    Predimensionarea elementelor structurii de rezistenta(conform SR EN 1992)

    1. GRINZI

    1.1 Grinzi principale transversale

    Lmax[m]= 20.7 (deschiderea grinzii)

    1.1 [m] 1.1 [m]

    0.45 [m] 0.45 [m]

    0.15 [m] 0.15 [m]

    0.3 [m] 0.3 [m]

    b= 0.12 [m] 0.12 [m]

    A= 0.21765 mp

    g[m]= 5.44125 [kN/m]

    1.2 Pana acoperis

    Lmax= [m]

    h(mm) bu(mm) bo(mm) Lmax(m)

    150 190 7.5

    190 230 10150 200 10

    190 240 12.5

    150 210 11

    190 250 15

    800 190 270 17.5

    h[m]= 0.5 [m]

    bo[m]= 0.19 [m]

    bu[m]= 0.24 [m]

    A= 0.1075 [mp]

    g= 2.6875 [kN/m]

    1.3 Grinzi marginale beton armat

    b= 0.8 [m]

    h= 0.3 [m]

    A= 0.24 [mp]

    g= 6 [kN/m]

    600

    Valoare

    recomandata

    Valoarea de

    calcul

    400

    500

    16

    l

    20

    lh

    40

    l

    50

    lbo

    ]m[35.015.0du

    ]m[4.03.0bu

  • 7/28/2019 Prefabricate.xls

    2/3

    1.4 Grinzi de fronton (beton armat)

    b= 0.7 [m]

    h= 0.3 [m]

    A= 0.21 [mp]

    g= 5.25 [kN/m]

    2. STALPI

    Dimensiunile tramei

    L= 20.7 [m]

    T= 15.2 [m]

    Stalp

    S1 As1= 315 [mp] 1 3 0 0

    S2 As2= 105.9 [mp] 0.5 2 0 0

    S3 As3= 27.2 [mp] 0 1 0 0S4 As4= 35.9 [mp] 0.5 1 1 0

    S5 As5= 13.1 [mp] 0 0 0.5 0.5

    S6 As6= 27.2 [mp] 0 0 1 0

    S7 As7= 53.6 [mp] 0 0.5 0 1

    = 0.3 (forta axiala normalizata)

    fcd= fck/b= 20 [N/mmp] 20000 [kN/mp]

    forta axiala in stalp la nivelul incastrarii in starea limita de serviciu de lunga durata

    (P+0,4U+0,4Z)

    Stalp

    S1 N= 861.6 [kN] h= 0.378953 [m] h= 0.5 [m]

    S2 N= 764.5 [kN] h= 0.356947 [m] h= 0.4 [m]

    S3 N= 667.3 [kN] h= 0.333492 [m] h= 0.4 [m]

    S4 N= 744 [kN] h= 0.352146 [m] h= 0.4 [m]

    S5 N= 654.8 [kN] h= 0.330347 [m] h= 0.4 [m]

    S6 N= 646.9 [kN] h= 0.328348 [m] h= 0.4 [m]

    S7 N= 683.1 [kN] h= 0.337417 [m] h= 0.4 [m]

    S1' N= 941.6 [kN] h= 0.396155 [m] h= 0.55 [m]

    Incarcare axiala Valoare recomandata Valoare de calcul

    Arii aferente

    Pane Grinzi

    marginale

    Grinzi

    fronton

    Grinzi

    principale

    cd

    ELD

    ss

    f

    Nh

    ELD

    sN

  • 7/28/2019 Prefabricate.xls

    3/3

    Calculul incarcarilor la nivelul acoperisului

    A. Incarcari permanente

    1. Invelitoare+ termoizolatie+hidroizolatie

    gth= 0.22 [kN/mp]ghd= 0.03 [kN/mp]

    ght+hd= 0.25 [kN/mp]

    2. Tabla profilata

    gtab= 0.13 [kN/mp]

    3. Grinzi

    3.1 Grinzi principale transversale (beton armat prefabricat)

    gGT= 5.4413 [kN/m]

    3.2 Pane de acoperis (beton armat prefabricat)

    gpane= 2.6875 [kN/m]

    3.3 Grinzi marginale (beton armat)

    ggm= 6 [kN/m]

    3.4 Grinzi de fronton (beton armat)

    ggf= 5.25 [kN/m]

    4, Incarcarea tehnologica

    gteh= 0.35 [kN/mp]

    5. Incarcarea data de platforma metalica

    Gpm= 10t= 100 [kN]

    6. Incarcarea data de condensator

    Gc= 10t= 100 [kN]

    B. Incarcari variabile

    7. Incarcarea din zapada

    2 [kN/mp]

    i= 0.8 (coeficient de forma pentru acoperisuri plane)

    ce= 1 (coeficient de expunere)

    ct= 1 (coeficient termic pentru acoperisuri cu termoizolatii uzuale)

    sok= 2.5 [kN/mp] (valoarea caracteristica a incarcarii din zapada pe sol)

    8.Incarcarea utilaqu= 0.75 [kN/mp] (acoperis de tip terasa necirculabila)

    sk=i*ce*ct*sok=