Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

download Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

of 8

Transcript of Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    1/8

    Enjoy a clean &comfortable life with MULTI V.

    2010

    Air Conditioning System

    Air Conditioning System

    Forcontinualproductdevelopment,LGreservestherighttochangespe

    cificationswithoutnotice.

    Distributed by

    EU-MV091

    LGMULTIVAirConditioningSystem

    2010

    2010

    CALOR SRL

    Str. Progresului nr.30-40, sect. 5, Bucuresti

    tel / fax : 021.411.44.44 / 021.411.36.14www.calorserv.ro - www.calor.ro

    http://www.calorserv.ro/http://www.calor.ro/http://www.calor.ro/http://www.calorserv.ro/
  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    2/8

    From installation to maintenance and repair,

    LG runs 30 global air conditioning academies,

    providing training for air conditioning

    professionals around the world.

    Lifes Good!

    Comfort Everyone in a Greener Way

    Pursuing a more comfortable life in todays complicated society has become second nature. However, we cannot

    afford to compromise the health of the environment for our own personal comfort. In order to achieve a balance

    between these two needs, LG provides products and solutions for those who seek comfortable lives in a greener way;

    comfort and eco-friendliness are our key values.

    We at LG create optimal living and working conditions by enabling our customers to control their environment: includ-

    ing temperature, humidity and air quality to make them more comfortable. LG products are safe to operate andeasy to manage and we provide our business partners with reliable and cost-effective solutions. Customer satisfaction

    motivates us to work closely and productively with our partners and we also offer a comprehensive after-sales and

    one-stop service system.

    LG is committed to protecting our environment by enhancing the energy efficiency of our products and our business

    operations by adhering to eco-friendly principles. LG has been significantly investing in R&D and pursuing continuous

    innovation to enhance product energy efficiency. LG uses eco-friendly refrigerants in its air conditioners, which help

    save the ozone layer and all LGs products are produced under an Eco-Design system, which ensures environmen-

    tally-friendly processes from production to disposal.

    LG is fully committed to making the lives of our customers more comfortable in an environmentally sustainable way

    and we strive to ensure our business partners benefit from partnering with us. Our commitment and innovation enable

    us to uphold our key values - Green and Comfort. With commitment and innovation, we comfort everyone our busi-

    ness partners and customers in a greener way.

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    3/8

    30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

    Outdoor unit line up

    HPMODEL 4 5 6 8 10 12 14 16 18 20 22 24 26 28

    Heat Pump

    Heat Recovery

    *3, 380V*1, 220V

    10 / 20SystemCapacity

    30 / 40 50 / 60

    10 / 20SystemCapacity

    30 / 40 50 / 60

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    4/8

    MULTI V Inverter units composed of serially arranged

    refrigerant pipes connected to a single outdoor unit are

    an efficient system that offers outstanding energy saving,

    simple and easy installation, and connection to different

    types of indoor units, making it easy to design and install.

    Outdoor unit

    M U L T I V

    o u t d o o r

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    5/8

    OutdoorUnit_M

    ULTIVseries

    Inverter

    DC InverterCompressor

    Constant SpeedCompressor

    * 25~105Hz

    Other Features

    DC Inverter fan motor- Max RPM increased from 850 to 920 rpm

    - Power consumption decreased by 30~40%

    01

    Upgraded Main PCB

    - 3-Digit 7 segment

    - Double DIP switch

    Main PCB

    02

    03

    04

    Wide louver heat exchanger- Improved heat exchange rate by 14%

    - Anti-corrosion treatment (Gold fin)

    Black box function

    - Save the last 3 minutes operating data

    - Precise analysis & fast trouble-shooting

    01

    02

    03 04

    Corrugate fin

    Wide louver fin

    Wide Louver heat exchanger

    I nv erter I nv erterInverter Combination

    Increased performance & high COP

    Faster response for partial load

    Optimized combination with space saving

    Competitive price for customers

    Reduced total base model units

    - Simple line-up (16 models > 5 models)- Easy stock & logistics management

    3 INV controller

    04

    01

    DC Inverter Compressor

    Oil injection mechanism

    - High reliability in low rpm operation

    - High efficiency in partial load operation

    02

    Oil discharge reduction

    - High reliability in high rpm operation

    - Enhanced oil circulation

    03

    05

    06

    Teflon coated bearing

    High performance oil pump

    Optimized scroll shape

    DC Inverter motor

    - High efficiency - Low noise

    World Highest COP! DC Inverter compressor

    Inverter combination

    High efficient DC Inverter fan

    Wide louver heat exchanger

    * Based on 10HP model

    A Company

    Total pipinglength 1000m

    Extended Piping Length

    MULTI V PLUS II / SYNC II

    Refer to the specifications for more information

    1st branchto farthestIndoor40m[90m**]Level

    difference100m

    Longestpiping length150m(200m**)

    MULTI V PLUS II, MULTI V SYNC II

    15m

    * Using Y branch

    Pursuing the market needs of high energy

    efficiency and environmental friendliness.

