1,013 0,061 0,705 0,023 0,472
12600 3,5 43,015 10,708 12,051 6,492 4,092 4,193 1,388 2,677 0,456 1,687 0,194 1,182 0,081 0,823 0,031 0,550
14400 4 54,847 12,238 15,360 7,419 5,214 4,792 1,768 3,059 0,580 1,928 0,247 1,351 0,103 0,940 0,039 0,629
16200 4,5 19,029 8,347 6,458 5,391 2,189 3,442 0,718 2,169 0,306 1,520 0,128 1,058 0,049 0,707
18000 5 23,050 9,274 7,821 5,990 2,650 3,824 0,869 2,410 0,370 1,689 0,154 1,175 0,059 0,786
19800 5,5 27,418 10,202 9,301 6,589 3,151 4,207 1,033 2,651 0,440 1,858 0,184 1,293 0,070 0,865
21600 6 32,127 11,129 10,896 7,188 3,690 4,589 1,210 2,892 0,516 2,026 0,215 1,410 0,082 0,943
23400 6,5 37,172 12,056 12,604 7,787 4,268 4,972 1,399 3,133 0,596 2,195 0,248 1,528 0,095 1,022
25200 7 14,425 8,386 4,884 5,354 1,601 3,374 0,682 2,364 0,284 1,645 0,108 1,100
27000 7,5 16,357 8,985 5,537 5,737 1,815 3,614 0,773 2,533 0,322 1,763 0,123 1,179
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
24/58
24 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
DIM: 25 x 2,3 32 x 2,9 40 x 3,7 50 x 4,6 63 x 5,8 75 x 6,8 90 x 8,2 110 x 10 d
i [mm] 20,4 26,2 32,6 40,8 51,4 61,4 73,6 90,0
Debit Volumetric
l/h l/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s
228800 8 18,398 9,584 6,227 6,119 2,041 3,855 0,869 2,702 0,362 1,880 0,138 1,258
30600 8,5 20,548 10,183 6,954 6,501 2,279 4,096 0,970 2,871 0,404 1,998 0,154 1,336
32400 9 22,806 10,782 7,717 6,884 2,528 4,337 1,076 3,040 0,448 2,115 0,171 1,415
34200 9,5 25,170 11,381 8,516 7,266 2,790 4,578 1,187 3,208 0,495 2,233 0,188 1,493
36000 10 27,639 11,980 9,350 7,649 3,062 4,819 1,303 3,377 0,543 2,350 0,207 1,572
37800 10,5 10,220 8,031 3,347 5,060 1,424 3,546 0,593 2,468 0,226 1,650
39600 11 11,125 8,414 3,643 5,301 1,550 3,715 0,646 2,586 0,246 1,729
43200 12 13,038 9,178 4,268 5,783 1,816 4,053 0,756 2,821 0,288 1,886
46800 13 15,089 9,943 4,939 6,265 2,101 4,391 0,875 3,056 0,333 2,043
50400 14 17,275 10,708 5,653 6,747 2,405 4,728 1,001 3,291 0,381 2,201
54000 15 19,595 11,473 6,412 7,229 2,727 5,066 1,135 3,526 0,431 2,358
57600 16 22,048 12,238 7,213 7,711 3,067 5,404 1,277 3,761 0,485 2,515
61200 17 8,057 8,193 3,426 5,741 1,426 3,996 0,542 2,672
64800 18 8,944 8,675 3,802 6,079 1,582 4,231 0,601 2,829
68400 19 9,872 9,157 4,197 6,417 1,746 4,466 0,663 2,987
72000 20 10,842 9,639 4,609 6,755 1,917 4,701 0,728 3,144
79200 22 12,906 10,602 5,485 7,430 2,281 5,171 0,866 3,458
86400 24 15,132 11,566 6,430 8,106 2,674 5,641 1,015 3,773
93600 26 17,520 12,530 7,443 8,781 3,095 6,111 1,175 4,087100800 28 8,523 9,457 3,544 6,581 1,345 4,401
108000 30 9,670 10,132 4,020 7,051 1,525 4,716
115200 32 10,883 10,807 4,523 7,522 1,716 5,030
122400 34 12,161 11,483 5,054 7,992 1,917 5,344
129600 36 13,503 12,158 5,611 8,462 2,128 5,659
136800 38 6,195 8,932 2,350 5,973
144000 40 6,805 9,402 2,581 6,288
162000 45 8,444 10,577 3,201 7,074
180000 50 10,243 11,752 3,883 7,860
198000 55 12,200 12,928 4,623 8,645
216000 60 5,423 9,431
234000 65 6,281 10,217
252000 70 7,196 11,003
270000 75 8,167 11,789
288000 80 9,195 12,575
Ţeavă încălzire : Bazată pe 50 °C temperatura apei*
*Factori corecţie pierdere presiune pentru alte temperaturi ale apei
°C 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Factor 1,217 1,183 1,150 1,117 1,100 1,067 1,050 1,017 1,000 0,983 0,967 0,952 0,938 0,933 0,918 0,904 0,890 0,873
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
25/58
25R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Diagramă de pierderi de presiuneNomograma este calculată la o temperatură a agentului termic de +70°C *
kPa/m
10
7
6
5
4
3
2
1
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,07
0,06
0,05
0,04
0,03
0,02
0,02
0,007
0,006
0,005
0,004
0,003
0,002
0,001
0,0007
0,0006
0,0005
0,0004
0,0003
0,0002
0,0001
0,01 0,02 0,03 0,05 0,070,04 0,06
0,1 0,2 0,3 0,5 0,70,4 0,6
1 2 3 5 7 104 6
20 30 50 7040 60
100 l/s
6,00
7,00
10,00
12,00
m/s
2 5
x 2 , 3
3 2
x 2 , 9
4 0
x 3 , 7
5 0
x 4 , 6
6 3
x 5 , 8
7 5
x 6 , 8
9 0
x 8 . 2
1 1 0
x 1
0 , 0
0,01
0,10
0,15
0,20
0,25
0,30
0,40
0,50
0,60
1,00
1,25
1,50
1,75
2,00
2,50
3,00
4,00
5,00
0,03
0,04
0,05
0,06
0,07
*Factori corecţie pierdere presiune pentru alte temperaturi ale apei
Temperatură °C 90 80 70 60 50 40 30 20
Factor 0,95 0,98 1,00 1,02 1,05 1,10 1,14 1,20
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
26/58
26 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Bazele dimensionării instalaţiilor de încălzireDacă este necesar, folosirea uneipierderi de presiune pe metru consi-derabil mai mari, este mai degrabăposibilă când dimensionăm ţevi dinplastic pentru încălzire, decât atuncicând dimensionăm ţevi de oţel. Nu
există limitări pentru viteza apei, de-oarece ţevile din plastic nu seerodează. Domeniul de pierderi depresiune recomandate a fost înnegrit.Diagrama include valorile nominaleΔϑ 20, 45 şi 30 pentru schimbări ale
temperaturii. Mărimea poate de ase-menea selectată funcţie de debitulmasic. Debitul masic necesar poate calculat cu formula:
Exemplu de dimensionare :
Obiectivul este selectarea ţevilor de încălzire pentru încălzi re şi a spaţiu luipentru centrala termică.Suprafaţa unei clădiri este de 300m² şi înălţimea camerelor este de2.9 m. Clădirea are încălzire cu radi-atoare normale cu temperatura apeipe tur de ϑ
1 = +70°C şi pe retur de
ϑ2= +40°C.
