SOLUTII INDUSTRIALE PENTRU ELIMINAREA PROGRESIVA A AGENTULUI FRIGORIFIC R22 Purtator de cuvant: Adrian Balaoi CSF, S.A. Sistemul Fri 3 Oil

Transcript of SOLUTII INDUSTRIALE PENTRU ELIMINAREA … · REDUCERE DE NOI PRODUSE -SIMPLU, ... (sau manual daca...

SOLUTII INDUSTRIALE PENTRU

ELIMINAREA PROGRESIVA

A AGENTULUI FRIGORIFIC R22

Purtator de cuvant:

Adrian Balaoi

CSF, S.A. – Sistemul Fri3Oil

Cadru Juridic: Regulamente

R.E. 1.005/2.0009

•Este interzisa utilizarea agentului frigorific R-22 pentru intretinere in

instalatiile RAC, din data de 1 Ianuarie 2.010

•Este permisa utilizarea R-22 reciclat si/sau regenerat de la acea data

pana la 31 Decembrie 2.014

ESTE INTERZISA REVANZAREA PENTRU R-22, Reciclat si/sau Regenerat,

de la 01-01-2.010

•Identificati Modificarea Echipamentelor

• Este permisa revanzarea pentru R22 regenerat

Procedura Retrofit R-22

DATE DESPRE R-22

In Spania inca exista 45.000 tns de R-22 in instalatii

Scurgeri previzibile: 10% pe an

80% din volum este in 20% din echipamente

20% este in echipamente de dimensiuni mici

STRATEGIE GENERALA

Nu este necesar retrofit-ul masiv in scurt timp.

Este interesant de a mentine 80% din instalatii cu agentul R22 existent

R-22

Instalatie cu R-22

IN SPANIA 55% DIN INSTALATII FUNCTIONEAZA CU R-22

CARE SUNT SOLUTIILE?

Propuneri industriale:

1. Eliminarea/Inlocuirea/Substituirea echipamentelor R-22.

2. Produse “Drop -in”: R-417A,R-427A, R-422D, etc.

3. Inlocuirea produselor cu POE sau PAG:

- Agent frigorific R-404A. Temp. de vap. medie si scazuta.

- R-407C A/A. Temp. de vaporizare inalta. -Clatiri POE.

- Curatarea circuitului si HCF cu POE.

•Este necesar sa se elimine MO pentru a evita fazele de

separare, care dauneaza indicelui de vascozitate.

Analizati instalatia inainte si dupa orice procedura RETROFIT.

Comparativ PROPUNERI AVANTAJE DEZAVANTAJE

ECHIPAMENTE ELIMINATE SI INLOCUITE SIMPLU SI IN UNELE CAZURI CONVENABIL, PENTRU

A EVITA COSTUL RETROFITULUI

ECONOMIC NEVIABIL IN 100% DIN CAZURI

REDUCERE DE NOI PRODUSE -SIMPLU, PRIN ALEGEREA CORECTA A PRODUSULUI

- NU ESTE NECESAR SA EXISTE UN TEHNICIAN BINE

INSTRUIT

- OPERATIUNI LIMITATE:

•RECUPERARE R-22

•INTRODUCERE R-... DE LA UN PRODUCATOR

SPECIFIC

-COMPLICA LOGISTICA

-DUBII: APLICARE, DISPONIBILITATE,

PERFORMANTA TEMPORARA

-“METODA BLIND”.

-PRODUSE PATENTATE DOAR DE UN SINGUR

PRODUCATOR

“MARFURI”+ POE/PAG

CLATIRI -METODA RAPIDA

-PRODUSE:

•TOTI PRODUCATORII

•TEMP. SCAZUTA/MEDIE: R-404A (R-507)

•TEMP. INALTA: R-407C

•PRODUCERE RIDICATA DE REZIDUURI

•COSTURI RIDICATE A FORTEI DE MUNCA

•ELIMINARE INSUFICIENTA A REZIDUURILOR

DIN INSTALATII

•RISC DE DEFECTIUNE A COMPRESOARELOR

•“METODA BLIND”