    Outdoor unit

    ** Conditional Application To make 40~90m of pipe length after first branch, refer to the part of install ation of outdoor units in PDB

    1000m

    150m(200m**)

    40m[90m**]

    100m

    15m

    5m

    Total piping length

    Longest piping length

    Longest piping length after 1st branch

    Level difference between ODU~IDU

    Level difference between IDU~IDU

    Level difference between ODU~ODU

    05

    06

    01

    04

    03

    02

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    6/8

    LG MV Easy start-up, easy trouble shooting

    Monitoring the normality of all partssuch as compressor, fan, valve, etc

    Operation state Central Controller Cycle view

    Command

    Sensor reading

    LATS MULTI V Convenient model selection program

    Highly user-friendly design(Autocad version)

    Automatic piping design & check

    Download from sales supporting system> http://www.lgeaircon.com

    Model selection Auto check

    CA D ap pl ic at io n Ma ki ng qu ot at io n

    Enhanced comfort for end-user!

    * Based on MULTI V PLUS II, 10HP model

    Night Silent OperationNight silent operation will be on for Xhours starting from the peak temperatureduring daytime, and then after Y hours,itll be back to normal operation.

    - Mode 1 > X : 8.0 hours, Y : 9.0 hours

    - Mode 2 > X : 6.5 hours, Y : 10.5 hours

    - Mode 3 > X : 5.0 hours, Y : 12.0 hours

    Each mode can be selected as 3 stepsof sound level.

    Pursuing the market needs of high energy

    efficiency and environmental friendliness.

    Outdoor unit

    Unit : dBA

    MINI PLUS II SYNC II

    Step 1

    Step 2

    Step 3

    46

    43

    40

    47

    44

    41

    47

    44

    41

    Automatic RefrigerantCharging Refrigerant charging without any

    scales or quantity calculation

    This function is recommendedduring service.

    Guaranteed temperature range :

    IDU(20~32C), ODU(0~43C)

    FDD function (Fault detect & diagnosis)

    Manifold

    Refrigerantcharging kit

    Refrigerant

    * Fault detect & diagnosis

    Automatic RefrigerantCheck-Up It can be checked refrigerant status

    during start-up whether it isundercharged or overcharged

    It can be decided appropriate amountof refrigerant automatically through

    cycle operation.

    FDD function (Fault detect & diagnosis)

    Leakage!

    Leakage!

    Leakage!

    Leakage!

    * Fault detect & diagnosis

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    7/8

    OutdoorUnit_M

    ULTIVMINI

    EFFICIENCYMULTI V MINI uses the cutting-edge, artificial

    intelligence control to obtain efficient operation

    and reduced noise.

    Day time Night t ime(Based on 4HP)

    Noise level (dBA)

    Slim & Compact Size

    Easy & efficient installation of MULTI VMINI will provide the best solution for smalloffices and shops.

    4, 5, 6 HP5, 6 HP

    Foot print area

    806mm

    730mm

    330mm

    950mm

    46%Reduction

    Volume

    52%Reduction

    W xH xD : 8 06 1 60 7 73 0 W xH xD : 9 50 x1 38 0x 33 0

    Conventional

    50 51 52

    4HP 5HP 6HP STEP 1 STEP 2 STEP 3

    404346

    Enhanced Comfort

    Night silent operation

    High COP

    Longest Piping Length

    Cooling Heating Cooling Heating

    4HP

    5HP

    6HP

    1, 220V 3, 380V

    3.9

    3.7

    3.6

    4.0

    4.0

    3.8

    3.7

    3.6

    3.5

    3.9

    3.9

    3.8

    Total piping length

    Longest piping length (Equivalent)

    Longest piping length after 1st branch

    Level difference between ODU~IDU

    Level difference between IDU~IDU

    Level difference between ODU~ODU

    300m

    150m(175m)

    40m50m(40m*)

    15m

    5m

    *Outdoor unit is lower than indoor unit.

    MULTI V MINI can be easily installed in small offices

    and shops. Designed for low-noise operation,

    it ensures a pleasant air conditioned environment.

    Enjoy a clean &

    comfortable life with MULTI V MINI.