Pasul 1.Determină necesarul puterii termice(volumul clădirii x necesarul specicde căldură).F = 300 m² x 2.9 m x 25 W/m³= 21750 W≈ 22 kW
Pasul 2.Determină correct Δϑ-axle saudebitul masic .Δϑ= (ϑ1 – ϑ2)=30 K
ṁ =Q
Δϑ · cp
Necesar specic de căldură [W/m³]
Casa Casa Clădire cuunifamilială cu terasă apartamente
15 – 22 15 – 26 15 – 20 nou
22 – 26 15 – 26 20 – 28 veche
undeṁ = debitul de masă kg/sQ = puterea termică KW
Δϑ = Diferenţa de temperatură °Cc
p = căldura specică a apei
4,19 kJ/kgK
P i e r d e r e
a d e p r e s i u n e R [ k P a / m ]
1,0 2 3 4 5 6 7 8 10
0,02 0,03 0,05 0,1 0,2 0,3 0,4 0,5 1,0 2 3 4 5 6 7 8 10 12ṁ [kg/s]
3 4 5 6 7 8 10 20 30 40 50 100
20 30 40 50 100 200 300 500
200 300 500 1000 1 500
1,5 2 3 4 5 6 7 8 10 20 30 40 50 100 200 300 500 1000
1 8 / 1 3
, 0
2 5 / 2 0
, 4
3 2 / 2 6
, 0
4 0 / 3 2
, 6
5 0 / 4 0
, 8
6 3 /
5 1
, 4
7 5 / 6 1 , 2
9 0 / 7 3
, 6
1 1 0 / 1 0
, 0
v = 3 , 0 m / s
2 , 0
1 , 5
1 , 0
0 , 5
0 , 3
1,5
1,0
0,8
0,60,5
0,4
0,3
0,2
0,1
0,08
0,06
0,05
0,04
0,03
0,02
Q [kW], ∆ ϑ= 20 K
Q [kW], ∆ ϑ= 45 K
Q [kW], ∆ ϑ= 30 K
• temperatura+55°C •incl. 20% rezistenţa la frecare pentru fiting .Coeficientul rugozitate ţeavă PEX 0..005
Pasul 3.Selectează dimensiunea corectă a ţeviidin zona pierderile de presiune recoman-date conform diagramei Δϑ= 30 K şiQ = 22 kW=› mărime ţeavă ø 25/20.4 mm
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
27/58
27R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Tabel de dimensionare rapidăŢeavă de încălzire
Domeniu (ecart de temperatură)
∆ϑ = 10 K ∆ϑ = 15 K ∆ϑ = 20 K ∆ϑ = 25 K ∆ϑ = 30 K ∆ϑ = 35 K ∆ϑ = 40 K Debit de Tip ţeavă Tip ţeavă Tip ţeavămasă ∆p,v ∆p, v ∆p, v
25/20.4 32/26.210 kW 15 kW 20 kW 25 kW 30 kW 35 kW 40 kW 860 kg/h 0,30974 kPa/m 0,09786 kPa/m
0,74962 m/s 0,46148 m/s
32/26.2 40/32.6 50/40.820 kW 30 kW 40 kW 50 kW 60 kW 70 kW 80 kW 1720 kg/h 0,32917 kPa/m 0,11240 kPa/m 0,03872 kPa/m
0,92296 m/s 0,58708 m/s 0,37481 m/s
32/26.2 40/32.6 50/40.830 kW 45 kW 60 kW 75 kW 90 kW 105 kW 120 kW 2580 kg/h 0,66923 kPa/m 0,22851 kPa/m 0,07872 kPa/m
1,38445 m/s 0,88062 m/s 0,56221 m/s
40/32.6 50/40.8 63/51.440 kW 60 kW 80 kW 100 kW 120 kW 140 kW 160 kW 3440 kg/h 0,37806 kPa/m 0,13023 kPa/m 0,04348 kPa/m
1,17416 m/s 0,74962 m/s 0,47232 m/s
50/40.8 63/51.4 75/61.250 kW 75 kW 100 kW 125 kW 150 kW 175 kW 200 kW 4300 kg/h 0,19244 kPa/m 0,06425 kPa/m 0,02805 kPa/m
0,93702 m/s 0,59040 m/s 0,41646 m/s
50/40.8 63/51.4 75/61.260 kW 90 kW 120 kW 150 kW 180 kW 210 kW 240 kW 5160 kg/h 0,26445 kPa/m 0,08839 kPa/m 0,03859 kPa/m
1,12443 m/s 0,70848 m/s 0,49975 m/s
50/40.8 63/51.4 75/61.270 kW 105 kW 140 kW 175 kW 210 kW 245 kW 280 kW 6020 kg/h 0,34945 kPa/m 0,11513 kPa/m 0,05053 kPa/m
1,31183 m/s 0,82656 m/s 0,58304 m/s
63/51.4 75/61.2 90/73.680 kW 120 kW 160 kW 200 kW 240 kW 280 kW 320 kW 6880 kg/h 0,14654 kPa/m 0,06334 kPa/m 0,02657 kPa/m
0,94464 m/s 0,66633 m/s 0,46072 m/s
63/51.4 75/61.2 90/73.690 kW 135 kW 180 kW 225 kW 270 kW 315 kW 360 kW 7740 kg/h 0,18133 kPa/m 0,07836 kPa/m 0,03266 kPa/m
1,06272 m/s 0,74962 m/s 0,51831 m/s
63/51.4 75/61.2 90/73.6100 kW 150 kW 200 kW 250 kW 300 kW 350 kW 400 kW 8600 kg/h 0,21940 kPa/m 0,09480 kPa/m 0,03905 kPa/m
1,18080 m/s 0,83291 m/s 0,57590 m/s
63/51.4 75/61.2 90/73.6110 kW 165 kW 220 kW 275 kW 330 kW 385 kW 440 kW 9460 kg/h 0,26071 kPa/m 0,11263 kPa/m 0,04639 kPa/m
1,29888 m/s 0,91620 m/s 0,63349 m/s
75/61.2 90/73.6 110/90.0120 kW 180 kW 240 kW 300 kW 360 kW 420 kW 480 kW 10320 kg/h 0,13183 kPa/m 0,05429 kPa/m 0,02064 kPa/m
0,99949 m/s 0,69108 m/s 0,46217 m/s
75/61.2 90/73.6 110/90.0130 kW 195 kW 260 kW 325 kW 390 kW 455 kW 520 kW 11180 kg/h 0,15238 kPa/m 0,06274 kPa/m 0,02385 kPa/m
1,08278 m/s 0,74867 m/s 0,50068 m/s
