NTE Enel RO

download NTE Enel RO

of 228

Transcript of NTE Enel RO

NORMA

TEHNICA ENEL

Prezentul document este proprietatea intelectual a societii S.C. ENEL Distribuie Banat S.A.; S.C. ENEL Distribuie Dobrogea S.A.; S.C. ENEL Distribuie Muntenia S.A.; Reproducerea sau divulgarea acestuia se va face cu obinerea n prealabil a aprobrii societii susmenionate care i va proteja drepturile civile i penale conform legii. This document is intellectual property of S.C. ENEL Distribuie Banat S.A.; S.C. ENEL Distribuie Dobrogea S.A.; S.C.ENEL Distribuie Muntenia S.A.; reproduction or distribution of its contents in any way or by any means whatsoever is subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.

Titlu Regulament tehnic de referin pentru racordarea Consumatorilor i Productorilor la reelele T i MT ale societii Enel Distribuie Banat, Dobrogea si Muntenia

Title Technical regulation reference for connecting electricity Consumers and Productors in HV and MT distribution network of Enel Distributie Dobrogea, Banat and Muntenia

Editie

Natura ModificrilorTraducerea in limba romana si adaptarea la normele romanesti. Aceasta specificatie se refera la editia originala CEI 0-16, DK 5400, DK 5600, DK 5740 drepturile de copiere apartinand Enel Distribuie.

1 Translation to romanian language and adaptation to romanian norm. This spec is referred to the master edition CEI 0-16, DK 5400, DK 5600, DK 5740 copyright of Enel Distribuie.

Unitatea Inginerie

Redactat M. DOMNICU F.D. ANDREI

Verificat S. PETRE V. OBREJAN A. POENARU G. DISSEGNA

Aprobat

Data 17/03/2010

Director General ENEL Distribuie Banat, ENEL Distribuie Dobrogea, ENEL Distribuie Muntenia

Alberto BIRGA

25/03/2010

1

NORMA TEHNICA ENEL REGULAMENT PRIVIND RACORDAREA UTILIZATORILOR LA REELE ELECTRICE DE MEDIE TENSIUNE I NALT TENSIUNE ALE SOCIETILOR DE DISTRIBUTIE DE ENERGIE ELECTRIC ENELCUPRINS Ediia de fa, furnizeaz prescripii de referin pentru conectarea corect a instalaiilor Utilizatorilor innd cont de caracteristicile utilizatorilor, electrice i de gestionare a majoritii reelelor din Romnia. Prescripiile in cont att de cerinele distribuiei energiei electrice i a siguranei funcionale a reelelor, ct i de cerinele Utilizatorilor care vor trebui s fie racordai la acestea din urm. Toi Distribuitorii, formulnd n detaliu Utilizatorilor prescripiile de racordare, respectnd Norma de fa, pun n practic un comportament uniform, transparent i echitabil (ne-discriminatoriu) pe teritoriul naional. Prescripiile din Norma de fa au ca scop racordarea la reelele de distribuie cu condiia ca instalaiile Utilizatorilor s fie conforme acesteia. Norma de fa se aplic noilor utiliti i parial i celor existente: regulile pentru acestea din urm sunt stabilite de ANRE.

