Preturi ere Pentru Canal la

download Preturi ere Pentru Canal la

of 8

Transcript of Preturi ere Pentru Canal la

  • 8/3/2019 Preturi ere Pentru Canal la

    1/8

    Installation intopre-formed duct

  • 8/3/2019 Preturi ere Pentru Canal la

    2/8

    1. Option: thermostatic valve withremote controlled head

    2. Build-in unit with metal separationwall

    1

    2

  • 8/3/2019 Preturi ere Pentru Canal la

    3/8

    155

    I n s t a

    l l a t i o n

    i n t o p r e - f

    o r m e

    d d u c t

    Warm power in a pre-formed ductIf you can ensure that there is a suitable pre-formed duct, then Jaga will provide you wit h acomplete Low-H2O construction package that can be easily mounted in your duct. This pac-kage contains all the components required for assembly against the wall of the duct or for freestanding type mounting.

    Low-H2O heat exchanger - of pure copper and aluminium, totally non-

    corrosive- a 30 year guarantee- pressure tested: 20 bar - with dirt-repellent and dust-proof lacquer in

    graphite grey (RAL 7024)- high heat output achieved with normal and

    lower flow temperatures- efficient: rapid heating up speed due to su-

    per low water content

    Practical advice1. Tests done by the Jaga Experience Lab and

    the Technical Department of the Universityof Eindhoven (The Netherlands) have pro-ven that the most efficient heat output willbe obtained when the heat exchanger is fit-ted for building into pre-formed ducts.

    2. Ensure there is sufficient space between theduct and the window, as it is important thatcurtains do not hang over the duct.

    3. It is preferable that the heat exchanger co-vers the total length of the window.

    High efficiency boiler combinationThanks to its low water content and high coef-ficient of heat conduction for low flow tempe-ratures, the unit for installation into a pre-for-med duct, with its modern Low-H 2O element,is ideal to use in combination with high effi-ciency boilers and/or condensing technoloy.

    Twin Power or DBE?The heat exchangers for installation into pre-formed ducts are also available:- with DBE: see price list Top performers.- with the super-powered Twin heat exchan-

    gers. The boiler temperature is on average15% lower for equivalent radiator dimen-sions

  • 8/3/2019 Preturi ere Pentru Canal la

    4/8

    56

    grille %free air flow

    75 1.00

    62.5 0.97

    60 0.96

    52 0.93

    50 0.9240 0.8430 0.66

    H

    1 3

    bb1 b1

    A

    C

    B

    D

    3 . 1

    H

    b

    I

    1 3

    b1

    AC

    B

    Wall mounting BIFW _Build-in Floor Wall

    Central mounting BIFF _Build-in Floor Freestanding

    KM

    L

    L'

    max.25

    duct frame grille heat exchanger

    wall central

    B C A type b b1 min. b b1 min.

    25 30 28.8 10-11 10 12 - -29 34 32.8 15-16 15 12 - -33 38 36.8 15-16 15 12 15 7.537 42 40.8 15-16 15 12 15 941 46 44.8 20-21 20 17 20 945 50 48.8 20-21 20 17 20 1149 54 52.8 20-21 20 17 20 1353 58 56.8 20-21 20 17 20 13

    In bold = standard

    duct frame grille heat exchanger

    L M K L max.per cm L +5 L + 3.8 L - 20

    Example 140 145 143.8 120

    duct heat exchanger total depthD min. H I

    34 20 3744 30 4754 40 5764 50 67

    Length M can be custom made per cm, up to 6 m in 1 piece.Longer ducts: 2 pieces of the same length (see parts).

    Standard feet adjustable from 13.5 to 18.5 cm.

    correctionfactor

    Corresponding widths

    Length

    Height

    Correction factors

    Heat outputs are calculated on the given di-mensions and with use of a Jaga grille with afree air flow of 75% (Jaga aluminium rigid gril-les). For other dimensions and grilles, correc-tion factors have to be applied.

    Jaga aluminiumrolled up and rigid

    Jaga Designo rigidaluminum androlled up wood

    Stainless steel

    Jaga Designorolled up wood

    Other

    Installation into pre-formed duct _Dimensions

  • 8/3/2019 Preturi ere Pentru Canal la

    5/8

    157

    I n s t a

    l l a t i o n

    i n t o p r e - f

    o r m e

    d d u c t

    Grilles and frames

    A large range of grilles and frames in variouscolours and materials: see parts list for CanalPlus page 236.

    Extended air vent

    For easy and rapid venting.Extended air vent for heat exchanger type 10, 15 and 20.Standard delivered with type 11, 16and 21.