75/61.2 90/73.6 110/90.0
140 kW 210 kW 280 kW 350 kW 420 kW 490 kW 560 kW 12040 kg/h 0,17427 kPa/m 0,07174 kPa/m 0,02727 kPa/m1,16608 m/s 0,80626 m/s 0,53919 m/s
75/61.2 90/73.6 110/90.0150 kW 225 kW 300 kW 375 kW 450 kW 525 kW 600 kW 12900 kg/h 0,19746 kPa/m 0,08129 kPa/m 0,03089 kPa/m
1,24937 m/s 0,86385 m/s 0,57771 m/s
75/61.2 90/73.6 110/90.0160 kW 240 kW 320 kW 400 kW 480 kW 560 kW 640 kW 13760 kg/h 0,22196 kPa/m 0,09136 kPa/m 0,03472 kPa/m
1,33266 m/s 0,92144 m/s 0,61622 m/s
90/73.6 110/90.0170 kW 255 kW 340 kW 425 kW 510 kW 595 kW 680 kW 14620 kg/h 0,10196 kPa/m 0,03874 kPa/m
0,97903 m/s 0,65473 m/s
90/73.6 110/90.0180 kW 270 kW 360 kW 450 kW 540 kW 630 kW 720 kW 15480 kg/h 0,11308 kPa/m 0,04296 kPa/m
1,03662 m/s 0,69325 m/s
90/73.6 110/90.0190 kW 285 kW 380 kW 475 kW 570 kW 665 kW 760 kW 16340 kg/h 0,12472 kPa/m 0,04738 kPa/m
1,09421 m/s 0,73176 m/s
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
28/58
28 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Ţeavă de încălzire
Domeniu (ecart de temperatură)
∆ϑ = 10 K ∆ϑ = 15 K ∆ϑ = 20 K ∆ϑ = 25 K ∆ϑ = 30 K ∆ϑ = 35 K ∆ϑ= 40 K Debit de Tip ţeavă Tip ţeavă Tip ţeavămasă ∆p,v ∆p, v ∆p, v
90/73.6 110/90.0200 kW 300 kW 400 kW 500 kW 600 kW 700 kW 800 kW 17200 kg/h 0,13687 kPa/m 0,05199 kPa/m
1,15180 m/s 0,77028 m/s
90/73.6 110/90.0210 kW 315 kW 420 kW 525 kW 630 kW 735 kW 840 kW 18060 kg/h 0,14953 kPa/m 0,05680 kPa/m
1,20939 m/s 0,80879 m/s
90/73.6 110/90.0220 kW 330 kW 440 kW 550 kW 660 kW 770 kW 880 kW 18920 kg/h 0,16269 kPa/m 0,06179 kPa/m
1,26698 m/s 0,84730 m/s
90/73.6 110/90.0230 kW 345 kW 460 kW 575 kW 690 kW 805 kW 920 kW 19780 kg/h 0,17635 kPa/m 0,06697 kPa/m
1,32457 m/s 0,88582 m/s
90/73.6 110/90.0240 kW 360 kW 480 kW 600 kW 720 kW 840 kW 960 kW 20640 kg/h 0,19051 kPa/m 0,07234 kPa/m
1,38216 m/s 0,92433 m/s
110/90.0250 kW 375 kW 500 kW 625 kW 750 kW 875 kW 1000 kW 21500 kg/h 0,07790 kPa/m
0,96285 m/s
110/90.0260 kW 390 kW 520 kW 650 kW 780 kW 910 kW 1040 kW 22360 kg/h 0,08364 kPa/m
1,00136 m/s
110/90.0270 kW 405 kW 540 kW 675 kW 810 kW 945 kW 1080 kW 23220 kg/h 0,08956 kPa/m
1,03987 m/s
110/90.0280 kW 420 kW 560 kW 700 kW 840 kW 980 kW 1120 kW 24080 kg/h 0,09567 kPa/m1,07839 m/s
110/90.0290 kW 435 kW 580 kW 725 kW 870 kW 1015 kW 1160 kW 24940 kg/h 0,10196 kPa/m
1,111690 m/s
110/90.0300 kW 450 kW 600 kW 750 kW 900 kW 1050 kW 1200 kW 25800 kg/h 0,10843 kPa/m
1,15541 m/s
110/90.0310 kW 465 kW 620 kW 775 kW 930 kW 1085 kW 1240 kW 26660 kg/h 0,11507 kPa/m
1,19393 m/s
110/90.0320 kW 480 kW 640 kW 800 kW 960 kW 1120 kW 1280 kW 27520 kg/h 0,12190 kPa/m
1,23244 m/s
110/90.0
330 kW 495 kW 660 kW 825 kW 990 kW 1155 kW 1320 kW 28380 kg/h 0,12890 kPa/m1,27096 m/s
110/90.0340 kW 510 kW 680 kW 850 kW 1020 kW 1190 kW 1360 kW 29240 kg/h 0,13608 kPa/m
1,30947 m/s
110/90.0350 kW 525 kW 700 kW 875 kW 1050 kW 1225 kW 1400 kW 30100 kg/h 0,14344 kPa/m
1,34798 m/s
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
29/58
29R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
P i e r d e r i d e
c ă l d u r ă [ W / m ]
Diferenţa de temperatură [K ]
10 9030 50 70
0
50
5
15
10
20
25
30
35
40
45
110/200
90/200
75/200
63/175
50/175
40/175
32/140
25/140
Conductivitate termică a solului : 1,0 W/mKGrosime strat acoperire a ţevii în şanţ : 0,8 m
Exemplu pentru Uponor Thermo Single 50/175
ϑM = Temperatură mediuϑ
E = Temperatură sol
∆ϑ = Diferenţă de temperatură (K)
∆ϑ = ϑM – ϑE ϑ
M = 75 °C
ϑE = 5 °C
∆ϑ = 75 – 5 = 70 KPierderi căldură: 15,75 W/m
6 V 047
Pierderea de căldură
NotăDiagrama arată pierderea de căldură pe o ţeavă.Pierderile de căldură pe tur şi retur trebuie calculate sep-
arat. Pentru a obţine pierderile totale, adunaţi pierderilepe tur şi retur.