Partea 1 Obiect, scop i definiii ............................................................................. 11 1 Obiectul i scopul Normei ........................................................................... 11 2 Domeniul de aplicare .................................................................................. 11 3 Definiii termeni ........................................................................................... 12 3.1. Gol de tensiune........................................................................................... 12 3.2. Staia de Transformare (ST) ....................................................................... 12 3.3. Sarcini eseniale (referitoare la instalaiile de producere) ........................... 12 3.4 Sarcini privilegiate (referitoare la instalaii de producere) ........................... 12 3.5 Sarcini proprii.............................................................................................. 12 3.6. Cablul de legtur....................................................................................... 12 3.7. Compatibilitate electromagnetic (CEM)..................................................... 12 3.8 Racordare ................................................................................................... 12 3.9 Dispozitiv de control al paralelismului ......................................................... 12 3.10 Dispozitivul generatorului............................................................................ 12 3.11 Dispozitiv de Interfa ................................................................................. 13 3.12 Dispozitiv de manevra................................................................................. 13 3.13 Dispozitiv General al Utilizatorului (DG)...................................................... 13 3.14 Distribuitor................................................................................................... 13 3.15 Exploatare................................................................................................... 13 3.16 Sarcin de energie electric ....................................................................... 13 3.17 Flicker ......................................................................................................... 13 3.18 Funcionarea reelei n condiii excepionale ............................................... 13 3.19 Funcionarea reelei n condiii normale de funcionare............................... 13 3.20 Funcionare insularizat.............................................................................. 13 3.21 Gestionarul reelei electrice de transport (RET - Transelectrica) ................ 14 3.23 Grup generator ........................................................................................... 14 3.24 Instalaie de producere ............................................................................... 14 3.25 Instalaie de autoproducere ........................................................................ 14 3.26 Instalaie de cogenerare ............................................................................. 14 3.27 Instalaie de utilizare (sau de Utilizator) ...................................................... 14 3.28 Instalaie Consumator ................................................................................. 14 2

3.31 Instalaie de racordare ................................................................................ 14 3.33 ntreruperea alimentrii ............................................................................... 14 3.34 Limite admisibile pentru perturbaiile provocate de receptoarele Utilizatorului15 3.35 Nivel de compatibilitate ............................................................................... 15 3.36 Nivel de emisie ........................................................................................... 15 3.37 Nivel de emisie transferat ......................................................................... 15 3.38 Planificarea operaional a RED................................................................. 15 3.39 Puterea maxim posibil a unei uniti (a unei centrale)............................. 15 3.41 Puterea cerut de reea .............................................................................. 15 3.42 Puterea nominal........................................................................................ 15 3.43 Programarea operaional a funcionrii RED ............................................ 15 3.44 Limita de proprietate ................................................................................... 15 3.45 Punct de delimitare ..................................................................................... 15 3.46 Punct de racordare (la RED)....................................................................... 16 3.47 Variaia tensiunii ......................................................................................... 16 3.48 Variaia rapid de tensiune ......................................................................... 16 3.49 Reea (reea de distribuie, reea de distribuie public).............................. 16 3.50 Reea de nalt Tensiune (T) ..................................................................... 16 3.51 Reea Foarte nalt Tensiune (FT)............................................................. 16 3.52 Reea Joas Tensiune (JT)......................................................................... 16 3.53 Reea n insul............................................................................................ 16 3.54 Reea MT .................................................................................................... 16 3.55 Reea planificat ......................................................................................... 16 3.56 Refuz de sarcin ......................................................................................... 16 3.57 Reanclanare automat rapid................................................................... 16 3.58 Servicii auxiliare de reea............................................................................ 16 3.59 Servicii auxiliare generale ........................................................................... 17 3.60 Serviciul de reglare a frecvenei.................................................................. 17 3.61 Serviciul de reglare al tensiunii ................................................................... 17 3.62 Sistem de Protecie General (SPG) .......................................................... 17 3.63 Staie electric ............................................................................................ 17 3.64 Serviciul de ntrerupere a sarcinii (DAS) ..................................................... 17 3.65 Sistem cu neutrul legat direct la pmnt ..................................................... 17 3.66 Tensiune armonic ..................................................................................... 17 3.67 Tensiune de exploatare declarat (tensiune declarat) .............................. 18 3.68 Utilizatorul reelei ........................................................................................ 18 3.69 Consumator (de energie electrica).............................................................. 18 3.70 Consumator nedispecerizabil...................................................................... 18 3.71 Consumator dispecerizabil.......................................................................... 18 3.72 Grup electric (generator)............................................................................. 18 3.73 Grup dispecerizabil ..................................................................................... 18 3.74 Grup nedispecerizabil ................................................................................. 18 Partea 2 Caracteristici ale Utilizatorilor, ale reelelor, ale criteriilor pentru alegerea nivelului de tensiune i ale schemelor de racordare la reelele T i MT 19 4 Caracteristici ale Utilizatorilor i clasificarea acestora................................. 19 4.1 Instalaia de utilizare ................................................................................... 19 4.1.1 Sensibilitatea echipamentelor n functie de parametrii de calitate a energiei electrice ......................................................................................................19 4.1.2 Aparate perturbatoare..................................................................................20 4.1.3 Utilizatori ntreruptibili ..................................................................................22 4.2 Instalaii de producere................................................................................. 22 4.2.1 Puterea ........................................................................................................22 4.2.2 Instalaii de producere perturbatoare ...........................................................22 4.4 Reele de distribuie .................................................................................... 23 5 Caracteristicile reelelor .............................................................................. 24 3