• LIMITA MO/POE– “REFRACTOMETRU

MANUAL”

PROCEDURA CSF,SA

ANALIZA ANTERIOARA SI RETROSPECTIVA A

RETROFITULUI

CURATARE TOTALA A INSTALATIEI

PRODUS+POE/PAG + ADITIVI

CLIMACHECK+SISTEM FRI3OIL +ZEROL ICE

-ANALIZA INAINTE SI DUPA RETROFITTING

-MAJORAREA CURATARII CU 8/10% CAP & COP

-MAJORAREA DE ADITIVI CU 4-10% CAP & COP

-RECUPERARE SI CURATARE AGENT FRIGORIFIC

PENTRU REUTILIZARE

-RAPORT TEHNIC ANTERIOR, INAINTE DE A LUA

DECIZIA DE RETROFIT. MAI TARZIU RAPORT PENTRU

CLIENT.

-INSTALATOR PROFESIONIST

-SIGURANTA SI SECURITATEA UTILIZATORULUI

•OPRIREA INSTALATIEI PENTRU O PERIOADA

DE TIMP

•FUNCTIONARE ECONOMICA MAI MICA

Metoda retrofit propusa de: CSF,SA

R-22

Analiza prealabila

a instalatiei

Recuperare si Curatare

HFC

+

POE

+

Aditiv

Punere in functiune cu:

HCF si POE + Aditiv

Analiza si

raport client CALCINARE

REUTILIZARE

INSCRIPTIE

INREGISTRARE

REZERVA

Analizele de Performanta sunt o posibilitate

Bazat pe PC si/sau Web (sau manual daca se doreste): Punere in functiune – minimizarea costului de garantie Inspectie de performanta – optimizare Intretinere preventiva Testare

Decizie de baza – expansiune, incarcare estimata, retrofit

Provizorii sau fixe – Locale sau la distanta

DIN-instalatie montata fix

Analize pe proces ”standard”

1. Presiune scazuta si temp.

de aspiratie a gazului.

2. Presiune inalta si temp.

de refulare a gazului.

3. Presiune inalta si temp.

lichidului.

Implementarea teoriei la utilizarea practica in industrie

1

2 3

Presiune

Entalpie

Compresiune ideala

Cap. de racire

Cap. de incalzire

Putere absorbita

P LP

P HP

Debit masic = puterea absorbita – pierderi de caldura/diferenta de entalpie a compresorului

COP = Capacitate de racire/ Putere absorbita

Analizarea Performantei Teoriei utilizand

metoda ”Cutia Neagra” pe compresor

Cresterea entalpiei agentului frigorific

Puterea absorbita

Compresorul poate fi utilizat la un debit masic masurat

Pierderi de caldura

(relativ mici si previzibile)

Puterea absorbita = cresterea entalpiei x debitul masic + pierderi de caldura prin carcasa

Castellana de

Suministros

Frigoríficos, S.A.

2. Recuperare si curatare circuit

Sistem Fri3Oil :

•Brevetare Spaniola din 2005

•20 de Tari: Europa si America de Sud •Recupereaza si curata orice agent firgorific halocarbon: CFC,

HCFC & HCF

•Eficienta energetica este imbunatatita prin curatarea circuitului intern

•R-22 pentru service pana la sfarsitul anului 2014

Procedura Retrofit R-22

Solutiile SISTEMULUI FRI3 OIL :

•Date tehnice:

– ELIMINARE REZIDUURI DE LA MOTOR COMPRESOR

– CAND EXISTA APA IN INSTALATIE

– RETROFITTING MO > POE

– INSTALARE NOUA CU AGENTI DE CONTAMINARE A AERULUI POE

– INTRETINERE PREVENTIVA PH<7

– CURATAREA TEVILOR DE PARTICULE SOLIDE DUPA SUDARE. EVITAREA SUDURII IN STRAT PROTECTOR CU N2.

– RECUPERAREA SI RECICLAREA TUTUROR AGENTILOR FRIGORIFICI HABLOCARBON DE LA ORICE INSTALATIE PANA

PE TEREN.