Pierderi de căldură la ţeava Uponor Thermo Single
Notă:Pierderile de căldură din diagramă sunt calculate cu un factor de siguranţă de 1,05 conform cu cerinţele normei germane"VDI-AG Gütesicherung". Ele depind de toleranţele din producţie.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
30/58
30 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Conductivitate termică a solulului : 1,0 W/mKGrosime strat acoperire a ţevii în şanţ: 0,8 m
P i e r d r i c ă l d u
r ă [ W / m ]
Diferenţă temperatură [K]
10 9030 50 70
0
45
5
15
10
20
25
30
35
40
2 x 63/200
2 x 50/200
2 x 40/175
2 x 32/175
2 x 25/175
Exemplu pentru Uponor Thermo Twin 2 x 32/175
ϑV = Temperatură tur ϑR = Temperatură returϑ
E = Temperatură sol
∆ϑ = Diferenţa de temperatură (K)∆ϑ = (qV – qR)/ 2 – qE ϑV = 70 °Cϑ
R = 30 °C
ϑE = 5 °C
∆ϑ
= (70 + 40)/2 – 5 = 50 KPierderi de căldură : 12,50 W/m
6 V 047
Pierderile de căldură la ţeava Uponor Thermo Twin
NotăDatele despre pierderile de căldură din diagramă sunt calculate cu un coecient de siguranţă de 1,05 conform cu normagermană "VDI-AG Gütesicherung". Ele depind de toleranţele de producţie comunicate.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
31/58
31R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Ţeavă pentru apă : Bazat pe temperatura apei de 50 °C *
Tabelul pierderilor de presiune
Dimensionarea ţevilor pentru apă caldă
DIM: 25 x 3,5 32 x 4,4 40 x 5,5 50 x 6,9 63 x 8,7ID [mm] 18 23,2 29 36,2 45,6
Debit de voluml/h l/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s kPa/m m/s
6 0,01
72 0,02108 0,03144 0,04
180 0,05 0,036 0,196216 0,06 0,050 0,236
252 0,07 0,065 0,275288 0,08 0,083 0,314
324 0,09 0,103 0,354360 0,1 0,124 0,393 0,037 0,237
720 0,2 0,429 0,786 0,127 0,473 0,043 0,3031080 0,3 0,890 1,179 0,263 0,710 0,089 0,454 0,031 0,2911440 0,4 1,494 1,572 0,442 0,946 0,150 0,606 0,051 0,389
1800 0,5 2,233 1,965 0,660 1,183 0,224 0,757 0,076 0,4862160 0,6 3,103 2,358 0,917 1,419 0,311 0,908 0,106 0,583 0,034 0,367
2520 0,7 4,098 2,751 1,210 1,656 0,410 1,060 0,140 0,680 0,045 0,4292880 0,8 5,215 3,144 1,540 1,892 0,522 1,211 0,178 0,777 0,058 0,490
3240 0,9 6,452 3,537 1,905 2,129 0,645 1,363 0,220 0,874 0,071 0,5513600 1 7,806 3,930 2,304 2,366 0,780 1,514 0,266 0,972 0,086 0,6123960 1,1 9,275 4,323 2,737 2,602 0,927 1,665 0,316 1,069 0,102 0,674
4320 1,2 10,857 4,716 3,203 2,839 1,084 1,817 0,370 1,166 0,120 0,7355040 1,4 4,233 3,312 1,433 2,120 0,489 1,360 0,158 0,857
5760 1,6 5,390 3,785 1,824 2,422 0,622 1,555 0,201 0,9806480 1,8 6,672 4,258 2,257 2,725 0,769 1,749 0,248 1,102
7200 2 8,075 4,731 2,731 3,028 0,931 1,943 0,301 1,2257920 2,2 9,598 5,204 3,245 3,331 1,106 2,138 0,357 1,3478640 2,4 11,239 5,677 3,799 3,634 1,294 2,332 0,418 1,470
9360 2,6 4,392 3,936 1,496 2,526 0,483 1,59210080 2,8 5,024 4,239 1,711 2,721 0,552 1,715
10800 3 5,694 4,542 1,939 2,915 0,626 1,83712600 3,5 7,532 5,299 2,564 3,401 0,827 2,143
14400 4 9,599 6,056 3,266 3,886 1,053 2,44916200 4,5 11,890 6,813 4,045 4,372 1,304 2,75518000 5 4,898 4,858 1,579 3,062
19800 5,5 5,824 5,344 1,877 3,36821600 6 6,823 5,830 2,198 3,674
23400 6,5 7,892 6,315 2,542 3,980
25200 7 9,032 6,801 2,908 4,28627000 7,5 10,240 7,287 3,297 4,59228800 8 3,708 4,89930600 8,5 4,140 5,205
32400 9 4,594 5,51134200 9,5 5,069 5,817
36000 10 5,566 6,12337800 10,5 6,083 6,429
39600 11 6,621 6,73643200 12 7,759 7,34846800 13 8,979 7,960
50400 14 10,279 8,573
*Factori corecţie pierdere presiune pentru alte temperaturi ale apei
°C 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Factor 1,208 1,174 1,144 1,115 1,087 1,060 1,039 1,019 1,000 0,982 0,965 0,954 0,943 0,928 0,923 0,907 0,896 0,878
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
32/58
32 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Diagramă pierderi de presiuneDiagrama pierderilor de presiune prin ţevi de apă la 70° *
kPa/m
10
7
6
5
4
3
2
1
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,07
0,06
0,05
0,04
0,03
0,02
0,02
0,007
0,006
0,005
0,004
0,003
0,002
0,001
0,0007
0,0006
0,0005
0,0004
0,0003
0,0002
0,0001
0,01 0,02 0,03 0,05 0,070,04 0,06
0,1 0,2 0,3 0,5 0,70,4 0,6
1 2 3 5 7 104 6
20 30 50 7040 60
100 l/s
0,03
0,04
0,05
0,06
0,07
0,10
0,15
0,20
0,25
0,30
0,40
0,50
0,60
1,00
1,25
1,50
1,75
2,00
3,00
4,00
5,00
6,00
2 8
x 4 , 0
3 2
x 4 , 4
4 0
x 5 , 5
5 0
x 6 , 9
6 3
x 8 , 7
7 5
x 1
0 , 3
9 0
x 1
2 , 4
1 1 0
x 1
5 , 1
1 8
x 2 , 5
0,01
m/s
*Factori corecţie pierdere presiune pentru alte temperaturi ale apei
Temperatură °C 90 80 70 60 50 40 30 20