Caracteristicile reelelor de T ..................................................................... 24 Caracteristici structurale ..............................................................................24 Niveluri de tensiune i frecven .................................................................24 Starea neutrului ..........................................................................................24 Curent de scurtcircuit trifazat maxim n scopul dimensionrii echipamentelor ....................................................................................................................24 5.1.1.4 Curent de scurtcircuit monofazat maxim n scopul dimensionrii prizei de pmnt........................................................................................................24 5.1.1.5 Curent de scurtcircuit trifazat maxim n punctul de racordare .....................24 5.1.1.6 Curent de scurtcircuit trifazat minim n punctul de racordare ......................24 5.1.1.7 Curent de scurtcircuit trifazat minim convenional n punctul de racordare .24 5.1.1.8 Curent de defect monofazat n punctul de racordare i timpul de eliminare a defectului ....................................................................................................25 5.1.1.9 Nivel de inere al izolaiei ............................................................................25 5.1.2 Caracteristici de exploatare .........................................................................25 5.1.2.1 Funcionarea reelei ....................................................................................25 5.1.2.2 Eliminarea defectelor ..................................................................................25 5.1.2.3 Automatizari de reea..................................................................................26 5.1.3 Calitatea serviciului......................................................................................26 5.1.3.1 Continuitatea serviciului ..............................................................................26 5.1.3.2 Calitatea tensiunii........................................................................................26 5.1.4 Supravegherea reelelor de distribuie .........................................................27 5.1.5 Sisteme de comunicaie...............................................................................27 5.1.6 Indisponibilitate pentru lucrri ......................................................................27 5.2 Caracteristici ale reelelor de MT ................................................................ 27 5.2.1 Caracteristici structurale ..............................................................................27 5.2.1.1 Niveluri de tensiune si frecven .................................................................27 5.2.1.2 Starea neutrului ..........................................................................................27 5.2.1.3 Curent de scurtcircuit trifazat maxim (n scopul dimensionrii echipamentelor) ..........................................................................................27 5.2.1.4 Curent de scurtcircuit trifazat maxim de exploatare ....................................28 5.2.1.5 Curent de scurtcircuit trifazat minim de exploatare .....................................28 5.2.1.6 Curent de scurtcircuit trifazat minim convenional.......................................28 5.2.1.7 Curent de defect monofazat i timp de eliminare a defectului.....................28 5.2.1.8 Defect dublu monofazat (dubl punere la pmnt) ....................................29 5.2.1.9 Nivelurile de inere ale izolaiei ..................................................................29 5.2.2 Caracteristici de exploatare .........................................................................29 5.2.2.1 Funcionarea reelei ....................................................................................29 5.2.2.2 Funcionarea poriunilor de reea MT de distribuie n insul ......................29 5.2.2.3 Eliminarea defectelor ..................................................................................30 5.2.2.4 Automatizari de reea..................................................................................30 5.2.3 Calitatea serviciului n reelele de MT ..........................................................30 6 Criterii pentru alegerea nivelului de tensiune i a schemelor de racordare la reelele de T i MT ..................................................................................... 31 6.1 Obiective i reguli generale......................................................................... 31 6.2 Definiia racordarii ....................................................................................... 31 6.3 Determinarea nivelului de tensiune i a punctului de racordare (pasul P1) 31 6.4 Alegerea schemei instalaiei de racordare (pasul P2)................................. 33 6.4.1 Scheme de racordare ..................................................................................33 6.4.2 Fiabilitatea diferitelor scheme de racordare.................................................33 Partea 3 Reguli de racordare la reelele T ............................................................. 35 7 Racordarea la reelele T ............................................................................ 35 7.1 Scheme de racordare ................................................................................. 35 7.1.1 Racordare rigid n derivaie n T.................................................................35 7.1.2 Racordare n intrare-ieire ...........................................................................35 4