    CODE H Separation wall

    5090.114078 20 5,05 5090.114178 30 5,505090.114278 40 5,855090.114378 50 6,10

    PageConnection sets & valves 163 Technical info 239 Parts 237 Correction factors 240 Product descriptions 246

    Output calculated in accordance withEN442, at a water temperature of 75/65C and a room temperature of 20C ( T=50).

    Installation into pre-formed duct _Options

  • 8/3/2019 Preturi ere Pentru Canal la

    6/8

    58

    BIFFBIFW

    L

    H

    BIFW: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Brackets- Separation wall, dark grey lacque-

    red- Air vent 1/8: elbow (type 10) or

    extended (type 11)- Drain cock 1/2

    BIFF: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Freestanding brackets- Feet: adjustable from 13.5 to

    18.5 cm- 2 separation walls, dark grey lac-

    quered- Air vent 1/8: elbow (type 10),

    extended (type 11)- Drain cock 1/2

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    020 75/65/20 582 655 728 801 946 1092 1237 1383 1528 1674 1819 1965 211190/70/20 746 840 933 1027 1213 1400 1586 1773 1959 2146 2332 2519 2706

    wall 110,60 123,30 130,90 137,90 155,70 183,80 200,10 217,40 249,70 269,10 286,80 305,30 322,00central 151,70 166,20 175,60 183,40 219,00 249,60 269,10 290,60 325,50 361,80 382,00 404,60 423,80

    030 75/65/20 734 826 918 1010 1193 1377 1560 1744 1927 2111 2294 2478 266290/70/20 941 1059 1177 1295 1529 1765 2000 2236 2470 2706 2941 3176 3412

    wall 118,50 132,20 140,70 148,00 168,50 197,80 215,70 235,10 268,70 290,30 309,20 329,70 347,70central 166,80 183,10 194,20 202,70 243,20 276,30 299,00 324,70 362,10 402,40 425,10 451,70 473,40

    040 75/65/20 856 963 1070 1177 1391 1605 1819 2033 2247 2461 2675 2889 310390/70/20 1097 1234 1372 1509 1783 2057 2332 2606 2880 3155 3429 3703 3978

    wall 126,50 141,00 150,40 158,20 181,20 211,80 231,30 252,80 287,70 311,40 331,60 354,20 373,40central 181,90 199,90 212,80 222,00 267,30 302,90 328,80 358,80 398,70 442,90 468,10 498,90 523,00

    050 75/65/20 898 1016 1134 1253 1490 1726 1964 2204 2445 2688 2931 3179 342690/70/20 1151 1302 1454 1606 1910 2213 2518 2825 3134 3446 3757 4075 4392

    wall 134,40 149,70 160,00 168,10 193,70 225,60 246,70 270,30 306,40 332,30 353,80 378,40 398,80

    central 196,80 216,60 231,20 241,20 291,30 329,30 358,50 392,70 435,00 483,20 510,90 545,70 572,40

    code height length typeORDERING CODE : BIFW. 020 090 10

    BIFF. 020 090 10

    Wall mounting _type 10 Central mounting _type 10

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    030 75/65/20 996 1121 1246 1370 1619 1868 2117 2367 2616 2865 3114 3363 361290/70/20 1277 1437 1597 1756 2075 2395 2714 3034 3353 3673 3992 4311 4630

    wall 211,40 233,60 246,90 259,30 290,90 340,70 369,10 398,80 456,30 491,20 522,10 553,90 583,40central 259,60 284,50 300,50 314,00 365,60 419,10 452,30 488,50 549,70 603,30 638,00 675,90 709,10

    040 75/65/20 1124 1264 1404 1545 1826 2107 2388 2668 2949 3230 3511 3792 407390/70/20 1441 1620 1800 1980 2341 2701 3061 3420 3780 4140 4501 4861 5221

    wall 219,20 242,30 256,50 269,30 303,50 354,40 384,40 416,30 475,10 512,00 544,20 578,10 608,80central 274,60 301,20 318,90 333,10 389,60 445,50 482,00 522,40 586,10 643,50 680,70 722,70 758,50

    050 75/65/20 1171 1317 1463 1610 1902 2195 2488 2780 3073 3366 3658 3951 424490/70/20 1501 1688 1875 2064 2438 2814 3189 3564 3939 4315 4689 5065 5440

    wall 227,20 251,20 266,30 279,40 316,20 368,40 400,00 434,10 494,00 533,20 566,60 602,50 634,50central 289,70 318,10 337,50 352,50 413,70 472,20 511,80 556,50 622,70 684,10 723,80 769,90 808,10

    code height length typeORDERING CODE : BIFW. 030 090 11

    BIFF. 030 090 11

    Wall mounting Twin_ type 11 Central mounting Twin_ type 11

    Installation into pre-formed duct

  • 8/3/2019 Preturi ere Pentru Canal la

    7/8

    159

    I n s t a

    l l a t i o n

    i n t o p r e - f

    o r m e

    d d u c t

    BIFFBIFWL

    H

    BIFW: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Brackets- Separation wall, dark grey lacque-

    red- Air vent 1/8: elbow (type 15) or

    extended (type 16)- Drain cock 1/2

    BIFF: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Freestanding brackets- Feet: adjustable from 13.5 to