Factor 0,95 0,98 1,00 1,02 1,05 1,10 1,14 1,20
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
33/58
33R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Ghid valori orientative pentru timpul mediu de montajechipamentele de racord şi accessorii:
Două exemple pentru timpul mediu de montaj pentru ţevileUponor :
Număr instalatori / grup minute per bucata(de ex. 2/15 = 2 instalatori necesitaă 15 minute per bucata)
Căciulă de capăt Uponor 1 / 5
Racord niplu reducţie Uponor 1 / 15
Piesă racordare Uponor 2 / 30
Piesă racord în T Uponor (completă) 2 / 40
Set izolator drept Uponor 1 / 35
Set izolator în T Uponor 1 / 45
Set izolator pentru colţ Uponor 1 / 35
Set izolator în H 2 / 50
Coloana Uponor incl. 6 x conexiunila mantaua exterioară de protecţie 2 / 50
Kit trecere Uponor apă nepresurizată NPW 1 / 30
Canal trecere Uponor apă sub presiune PWP 1 / 30
Tip ţeavă 25 Metri 50 Metri 100 Metri
instalator/minute instalator/minute instalator/minute
Single:
25 2 / 15 2 / 30 3 / 40
32 2 / 15 2 / 30 3 / 40 40 2 / 20 2 / 40 3 / 60
50 2 / 20 2 / 40 3 / 60
63 3 / 20 3 / 40 4 / 60
75 3 / 25 3 / 50 4 / 75
90 3 / 30 4 / 60 5 / 90
110 3 / 30 4 / 60 5 / 90
Twin:
25 2 / 20 2 / 40 3 / 60
32 2 / 20 2 / 40 3 / 60
40 2 / 30 3 / 40 4 / 60
50 3 / 25 3 / 50 5 / 90
63 3 / 30 4 / 60 5 / 90 Quattro:
2 / 30 3 / 40 4 / 60
Timpul necesar pentru instalarea aces-tor sisteme de ţevi depinde de condiţiilelocale. În tabelul următor, obstacolele,subtraversările, condiţiile meteo, timpiide montaj pentru tinguri, şi alte
aspecte nu au fost luate în consider-are. Folosirea unor utilaje cum suntexcavatoare sau vinciuri de cablurinu a fost inclusă în calcul.
Timpii de instalare menţionaţi în continuare sunt minute de grup pentru numărul corespunzător de instalatori(neincluzând lucrări de excavare). Cifrele sunt doar orientative pentru calcule.
Examplu 1: Instalare a 2 x 25 m Uponor Thermo Single 63 mm 3 instalatori fără ajutoare suplimentare
Timp instalare: 3 x 20 minute
Examplu 2: Instalarea a unui kit trecere izolator NPW 1 instalator fără ajutoare suplimentare Ghid valori pentru Căciuli de capăt 1/5, niplu conversie
1/15, set manşon trecere perete set NPW 1/30
Timp instalare : 1 x 50 minutes
Instalare
Ghid de valori pentru procesul de instalare
Timp instalare
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
34/58
34 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Manipularea ţevilor
Vă rugăm să reţineţi !
Când ridicaţi colacii de ţeavă, folosiţiun cablu de nylon sau textile cu olăţime de cel puţin 50 mm. Dacăridicaţi colaci cu un încărcător frontalcu furci sau cu un utilaj similar, fur-cile trebuie rotunjite sau căptuşite.Datorită exibilităţii şi masei colacilor,diametrul colacului poate varia cu 30cm.
Folosiţi numaicurele detransport aprobate, cu
lăţimea minimă50 mm
Ridicaţi colacii numai pentru scurttimp. Colacii trebuie asiguraţi
împotriva deplasării
Vă rugăm să reţineţi !Masele plastice, nu trebuieniciodată să e puse încontact cu substanţeagresive ca ulei de motor,solvenţi, conservanţi pent-
ru lemn sau similare.
Stocare, ridicare şi manipulare colacţeavăAu fost montate capace de protec-ţie la capetele ţevii, pentru a protejaţevile interioare din PE-Xa faţă de lumi-na soarelui sau alte deteriorări, inclusivla umplere cu pământ. Protejaţi colaculde ţeavă de obiecte ascuţite pe timpultransportului şi depozitării.
Nu târâţi colacul pe suprafeţe rugoase.Asiguraţi-vă că tamburul cu ţeavă
preizolată nu este strivit şi ţeava nueste deformată prin îndoire pe timpuldepozitării. Păstraţi colacii în poziţieorizontală. Colacii de ţeavă şicamerele de racordare pot depozitate
în spaţii deschise, alte componente alesistemului trebuie depozitate în spaţiiacoperite.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
35/58
35R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Păstraţi colacii cu ţeavă livrată pe câtde mult e posibil în ambalajul deprotecţie până la instalare ! Apoiderulaţi ţeava direct în şanţ sau lângăel.
Instalarea ţevii din colac
Fig. 1 Fig. 2
Niciodată nu trageţi ţeava de-a lungul
solului pentru că obiecte ascuţite potcauza deteriorarea. Dacă mantaua sedeteriorează, poate reparată folosindun manşon termocontractiv. Toatepărţile traseului ţevii şi accesoriile siste-mului trebuie inspectate vizual înainteainstalării sau reparate defectele careinuenţează funcţionarea. Părţile caresunt lovite grav, trebuie înlăturate !Dacă ţeava va instalată orizontal îndeschideri, ea trebuie plasată pe punc-te de sprijin (ce folosesc nisip de exem-plu) ce previn alunecarea ulterioară.