5.1 5.1.1 5.1.1.1 5.1.1.2 5.1.1.3

7.1.3 7.1.3.1 7.1.3.2 7.1.3.3 7.2 7.2.1 7.2.2 7.2.2.1 7.2.2.2 7.2.2.3 7.2.2.4 7.2.3 7.3 7.4 7.4.2 7.4.3 7.5 7.5.1 7.5.1.1 7.5.1.2. 7.5.2 7.5.3 7.5.3.1 7.5.3.2 7.5.4 7.5.5 7.5.5.1 7.5.5.2 7.5.5.3 7.5.6 7.5.7 7.5.8 7.5.9 7.5.10 7.5.11 7.5.12 7.5.12.1 7.5.12.2 7.5.12.3 7.5.12.4 7.5.12.5 7.5.13 7.5.14 7.6 7.6.1 7.6.2 7.7 7.7.1 7.7.1.1 7.7.1.2 7.7.2 7.7.2.1 7.7.2.2 7.7.2.3

Racordarea n anten ..................................................................................36 Racordarea n anten simpl (figura 6).......................................................36 Racordarea n anten n staie adiacent ...................................................36 Racordarea n anten in celula Staiei de Transformare.............................37 Schema instalaiei pentru racordare ........................................................... 37 Absen bare ...............................................................................................38 Sistem monobara.........................................................................................38 Schema normal.........................................................................................38 Scheme reduse...........................................................................................38 Schema extins ..........................................................................................39 Schem cu mai muli Utilizatori i schem cu multiple bare Utilizator.........39 Dispozitive de legare la pmnt necesare racordarii ...................................39 Soluii indicative de racordare..................................................................... 39 Scheme de racordare ................................................................................. 42 Scheme monofilare pentru racordarea n anten.........................................47 Scheme monofilare pentru conectare intrare-ieire .....................................51 Reguli tehnice de racordare comune tuturor categoriilor de Utilizatori........ 59 Puncte de delimitare i echipamente ale Utilizatorului necesare pentru racordare ....................................................................................................59 Punct de delimitare de gestiune..................................................................60 Echipamente ale Utilizatorului aferente racordrii.......................................61 Instalaie de racordare la retea ....................................................................61 Instalaia de utilizare pentru racordare.........................................................62 Echipamente prevzute ..............................................................................62 Criterii de dimensionare ..............................................................................63 Puncte de racordare multiple i alimentare de rezerv................................63 Instalaia de legare la pmnt......................................................................64 Dimensionare..............................................................................................64 Verificri......................................................................................................64 Racordari la alte instalaii de legare la pmnt ...........................................65 Responsabilitati privind securitatea ............................................................66 Indisponibilitate datorit lucrarilor de mentenana........................................66 Servicii auxiliare...........................................................................................66 Caracteristicile suprafetelor i spatiile aferente instalaiei de racordare ......66 Caracteristicile componentelor electrice ......................................................68 Dispozitiv General........................................................................................68 Sistemul de protecie asociat la Dispozitivul General ..................................68 Criterii generale ..........................................................................................68 Proteciile adoptate de Utilizatori ................................................................69 Reglajul dispozitivelor de protecie .............................................................70 Intervenii pe dispozitivele de protecie .......................................................70 Dispozitive de reanclanare automat ........................................................70 Starea neutrului ...........................................................................................71 Sisteme de comunicaie...............................................................................71 Reguli tehnice de racordare pentru Consumatori ....................................... 71 Dispozitive pentru ntreruperea sarcinii....................................................... 71 Limite de schimb de putere reactiv ............................................................72 Reguli tehnice de racordare pentru Productori ......................................... 72 Prescriptii generale ......................................................................................72 Teledeclanare rapid pentru protecie.......................................................72 Teleprotecie i difereniale longitudinale ....................................................72 Productori nedispecerizabili ......................................................................72 Instalaie de utilizare. Echipamente prevzute............................................72 Performanele aferente instalaiilor productorului......................................73 Protecii ale grupurilor de generare.............................................................74 5