Procedura Retrofit R-22

Solutiile SISTEMULUI FRI3 OIL :

Procedura Retrofit R-22

•MEDIU INCONJURATOR :

– OAMENI

•MEDIU FAVORABIL

•SOLUTIE GLOBALA PENTRU DESEURI TOXICE

–LEGI

•RECUPERAREA SI RECICLAREA AGENTILOR

FRIGORIFICI

•RECICLARE UTILAJE

•USURINTA DE ELIMINARE A REZIDUURILOR

Solutiile SISTEMULUI FRI3 OIL :

Procedura Retrofit R-22

ECONOMIC:

– REUTILIZAREA AGENTILOR FRIGORIFICI

– EVITAREA DISTRUGERII AGENTILOR FRIGORIFICI

– EVITAREA SCURGERII AGENTILOR FRIGORIFICI

– NU NECESITA CUMPARAREA AGENTILOR FRIGORIFICI NOI

– GARANTIE FIABILA SI PROFESIONALA

– ECONOMII DE NITROGEN USCAT

– INCASARI DE LA SERVICE

– ECONOMII CU FORTA DE MUNCA, UNITATI VRV.

PRINCIPII DE BAZA ALE SISTEMULUI DE CURATARE

DIALIZA

Procedura Retrofit R-22

1.- MISCIBILITATE/SOLUBILITATE

2.- DECANTARE DENSITATI

3.- SEPARAREA LICHIDELOR PRIN

VAPORIZAREA AGENTULUI FRIGORIFIC

PRINCIPII FIZICE ALE SISTEMULUI

Procedura Retrofit R-22

3. Aditivii Zerol ICE & ICE32

•Scad frecarile

•Reduc temp. de refulare

•Extind durata de viata a

compresorului

•Reduc Consumul de Energie

Electrica

•Creste Capacitatea Ref.

•Creste COP

•Imbunatatire de 4-10%

STUDIU DE CAZ I

CLIMATIZARE

• Locul: Barcelona

• Data: Iulie 2.009

• Compania: Sodexo Facilities Management, S.A.

• Echipament: Grup racire lichide apa/apa

• 600kW, cu 2 circuite

Inregistrator cu

ClimaCheck

Agent frigorific: R-22

Numar de Compresoare: 4

Numar de circuite: 2

Incarcare agent frigorific: 2 x 54 Kgs

Temp. de evacuare a apei

Vaporizator (°C)

Temp. de evacuare a apei

Condensator (°C)

Cap. de racire

(kcal/h.)

Putere

(kW)

5 30 494.000 142

6 30 518.000 144

8 30 564.000 146

10 30 610.000 147

12 30 656.000 148

5 35 476.000 152

6 35 498.000 154

8 35 542.000 157

10 35 586.000 160

12 35 630.000 163

5 40 440.000 162

6 40 460.000 166

8 40 502.000 169

10 40 542.000 172

12 40 584.000 175

Tabel cu capacitate de racire, consumul de energie electrica, in ceea ce priveste temp. apei Condensatorului sau Vaporizatorului ΔT 5,5 °C, cu privire la manualul de service.

CAPACITATEA DE

RACIRE SI PUTERE

CAZ Capacitate de

racire (Kw)

Putere

(Kw)

R-22 240 76

DROP IN 205 73

R-407C 275 81

Vaporizator Admisie

(°C)

Evacuare

(°C)

R-22 13 - 16 10 - 12

DROP IN 13 12

R-407C 13 - 16 10 - 12

ADMISIE si EVACUARE

Vaporizator si Condensator

(flux Sec)

Condensator Admisie

(°C)

Evacuare

(°C)

R-22 26 - 28 30 - 32

DROP IN 26 - 29 29 - 32

R-407C 26 - 29 30 - 32

Temp. aspiratie, refulare

si linia de lichid

CAZ Aspiratie

(°C)

Lichid

(°C)

Refulare

(°C)

R-22 10 38 90

DROP IN 14 37 78

R-407C 7 37 70

Presiune Inalta si

Presiune Scazuta

CAZ LP (Bar) HP (Bar)

R-22 3,8 – 4,5 14 – 15,5

DROP IN 3,2 – 3,7 19 - 20

R-407C 4,2 – 4,5 16 - 17

Supraincalzire si

Subracire

CAZ Recalent.