Dacă solul este denivelat, aceste punc-te de sprijin trebuie prevăzute la ecare25 metri.
Când îngropăm secţiuni de ţeavă,capetele cu lungimea de 3 până la 5metri trebuie lăsate libere pentru mon-tarea sistemelor de racordare. Laschimbarea materialului ţevii din oţel înmasă plastică, forţele de dilatare trebuietranferate de la ţeava de oţel la cea demasă plastică pe timpul schimbărilor de
temperatură. În acest caz, se evită
Atenţie :Capetele ţevii din colac se pot desprinde cândbenzile textile sunt desfăcute (vezi Fig. 1). Deaceea asiguraţi-vă ca spirele ţevii din colaci săe tot timpul xate cu două-trei benzi. (vezi Fig.2).
apariţia forţelor de forfecare; dacă estenecesar, montaţi puncte xe în jurulcapetelor ţevii de oţel. Dacă lucraţi latemperaturi extrem de joase, (rigiditateaţevii este crescută), ţevile trebuie depo-zitate într-un spaţiu încălzit sau trebuieefectuat montajul într-un spaţiu încălzitdupă care instalaţia trebuie mutată direct
în şanţ.
Derularea ţevii de la exterior (recomandată pentru ţeavă cu mantaua externă dediametru 200 mm sau lungimi ale colacului de peste 100 m):
Înlăturaţi folia de ambalare. Desfaceţiprima bandă de nylon de la capătulexterior al ţevii, desfaceţi capătul ţeviidin colac şi xaţi colacul cu restulspirelor cu banda de nylon. Atenţie –când desfaceţi prima bandă de nylon,capătul ţevii este pretensionat şi poatesă vă rănească ! Fixaţi capătuldesfăcut al ţevii (de ex. îngropându-l
sau punând nisip peste el) şi derulaţimai departe până la următoarea bandăde nylon. Repetaţi procesul până cândcolacul este complet derulat.
Derularea ţevii din colac de la interior (recomandată pentru ţevi cu mantaua deprotecţie cu diametre între 140 mm şi 175 mm sau lungimi ale colacului de până la100m):
Nu detaşaţi ambalajul exterior! Tăiaţibenzile de xare din nylon. Scoateţi
capătul interior al ţevii din colac (nuscoateţi capacul de protecţie al ţeviipână când aceasta nu este
conectată!). Fixaţi capetele ţevii (deex. îngropându-le sau acoperindu-le
cu nisip). Derulaţi colacul spiră cuspiră.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
36/58
36 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Raze minime de îndoire în mm
Produs 25 32 40 50 63 75 90 110
Uponor Thermo Single 250 300 350 450 550 800 1100 1200
Uponor Thermo Twin 500 600 800 1000 1200Uponor Aqua Single 350 400 450 550 650
Uponor Aqua Twin 650 700 900 1000
Uponor Quattro 800 800
Atenţie :Ţeava de PE-Xa se poate strangulasau poate distrusă dacă raza de
îndoire este mai mică decât ceaminimă specicată.
Raza de îndoire
Graţie structurii şi materialului folosit,sistemele de ţeavă exibilă preizolatăsunt extraordinar de exibile. Razelede îndoire minime permise sunt listate
în tabelul următor şi trebuie respectatecând ţeava este montată:
Nu este recomandat montajul ţevii latemperaturi de sub -15°C. Pe vremerece, montajul este mai uşor dacăţevile sunt deja încălzite, ind depo-
zitate de exemplu în prealabil înspaţii încălzite. Pe şantier, ţevile pot încălzite cu o suantă cu aer cald.
Încălzirea ţevilor deasupra unui foc
Instalare la temperaturi joase
deschis este interzisă.
Ţevile pot de asemenea montate peperete sau pe plafon, folosind colieresau plasându-le într-un canal de cab-luri.
În scopul prevenirii îndoirii ţevii,instalaţi colierele conform tabeluluialăturat. Tabelul stabileşte intervalulmaxim dintre punctele de sprijin pen-tru montaj orizontal şi vertical în
Montajul pe perete sau pe plafon
scopul prevenirii atârnării ţevii.Dacă este necesar, intervalul dintrecoliere poate scurtat.
Diametru manta Interval maxim întreOD[mm] puncte sprijin [m]
68 0,6
90 0,9140 1,2
175 1,8
200 2,2
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
37/58
37R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Dilatarea termicăDe exemplu: la instalarea unei ţevi deapă caldă, temperatura pe şantier estede 20°C. Cu cât se va dilata ţeavadacă prin ea va circula apă cu temper-atura de 70°C ?Gracul arată că diferenţa detemperatură dintre 20°C şi 70°C pro-duce o elongaţie termică de 12,5 – 2,5= 10 mm/m.
Ancorarea
Dilatarea materialului duce la micischimbări în lungimea ţevii de PE-Xa,de aceea colierele sau punctele xede sprijin trebuie să permită deplasăriale ţevii.
Ţevile de dimensiuni mici (cu diame-trele OD ≤ 50 mm) pot ancorate înmod normal de piesele de la racor-
duri). Ţevile de dimensiuni mai mari(diametrele OD ≤ 50 mm) trebuieancorate folosind un punct x.
Vă rugăm să reţineţi !Ancorarea nu se face pe mantauaexterioară a ţevii preizolate.
Fixare cot ţeavă PE-Xa cu colier (OD ≤ 50 mm)
Fixare conector x cu colier(OD > 50 mm)
S c h i m
b a r e
l u n g i m e [ m m / m ]
Temperatură [°C]
0
0 8010 20 40 60 705030
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
38/58
38 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Instrucţiuni de montajRacorduri Uponor cu colier strângere
Racordurile Uponor cu colier destrângere sunt un set complet de tin-guri care racordează ţevile UponorPEX folosite în instalaţiile sanitare şide încălzire şi în anumite aplicaţii
industriale.Racordurile Uponor cu colier destrângere sunt folosite pentru diame-tre exterioare de 25-110 mm şi presi-uni între 6 şi 10 bar. Combinaţiile din-
tre tinguri se creează folosind pieseracord. Racordurile sunt etanşatefolosind garnituri O-ring, furnizate cutingurile.