    18.5 cm- 2 separation walls, dark grey lac-

    quered- Air vent 1/8: elbow (type 15),

    extended (type 16)- Drain cock 1/2

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    020 75/65/20 969 1090 1211 1332 1574 1817 2059 2301 2543 2786 3028 3270 351290/70/20 1242 1397 1552 1707 2018 2329 2639 2950 3260 3571 3882 4192 4502

    wall 141,60 158,20 169,60 179,10 203,30 242,80 265,80 307,90 354,90 381,90 406,80 432,20 455,80central 182,80 201,10 214,30 224,50 266,60 308,60 334,80 381,10 430,60 474,60 501,90 531,50 557,60

    030 75/65/20 1208 1359 1510 1661 1963 2265 2567 2869 3171 3473 3775 4077 437990/70/20 1549 1742 1936 2129 2516 2903 3291 3678 4065 4452 4839 5226 5613

    wall 149,60 167,00 179,30 189,20 216,10 256,80 281,40 325,60 373,80 403,00 429,20 456,70 481,50central 197,90 217,90 232,80 243,80 290,80 335,30 364,70 415,20 467,20 515,10 545,00 578,70 607,20

    040 75/65/20 1394 1568 1742 1916 2265 2613 2962 3310 3659 4007 4356 4704 496590/70/20 1787 2010 2233 2456 2903 3350 3797 4243 4690 5136 5584 6030 6364

    wall 159,20 177,50 190,70 200,90 231,20 273,20 299,40 345,70 395,20 427,40 454,80 484,40 510,40central 214,50 236,40 253,10 264,80 317,30 364,30 397,00 451,70 506,20 558,90 591,30 629,00 660,10

    050 75/65/20 1472 1663 1855 2047 2432 2820 3210 3544 3901 4232 4563 4882 503990/70/20 1887 2132 2378 2624 3118 3615 4115 4543 5001 5425 5849 6258 6459

    wall 167,90 187,10 201,10 211,70 245,00 288,30 316,10 364,50 415,20 450,00 478,60 510,30 537,60

    central 230,40 253,90 272,40 284,80 342,60 392,10 427,90 486,90 543,90 600,90 635,80 677,60 711,20

    code height length typeORDERING CODE : BIFW. 020 090 15

    BIFF. 020 090 15

    Wall mounting _type 15 Central mounting _type 15

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    030 75/65/20 1316 1480 1644 1809 2138 2467 2796 3124 3453 3782 4111 4440 476990/70/20 1687 1897 2107 2319 2741 3162 3584 4005 4426 4848 5270 5692 6113

    wall 266,90 296,00 314,90 332,70 375,50 445,60 486,00 560,40 644,40 692,30 736,30 781,00 822,50central 315,10 346,90 368,40 387,30 450,20 524,00 569,20 650,00 737,70 804,40 852,20 903,00 948,20

    040 75/65/20 1511 1700 1889 2078 2456 2833 3211 3589 3967 4344 4722 5100 547890/70/20 1937 2179 2421 2664 3148 3632 4116 4601 5085 5568 6053 6538 7022

    wall $ 276,60 306,60 326,40 344,50 390,90 462,20 504,20 580,80 666,00 717,00 762,20 808,90 851,70central 332,00 365,50 388,80 408,40 477,00 553,30 601,70 686,80 777,00 848,50 898,70 953,60 1001,40

    050 75/65/20 1603 1803 2003 2204 2604 3005 3406 3806 4207 4608 5008 5409 581090/70/20 2055 2311 2568 2825 3338 3852 4366 4879 5393 5907 6420 6934 7448

    wall 285,30 316,20 336,80 355,40 404,70 477,30 520,90 599,60 686,00 739,60 786,10 834,90 878,90central 347,80 383,10 408,10 428,50 502,20 581,00 632,70 722,00 814,70 890,50 943,20 1002,20 1052,50

    code height length typeORDERING CODE : BIFW. 030 090 16

    BIFF. 030 090 16

    Wall mounting Twin_ type 16 Central mounting Twin_ type 16

    Installation into pre-formed duct

  • 8/3/2019 Preturi ere Pentru Canal la

    8/8

    60

    BIFFBIFWL

    H

    BIFW: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Brackets- Separation wall, dark grey lacque-