7.7.2.4 7.7.2.5 7.7.3 7.7.4 7.7.5 7.7.6 7.8 8 8.1 8.1.1 8.1.2 8.1.3 8.1.4 8.1.5 8.2 8.2.1 8.3 8.4 8.4.1 8.4.2 8.5 8.5.1 8.5.2 8.5.3 8.5.3.1 8.5.3.2 8.5.4 8.5.5 8.5.5.1 8.5.5.2 8.5.5.3 8.5.6 8.5.7 8.5.9 8.5.10 8.5.11 8.5.12 8.5.12.1 8.5.12.2 8.5.12.3 8.5.12.4 8.5.12.5 8.5.12.6 8.5.12.7 8.5.13 8.5.14 8.6.1 8.6.2 8.6.3 8.7 8.7.1 8.7.2

Protecii mpotriva defectelor interne n instalaia de utilizare .....................74 Dispozitive specifice pentru separarea reelei.............................................74 Productori dispecerizabili ...........................................................................75 Funcionarea grupului din reea n insula.....................................................75 Informaii pentru evidenta evenimentelor.....................................................75 Limite de schimb de putere reactiv ............................................................75 Reguli tehnice pentru racordare reelelor interne de utilizare...................... 75 Racordarea la reeaua de MT ..................................................................... 76 Scheme de racordare ................................................................................. 76 Racordare n intrare ieire pe liniile existente (schema A)........................77 Racordare n anten din staie T/MT (schema B1) .....................................77 Racordare n anten din postul de MT/JT (schema B2) ..............................77 Racordare n anten prin EDM (eventual adugat n post existent) n lungul unei linii existente (schema C) ....................................................................77 Racordare n derivaie rigid n T pe o linie existent (schema D)...............77 Schema instalatiei de racordare ................................................................. 77 Dispozitive de legare la pmnt aferente racordrii.....................................79 Soluii de racordare..................................................................................... 80 Schema instalaiei de utilizare pentru racordare ......................................... 81 Schem cu o singur celul (caz general aplicabil tuturor Utilizatorilor) ......81 Schema cu doua celule de MT pe bara principal .......................................83 Reguli tehnice de racordare comune tuturor categoriilor de Utilizatori........ 85 Punct de delimitare, puncte de delimitare de gestiune i de exploatare ......85 Instalaia de racordare .................................................................................86 Instalaia de utilizare ....................................................................................86 Echipamente prevzute ..............................................................................86 Criterii de dimensionare ..............................................................................87 Puncte de racordare multiple i alimentri de rezerv .................................88 Instalaia de legare la pmnt......................................................................88 Dimensionare..............................................................................................88 Verificri......................................................................................................90 Legturi la alte instalaii de legare la pmnt..............................................91 Responsabiliti privind securitatea .............................................................91 Indisponibilitate datorat lucrrilor de mentenan ......................................91 Caracteristicile spaiilor................................................................................91 Caracteristicile echipamentelor electrice .....................................................93 Dispozitiv General........................................................................................94 Sistem de protecie asociat la Dispozitivul General .....................................94 Criterii generale ..........................................................................................94 Protecii adoptate pentru toi Utilizatorii.......................................................95 Reglaje ale PG............................................................................................97 Circuite de comand ...................................................................................99 Intervenii pe dispozitivele de protecie .....................................................100 Dispozitive de reanclanare automat ......................................................100 Coordonare selectiv ntre proteciile de MT ale utilizatorului (protecii bazate pe schimb de informaii) ................................................................100 Limite de putere pe seciunile de bare de JT .............................................102 Limitele energizrii ale transformatoarelor instalate simultan ....................103 DG simplificat pentru instalaia Consumatorului cu un transformator MT/JT de putere nominal egal sau mai mic de 400 kVA (soluie n studiu)....104 Instalaie consumator cu linie n anten.....................................................105 Limite de schimb de putere reactiv ..........................................................105 Reguli tehnice de racordare pentru Productori ....................................... 105 Limite de putere total produs care se pot racorda la reelele de MT ......105 Schema general de racordare a unui Productor ....................................105 6