Piesele racordului cucolier de strângereVericaţi dacă locul gar-niturii o-ring este curat.Folosiţi numai o-ring-urifurnizate cu conectorii.Plasaţi o-ring-ul în
canelură. Strângeţitoate părţile manual lamaxim. Strângeţi părţilefolosind o cheie depiuliţe sau un cleşte cufălci mici la partea de jos(metal pe metal). Cândse montează alte piesela conectorii Uponorcu colier, sau la ţevi,conectorii cu let trebuiestrânşi cu in sau cânepă.
M o S 2 0 mm
1 2 3
4 5 6
7 8
Tăiaţi ţeava la unghi drept folosind un cleştespecial pentru ţeava de plastic .
Reţineţi! Nu folosiţi un ferăstrău pentrucă acesta poate lăsa resturi în ţeavă. Aceste resturi pot bloca robineţii ulterior
Înlăturaţi resturile din interiorul ţeviifolosind o u nealtă specială sau un cuţit .
Scoateţi colierul exterior de pe conectorScoateţi şurubul şi lărgiţi colierul exteriorfolosind un cleşte special.
Plasaţi şurubul între fălcile colier ului exterior şi împingeţi colierul exterior pe ţeavă
Împingeţi colierul exterior spre ţeavăReţineţi !Verificaţi dacă colierul a fost rotit
în poziţia corectă
! Urechile colierului trebuiesă se strângă deasupra .
Instalarea ţevii este uşoară şi O-ringul rămânenedeteriorat dacă el este lubrifiat
(de exemplu spray cu silicon )
Ţeava este împinsă spre umărul colieruluipână când ţeava se opreşte. Instalaţi colierulexterior astfel încât să poată fi montatşurubul prin urechile colierului.
Strângeţi fitingul Uponor. Ungeţi filetulşurubului şi şaiba înainte de strângere.Folosiţi un tipvaselina siliconică. Strângeţi piulia cu atenţie folosind o cheie. Menţineţi şurubul fixfolosind o altă cheie când strângeţi şurubul.
Strângeţi şurubul astfel ca urechile colieruluisă se atingă . Dacă ele nu se ating, aşteptaţi cel puţin 30 minute înainte de a strânge din nou piuliţa.
indicat de unsoare cum este
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
39/58
39R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Sistemul Uponor Quick & Easy (Q&E)este bazat pe memoria materialuluiţevii PEX Uponor, care face să-şirevină la forma iniţială după ce a dila-tat. Tehnica a fost patentată de Uponorşi este destinată exclusiv folosirii cuUponor PEX. Din această cauză, tre-buie folosite numai piese originaleUponor. Ţevile nu vor despachetate
înaintea instalării pentru a opri oricedeteriorare sau probleme care potapărea de la radiaţia UV. Vericaţidacă ţevile nu sunt pline cu impurităţi(fără praf, mortar şi uleiuri). Capacelela presiune trebuie puse la capeteleţevii pentru a stopa impurităţile să intre
înăuntru. Capacele trebuie să rămânăla capetele ţevii cât de mult posibil.
Pentru ca sistemul Uponor Quick &Easy să funcţioneze perfect, trebuierespectate următoarele instrucţiuni demontaj :
1
2
1
proiecţie ca. 1 mm (Dim. 16 – 25 mm)ca. 3 mm (Dim. 32 mm)
2
rotire/dilatarepaşi
(fiecare max. 45°)
3a
0 mm
Fitingurile Uponor Q&E
Trebuie montat capul de expadareUponor potrivit cu dimensiunileţevii şi tipul ei. Introduceţi capul deexpandare drept cât de mult posibil încapătul ţevii şi împingeţi maşina spreţeavă.Porniţi maşina (ţineţi apăsat între-rupătorul). Imediat ce expanderulUponor este deschis la maxim (serecunoaşte din sunetul specic),maşina comută automat pe cursa de
revenire şi capul este din nou închis.Daţi drumul la întrerupător din nou,trageţi puţin afară capul sculei din
ţeavă, astfel ca fălcile conului să sedesprindă de pereţii ţevii. Rotiţi maşinaradial cu puţin (maximum 45°) şi
împingeţi capul expanderului cât demult puteţi în capătul ţevii. Porniţimaşina. Repetaţi operaţia de dilatarede câte ori este nevoie pentru cafălcile expanderului să e introduse lalimita maximă în ţeavă. Apoi dilataţipentru ultima dată. Imediat treceţi lapunctul 4.
Operaţia de dilatare folosind expanderul Uponor Q&E cu baterie
rotire/dilatarepaşi
(fiecare max. 45°)
3b
0 mm
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
40/58
40 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
max. 10 Sec.
4
0 mmReţineţi ! Nu trebuie să fiedistanţă între ţeavă
şi capătul fitingului
Împingeţi rapid ţeava până la limităpe fiting. Menţineţi în această poziţieţeava pentru câteva secunde, pânăcând ţeava se strânge pe fiting.
Montare
Pasul 1. Tăierea țeviiTăiaţi ţeava în unghi drept cu un cuţit adecvat.Capătul ţevii trebui să e curat şi fără zgârieturi
Pasul 2. Plasarea inelului Q&E pe ţeavă
Împingeţi inelul potrivit cu dimensiunile ţevii ca săalunece pe suprafaţa ţevii până la limită. Ineluleste prevăzut cu opritor pentru un montaj sigurşi uşor.
Instrucţiuni de montaj pentru sistemul UPONOR Quick&Easy
Pentru ca sistemul UPONOR Quick & Easy să funcţioneze perfect , trebuie urmărite următoareleinstrucţiuni de montaj:
Pasul 3. Montarea tinguluiDeschideţi complet mânerele cleştelui, plasaţicapul expandor în interiorul ţevii şi apoi strângeţibraţele până sunt complet închise. Rotiţiexpandorul ( cu maxim 1/8 rotaţii). Înt re operaţiilede lărgire scoateți expandorul şi rotiţi capul astfel încât să se mişte liber fără să atingă pereţii ţevii.
Lărgirea nalăCând inelul atinge marginea capului de expandarelărgirea trebuie să se oprească. Dacă instalaţia afost excutată într-o zonă în care accesul este dicil,va necesar să menţineţi pentru maxim 3 secundela ultima lărgire pentru a avea timp sucient demontare a tingului.
Instalarea trebuie oprită atunci când temperaturaambientului este sub -15 ºC.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
41/58
41R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Căciulile de capăt Uponor
Căciulile de capăt se vor folosi întotdeauna pentru capetele ţevii.Ele protejează izolaţia contra umezelii şi separă elementele ţevii preizolate.