    red- Air vent 1/8: elbow (type 20) or

    extended (type 21)- Drain cock 1/2

    BIFF: standard delivery - Low-H2O heat exchanger, dark greylacquered in RAL 7024

    - Freestanding brackets- Feet: adjustable from 13.5 to

    18.5 cm- 2 separation walls, dark grey lac-

    quered- Air vent 1/8: elbow (type 20),

    extended (type 21)- Drain cock 1/2

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    020 75/65/20 1362 1532 1702 1872 2213 2553 2894 3234 3575 3915 4256 4596 493690/70/20 1746 1964 2182 2400 2837 3273 3710 4146 4583 5019 5456 5891 6327

    wall 173,20 195,20 209,10 222,00 270,50 322,80 352,40 383,10 443,70 478,60 510,60 543,80 574,80central 214,40 238,10 253,80 267,40 333,80 388,60 421,40 456,30 519,40 571,30 605,80 643,10 676,60

    030 75/65/20 1694 1906 2118 2330 2753 3177 3600 4024 4447 4871 5294 5718 614290/70/20 2171 2443 2715 2987 3529 4073 4615 5158 5700 6244 6786 7330 7873

    wall 181,10 203,90 218,70 231,90 283,00 336,60 367,70 400,60 462,50 499,50 532,70 568,00 600,20central 229,30 254,80 272,20 286,60 357,70 415,00 451,00 490,20 555,80 611,60 648,50 689,90 726,00

    040 75/65/20 1952 2196 2440 2684 3172 3660 4148 4636 5124 5612 6100 6588 707690/70/20 2502 2815 3128 3441 4066 4692 5317 5943 6568 7194 7819 8445 9071

    wall 190,70 214,40 230,00 243,70 298,20 352,90 385,70 420,70 483,80 523,90 558,30 595,60 629,20central 246,00 273,30 292,40 307,50 384,30 444,00 483,30 526,80 594,80 655,40 694,80 740,30 778,80

    050 75/65/20 2136 2414 2692 2968 3303 3881 4454 5026 5577 6115 6632 7142 764690/70/20 2738 3094 3451 3805 4234 4975 5709 6443 7149 7839 8501 9155 9801

    wall 200,40 225,00 241,50 255,50 313,60 369,60 404,00 441,10 505,40 548,60 584,20 623,60 658,40

    central 262,90 291,90 312,80 328,60 411,10 473,30 515,80 563,50 634,10 699,50 741,30 791,00 832,00

    code height length typeORDERING CODE : BIFW. 020 090 20

    BIFF. 020 090 20

    Wall mounting _type 20 Central mounting _type 20

    for duct length 110 120 130 140 160 180 200 220 240 260 280 300 320H L 090 100 110 120 140 160 180 200 220 240 260 280 300

    030 75/65/20 1732 1948 2164 2381 2814 3247 3680 4112 4545 4978 5411 5844 627790/70/20 2220 2497 2774 3052 3607 4162 4717 5271 5826 6381 6936 7491 8046

    wall 290,10 325,10 347,40 367,80 445,60 528,70 576,00 624,70 721,20 777,70 828,30 881,00 930,40central 338,40 376,00 400,90 422,40 520,30 607,10 659,30 714,30 814,60 889,80 944,10 1003,00 1056,10

    040 75/65/20 2021 2274 2527 2779 3285 3790 4295 4801 5306 5811 6317 6822 732790/70/20 2591 2915 3239 3562 4211 4858 5506 6154 6802 7449 8098 8745 9392

    wall 299,70 335,60 358,70 379,50 460,80 545,10 594,00 644,80 742,60 802,10 853,90 908,60 959,30central 355,10 394,50 421,10 443,40 546,90 636,20 691,60 750,80 853,60 933,60 990,40 1053,30 1109,00

    050 75/65/20 2180 2453 2726 2998 3543 4088 4633 5179 5724 6269 6814 7359 790490/70/20 2794 3144 3494 3843 4542 5240 5939 6639 7337 8036 8735 9433 10132

    wall 309,30 346,10 370,10 391,20 475,90 561,50 612,00 664,90 764,00 826,40 879,50 936,30 988,20central 371,80 412,90 441,30 464,30 573,50 665,30 723,80 787,40 892,60 977,30 1036,60 1103,70 1161,80

    code height length typeORDERING CODE : BIFW. 030 090 21

    BIFF. 030 090 21

    Wall mounting Twin_ type 21 Central mounting Twin_ type 21

    Installation into pre-formed duct