(°C)

Subenf.

(°C)

R-22 9,5 – 11,5 2,5 – 3,5

DROP IN 15 10

R-407C 1 – 2 2,3

CAZ Incalzire

COP

Racire

COP

R-22 4,1 3,2

DROP IN 3,7 2,8

R-407C 4,2 3,3

Incalzire si racire COP

EFICIENTA IZENTROPICA

CAZ I EFFI (%)

R-22 62

DROP IN 68

R-407C 64

STUDIU DE CAZ II

REFRIGERARE

• Locul: Milano

• Data: Februarie 2.010

• Compania: S.C.A.R. Refrigerazione, srl.

• Echipament: Centrala de compresoare de temperaturi pozitive pentru

Hypermarket

• 6 compresoare Bitzer, peste 200 terminale

TEMPERATURA MEDIE CENTRALA Agent frigorific: R-22

Numar de Compresoare: 6

Producator: BITZER

Model: 6F-40.2Y

Tabel pentru capacitati, consumuri si COP, in ceea ce priveste software-ul BITZER, pe unitate

MODEL 6F-40.2

(R-22)

6F-40.2

(R-22)

6F-40.2

(R-404A)

6F-40.2

(R-404A)

Temp. de Vaporizare (°C) -16 -12 -15 -13

Temp. de Condensare(°C) 33 26 20 20

Cap. de Racire (kW) 66,1 83,5 92,7 101,5

Putere consumata (kW) 24,0 23,4 24,3 24,8

Temp. de Refulare (°C) 109,3 88,7 59,6 56,8

COP 2,57 3,38 3,36 3,70

CAZ CAP.

RACIRE

(kW)

PUTERE

(kW)

R-22 90 - 180 29 - 53

R-404A 110 - 200 32 - 57

CAPACITATE

DE RACIRE SI PUTERE

VAPORIZARE

(°C)

CONDENSARE

(°C)

R-22 -16 / - 12 26 / 30

R-

404A

-17 / - 13 19 - 20

Temp. de

Vaporizare si

Condensare

Temp. Aspiratie,

Refulare si

linia de Lichid

CAZ Aspiratie

(°C)

Lichid

(°C)

Refulare

(°C)

R-22 6 24 85

R-404A 7 18 65

CAZ Racire

COP

R-22 3,0 – 3,4

R-404A 3,2 – 3,6

RACIRE COP

E.R. 842/2006

Obiectiv:

- Minimizarea emisiilor de gaze Fluorurate cu Efect de sera

Masuri:

- Certificare de etanseitate: E.R. 1516/2007

- Plasarea unui Sistem de Detectare a Scurgerilor

- Calificarea personalului

Cadru Juridic. Regulamente

Dovezi de certificare a etanseitatii

• Protocol E.R.1516/2007

• in vigoare din 04/07/2007

• Certificari:

• 3/30kg ----- 1/an

• 30/300kg ---- 2/an

• >300kg ----- 4/an

Gaze fluorurate si Detectari Scurgeri

Calificarea Personalului si a Companiilor

Calificare de 4 tipuri

In Spania sunt 2 tipuri de calificari

ULTRAPROBE100 KT1

ULTRAPROBE100KT1

ULTRAPROBE100 KT1

DETECTARE PRESIUNE

DETECTARE VACUUM

MICROSCURGERI

VACUUM

Detectari Scurgeri

ULTRAPROBE100 KT1

Detectari Scurgeri

ULTRAPROBE100 KT1

Detectari Scurgeri

ULTRAPROBE100 KT1

Frecventa Inalta

Generator de Ton

LLA

Detectari Scurgeri

ULTRAPROBE100 KT1

Multumim pentru atentie