8.7.3 Condiii de funcionare a instalaiei de producere ......................................110 8.7.4 Dispozitive prevzute.................................................................................110 8.7.4.1 Dispozitivul de Interfa (DDI) ...................................................................111 8.7.4.2 Dispozitivul generatorului (DDG) ..............................................................112 8.7.5 Sisteme de protecie ..................................................................................112 8.7.5.1 Protecii asociate DDI ...............................................................................112 8.7.5.2 Protecie de rezerv n caz de refuz de deschidere a DDI........................113 8.7.5.3 Eliminarea temporar a SPI......................................................................114 8.7.5.4 Proteciile grupurilor de producere............................................................114 8.7.5.5 Caracteristicile TT pentru SPI ...................................................................114 8.7.5.6 Dispozitive de control pentru punerea n paralel (generator-reea)...........115 8.7.6 Instalaia productorului conectat n anten ..............................................115 8.7.7 Limite de schimb de putere reactiv ..........................................................115 8.8 Reguli tehnice pentru racordarea reelelor interne ale Productorilor....... 116 Partea 5 Prevederi pentru Productori i Consumatori, IT i MT, pentru compatibilitatea electromagnetic (EMC), msurarea continuitii i calitii tensiunii...................................................................................................................... 117 9 Prevederi pentru compatibilitatea electromagnetic ................................. 117 9.1 Evaluarea perturbaiilor............................................................................. 117 10 Msurarea continuitii i calitii tensiunii ................................................ 117 Partea 6 Reguli de racordare ntre reele de distribuie ...................................... 118 11 Reguli tehnice de racordare pentru reelele de distribuie......................... 118 11.1 Punct de interconectare ............................................................................ 118 11.2 Msurarea energiei schimbate.................................................................. 118 11.3 Semnale i msurri schimbate ntre operatorii de retea.......................... 118 11.4 Exploatare i ntreinere ............................................................................ 118 11.5 Calitate tehnic a serviciului ..................................................................... 118 Partea 7 Sisteme de msurare a energiei 119 12 Sisteme de msurare a energiei ............................................................... 119 12.1 Caracteristicile sistemelor de msurare .................................................... 119 12.2 Instalarea sistemului de msurare ............................................................ 120 12.3 Cerine funcionale ale contorului.............................................................. 121 12.4 Activarea i ntreinerea sistemului de msurare ...................................... 122 12.5 Sistemul de msurare al energiei n punctele de consum......................... 123 12.6 Sistemul de msurare a energiei n punctele de producere...................... 123 Parte 8 Contract de Distributie/Furnizare, obligaii de informare i documentaii125 13 Contract de Distributie/Furnizare, obligaii de informare i documentaie . 125 13.1 Contract de Distributie/Furnizare .............................................................. 125 13.1.1 Caracteristici indicative ale REELEI n punctul de racordare...................125 13.1.2 Caracteristici ale instalaiilor i ale proceselor ...........................................126 13.1.3 Exploatarea, conducerea i controlul instalaiilor .......................................126 13.1.4 Convenia de Exploatare ...........................................................................127 13.2 Documentaie tehnic necesar pentru racordare .................................... 127 13.2.1 Schem monofilar....................................................................................128 13.2.2 Schemele funcionale ale Sistemului de Comand, Control i Protecie....128 13.2.3 Descrieri tehnice, manuale i date de recepie ..........................................129 ANEXA L1................................................................................................................... 130 (Model de scrisoare care trebuie trimis clienilor nainte de punerea n funciune a Postului de transformare) ............................................................................................ 130 ANEXA L2................................................................................................................... 132 Declaratie de confirmare a racordarii........................................................................... 132 ANEXA A .................................................................................................................... 133 Coordonarea proteciilor i a automatizarilor de reea cu proteciile instalaiilor utilizatorului.................................................................................................................. 133 A.1 Reele de T .............................................................................................. 133 7