  • 8/12/2019 Unitati Externe Lg Multi v Mini Pliant Prezentare Limba Engleza

    8/8

    11.2

    12.5

    2.9

    3.1

    3.86

    4.03

    950 x 1380 x 330

    118

    50

    52

    110

    1

    3.7

    FV50S[PVE]

    1.7

    9.52(3/8)

    15.88(5/8)

    1

    6

    15.5

    18.0

    4.3

    4.7

    3.60

    3.83

    950 x 1380 x 330

    118

    52

    54

    110

    1

    3.7

    FV50S[PVE]

    1.7

    9.52(3/8)

    19.05(3/4)

    1

    9

    14.0

    16.0

    3.8

    4.0

    3.68

    4.00

    1, 220 ~ 240, 50

    950 x 1380 x 330

    118

    51

    53

    110

    1

    3.7

    FV50S[PVE]

    1.7

    9.52(3/8)

    15.88(5/8)

    1

    8

    OutdoorUnit_M

    ULTIVMINI

    DC Inverter Compressor & Fan motor

    Black Box Function

    Night Silent Operation

    Fault Detect & Diagnosis

    Pump Down

    * Specifications

    Capacity Cooling kW Heating kWPower Cooling kWInput Heating kWCOP Cooling HeatingPower Supply , V, HzDimensions(WxHxD) mmWeight kgColorNoise level Cooling dBA3 Heating dBA3Fan Type Air ow rate [CMM]Compressor Type Number of compressorsHeat ExchangerRefrigerant Type

    Charge kg ControlRefrigerant TypeOil Charge lPiping Liquid Pipes mm(inch)Connections Gas Pipes mm(inch)Number of outdoor unitNumber of maximum connectable indoor units

    HP

    Model

    4

    Ratio of the connectable indoor units

    Longest piping length / Level difference

    65

    EEV

    Gold Fin

    R410A

    DC INVERTER

    BLDC

    Warm Gray

    5 64

    14.0

    16.0

    3.9

    4.1

    3.59

    3.90

    3, 380 ~ 415, 50

    950 x 1380 x 330

    112

    51

    53

    110

    1

    3.7

    FV50S[PVE]

    1.3

    9.52(3/8)

    15.88(5/8)

    1

    8

    11.2

    12.5

    3.0

    3.2

    3.73

    3.91

    950 x 1380 x 330

    112

    50

    52

    110

    1

    3.7

    FV50S[PVE]

    1.3

    9.52(3/8)

    15.88(5/8)

    1

    6

    15.5

    18.0

    4.4

    4.8

    3.52

    3.75

    950 x 1380 x 330

    112

    52

    54

    110

    1

    3.7

    FV50S[PVE]

    1.3

    9.52(3/8)

    19.05(3/4)

    1

    9

    EEV

    Gold Fin

    R410A

    DC INVERTER

    BLDC

    Warm Gray

    Independent Unit ARUN40GS2 ARUN60GS2ARUN50GS2 ARUN40LS2 ARUN60LS2ARUN50LS2

    *1, 220V *3, 380V

    150m/50m

    50~130%

    150m/50m

    50~130%

    Note :

    1. Capacities are based on the following conditions Cooling-Indoor temp. 27C[80.6F]DB / 19C[66.2F]WB Heating-Indoor temp. 20C[68F]DB / 15C[59F]WB

    Outdoor temp. 35C[95F]DB / 24C[75.2F]WB Outdoor temp. 7C[44.6F]DB / 6C[42.8F]WB

    Interconnecting piping length 7.5m Interconnecting piping length 7.5m

    Level difference of zero Level difference of zero

    2. Capacities are net capacities3. Due to our policy of innovation some specifications may be changed without notification4. EEV : Electronic Expansion Valve

    Max. 9 Indoor UnitsConnectable

    Maximum 9 indoor units can be connectedto one single outdoor unit with 130%indoor unit combination.

    - 9 indoor units for 6HP

    - 8 indoor units for 5HP

    - 6 indoor units for 4HP

    Easy to Service

    Inner SVC valve- 4 Way piping is possible (Front, Rear, Right, Down)

    - Excellent exterior

    01

    Convenient moving handle02

    units

    *Based on 6 HP model

    54321

    876 9

    1 Way 4 Way

    Compact design & Easy service- Remove 3 pieces of screw for SVC

    - Front panel removal system

    03

    3 pieces of screw

    Easy service

    MULTI V MINI can be easily installed in small offices

    and shops. Designed for low-noise operation,

    it ensures a pleasant air conditioned environment.

    02

    01

    03

    Feature