Montarea capacelor de la capetele ţevilorPuneţi capacele la capete înaintea racordării.
O I L
1 2 3
4 5
Înlăturaţi mantaua ţevii şi izolaţia astfel caţeava să fie vizibilă suficient pentru a racorda capetele. Fiţi sigur că nu deterioraţi ţeava de PEX.Curăţaţi suprafeţele cu atenţie.
Instalaţi garnitura pe al do ilea inel. Tăiaţi ieşir ile căciu lior de capăt conform cu dimensiunea ţevii de PEX.
Insta laţ i căciula de capăt folosind un lubr ifiant special Mon taţi co lierul deasupra căciulii de capăt şi garniturii..
1. 2.
Notă:
Montarea setului izolator Uponor
Vă rugăm reţineţi !Respectaţi de asemeneainstrucţiunile pentru seturile deizolaţie Uponor.
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
42/58
42 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Setul izolator Uponor
Examplu: Ramicaţie în TSetul pentru ramicaţie în T este desti-nat pentru izolaţie şi impermeabilizarela elementele branşamentelor simplesau duble.Toate ramicaţiile din set sunt deaceeaşi mărime. Ţevile de mărimi difer-ite sunt impermeabilizate folosind inelereductoare.Ţevile sunt conectate conform
instrucţiunilor de pe conectori (veziconectarea ţevii PEX). Căciulile de
Vă rugăm să reţineţi !
Testul de presiune se face înaintea etanşării setului.
capăt sunt montate înainte ca ţevilesă e racordate şi previn intrareaumezelii în interiorul elementelor ţeviipe timpul unei posibile scurgeri dinracord.
Citiţi instrucţiunile de montaj cu atenţie înainte de instalare. Vericaţi dacăsetul conţine toate componentele dinlistă.
1 2 3Inel reductorUponor
Set căciuliţă capătUponor
Instalare -eu (ramificaţie în T)T
Înlăturarea mantalei de protecţie şi izolaţiei din jurul ţevii PEX .Aveţi grijă să nu deterioraţi ţeava de PEX !
Montaţi inelul de reducţie pe ţeavă dacăeste necesar (Numai pentru diametrele OD 68 şi 90 mm)
Montaţi capacele de protecţie.Reţineţi ! Nu se folosesc cleme inella fitingurile de la capătul ţevii
L1
L1
L1
L1
OD L1[mm] [mm]
140 300
175 400
200 500
150 m m
OD
OD
1. 2.
4
Tăiaţi ţeava de PEX la lungimea dorită astfel ca lungimea
ţevii neizolate să fie cât mai mică
5
Racordaţi ţevile de PEX. Lăsaţi vizibilă cât mai puţină
ţeavă neizolată.
Faceţi testul de presiune înainte de închiderea
setului izolator
L2
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
43/58
43R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
6
Întindeţi adeziv la capetele setului izolator, Folosiţi masă de ad eziv de asemenea între inelul reduct or şi mantauaţevii, în funcţie de dimensiunea mantalei exterioare
8
Închideţi cu grijă setul izolator
9a
Strângeţi cele două părţi ale setului izolator cu şurubur i.
ø 200 mm
ø 175 mm
ø 68/90/140 m m
ø 90 mm
ø 68 mm
7
Montaţi ţeava în setul izolator
Întindeţi masa adezivă pe cusăturile orizontale ale setului izolator şi pe capetele ţevii.
9b
8 x 30 m m
SW 13
Inel reducţie
8/16/2019 Specificatii tehnice conducte pentru instalatii in constructii
44/58
44 R E Ţ E L E T E R M I C E U P O N O R - M A N U A L T E H N I C 0 5 / 2 0 1 1
Căminul de branşament Uponor
Căminul de branşament Uponor poa-te folosit pentru toate dimensiunile de ţeavă(140–200 mm). Căminul este disponibil îndouă modele, în T şi în X.Căciulile de capăt sunt întotdeauna folosite
în cămin.
Pregătirea şanţuluiNivelaţi fundul şanţului cu nisip şicompactaţi-l. Dacă este nevoie montaţio placă de ancorare sub stratul denivelare.
Adâncimea normală a capaculuicamerei este la 50 cm. O adâncimede 30 cm este permisă dacă nusunt plasate încărcări directe deas-upra camerei.
1 2 3
4 5 6
7 8
≈ 50 cm(min. 30 cm)
1 2 0 m m
Instalarea camerei de racord Uponor
Umplerea şanţului
Tăiaţi mufele exterioare ale cutie deracord, în funcţie de mărimea cerută deţeava exterioară pentru a face racor-darea, 10-20 cm, depinzând de mărimeaţevii.
Puneţi căciuliţe de capăt pe ţevi.Montaţi conectorii la capeteleţevilor de PEX.
Împingeţi ţeava prin conectori şi în inte-riorul camerei. Strângeţi căciuliţele decapăt pe mantaua ţevii folosind clemeinelare. Conectaţi ţevile şi strângeţicuplajul.
Frecaţi cu glaspapir suprafaţa racor-dului căminului în jurul manşonuluitermocontractabil. Curăţaţi zona deracordare.
Preîncălziţi zona de sub manşonul ter-mocontractabil folosind o lampă cugaz. Puneţi manşonul termocontrac-tabil la loc şi trageţi fermoarul.
Încălziţi manşonul cu o flacără uşoară,conform instrucţiunilor de pe manşonultermocontractabil începând de la pete-cul de acoperire al fermoarului. Întâi încălziţi capătul manşonului dinsprecămin. Mutaţi apoi flacăra pe întregulmanşon.
Închideţi capacul căminului dar strân-geţi şuruburile după ce ţeava a fosttestată la presiune. Începeţi umplereaşanţului tasând nisip în jurulracordurilor.
Începeţi umplerea şanţului folosindpietriş. Aveţi grijă să nu deterioraţi man-şoanele termoizolante. Menţineţi camera în poziţie verticală. Compactaţi umplu-tura în straturi de aprox. 20-30 cm Com-pactarea mecanică directă asupra ca-merei de racord este interzisă.
ţevii.
Cazuri speciale : Încărcare trac: O placă de beton poate folosită deasupra camerei pentru dis-tribuirea sarcinii. Fără o placă de
protecţie, o cameră instalată la o adân-cime de 50 cm poate suporta o
încărcare ocazională pe termen scurtde 3,000 kg (= 6,000 kg/m²; de exe-mplu, un tractor mergând pe deasupra).
Încărcarea pe termen lung