Protecii i automatizari de reea............................................................... 134 Coordonarea proteciilor reelei cu cele ale utilizatorului........................... 134 Reele de MT ............................................................................................ 134 Protecii i automatizri de reea............................................................... 134 Coordonarea proteciilor reelei cu cele ale Utilizatorului .......................... 135 Coordonare selectiv ntre proteciile utilizatorului la aceeai tensiune cu tensiunea de racordare ............................................................................. 135 ANEXA B .................................................................................................................... 137 Cerine minime ale DG i SPG pentru instalaii de MT existente................................. 137 Declaraie de conformitate........................................................................................... 137 B.1 ncercri la complexul DG+PG.................................................................. 137 ANEXA C .................................................................................................................... 140 Caracteristici privind Sistemul de Protecie General pentru reelele de T ................... 140 C.1 Generaliti ............................................................................................... 140 C.1.1 Transformatoare de curent pentru protecie (TC) ..................................... 140 C.1.2 Transformatoare de tensiune pentru protecie (TT) .................................. 141 C.1.3 Indicaii de funcionare pentru PG............................................................. 141 C.1.4 ncercri i certificri ale PG ..................................................................... 142 C.1.4.1 ncercri de funcionare ............................................................................ 142 C.1.4.2 ncercri de compatibilitate cu mediul nconjurtor ................................... 142 C.1.4.3 ncercri de suprancrcare a circuitelor de msurare .............................. 143 C.1.4.4 Conformitatea dispozitivelor...................................................................... 144 ANEXA D .................................................................................................................... 145 Caracteristicile Sistemului de Protecie General (SPG) pentru reele de MT............. 145 D.1 Definiia SPG pentru reele de MT ............................................................ 145 D.2 Caracteristicile SPG neintegrat................................................................. 146 D.2.1 TC pentru protecia maximal de curent ................................................... 147 D.2.1.1 Caracteristici i verificri n cazul utilizrii de TC lineare........................... 148 D.2.1.1.1 Verificri efectuate pe TC lineare.............................................................. 148 D.2.1.1.2 ncercri funcionale pentru PG care utilizeaz TC liniare ........................ 149 D.2.1.2 Caracteristici i verificri n cazul utilizrii TC neliniare............................. 149 D.2.1.2.1 Verificri n cazul TC neliniare .................................................................. 149 D.2.1.2.2 ncercrile pentru confirmarea cuplrii corecte PG+TC neliniar................ 149 D.2.1.3 Soluii de protejare prin utilizarea de transformatoare de curent neconvenionale........................................................................................ 152 D.2.2 Transformatoare de curent toroidale pentru protecia mpotriva defectelor la pmnt (TCH) ........................................................................................... 153 D.2.2.1 Caracteristicile i ncercrile pentru transformatoarele de curent homopolar (TCH) omologate ...................................................................................... 154 D.2.2.1.1 Caracteristicile TCH omologate ................................................................ 154 D.2.2.1.2 ncercri funcionale pentru PG care utilizeaz TCH omologate............... 155 D.2.2.2 Caracteristicile i ncercrile pentru TCH neomologate ............................ 155 D.2.2.2.1 Caracteristicile TCH neomologate ............................................................ 155 D.2.2.2.2 ncercri funcionale pentru PG care utilizeaz TCH neomologate........... 155 D.2.2.3 Caracteristicile i ncercrile pentru TCH neconvenionale....................... 157 D.2.3 Transformatoare de tensiune pentru tensiunea homopolara .................... 157 D.2.3.1 Caracteristicile i ncercrile pentru TT homopolare omologate ............... 158 D.2.3.1.1 Caracteristicile TT homopolare omologate ............................................... 158 D.2.3.1.2 ncercri funcionale pentru TT homopolare omologate............................ 158 D.2.3.2 Caracteristicile i ncercrile pentru TT homopolare neomologate ........... 158 D 2.3.2.1 Caracteristici ale TT homopolare neomologate ........................................ 158 D 2.3.2.2 ncercri funcionale pentru TT homopolare neomologate........................ 159 D.2.3.3 TT homopolare neconvenionale .............................................................. 159 D.2.4 Caracteristicile Proteciei Generale (PG) .................................................. 159 D.2.4.1 Prescripii funcionale pentru protecia maximal de curent de faz ......... 159 A.1.1 A.1.2 A.2 A.2.1 A.2.2 A.2.3 8

Prescripii funcionale pentru protecia mpotriva curentului maximal homopolar................................................................................................. 160 D.2.4.3 Prescripii funcionale pentru protecia homopolar direcional............... 161 D.2.4.4 ncercri cu arc intermitent........................................................................ 162 D.2.4.4.1 ncercri pe SPG cu protecie maximal homopolar de curent ............... 162 D.2.4.4.2 ncercri pe SPG cu protecie homopolar direcional ............................ 163 D.2.4.5 Comenzi de deschidere ntreruptor........................................................... 164 D.2.4.6 Semnalizri locale..................................................................................... 164 D.2.4.7 ncercri pe PG......................................................................................... 164 D.2.4.7.1 ncercri funcionale.................................................................................. 165 D.2.4.7.2 ncercri de compatibilitate electromagnetic ........................................... 166 D.2.4.7.3 ncercri de compatibilitate cu mediul ....................................................... 166 D.2.4.7.4 ncercri de suprancrcare ale circuitelor de msur .............................. 167 D.2.5 Conformitatea dispozitivelor...................................................................... 167 D.3 Caracteristicile Sistemului de Protecie General integrat ........................ 168 D.3.1 Prescripii funcionale pentru SPG integrat ............................................... 168 D.3.1.1 Prescripii funcionale pentru protecia maximal de curent de faz ......... 168 D.3.1.2 Prescripii de funcionare pentru protecia maximal homopolar de curent169 D.3.1.3 Prescripii de funcionare pentru protecia homopolar direcional ......... 171 D.3.1.4 Comenzi de deschidere ntreruptor........................................................... 172 D.3.1.5 Semnalizri locale..................................................................................... 172 D.3.2. ncercri i certificri ale SPG integrat ...................................................... 172 D.3.3 ncercri de funcionare ............................................................................ 172 D.3.3.1 Exemplu de posibil modalitate de verificare a treptei homopolare direcionale n SPG integrate care folosesc 3 traductoare de curent ........ 173 D.3.3.2 ncercri pentru defecte polifazate ............................................................ 176 D.3.3.3 ncercri de defect monofazat................................................................... 177 D.3.3.3.1 ncercri la SPG cu protecie maximal homopolar de curent ................ 177 D.3.3.3.2 ncercri la SPG cu protecie homopolar direcional ............................. 179 D.3.3.4 ncercare cu arc intermitent ...................................................................... 179 D.3.3.4.1 ncercri la SPG integrat cu protecie de curent homopolar maxim .......... 180 D.3.3.4.2 ncercri pe SPG cu protecie homopolar direcional ............................ 180 D.3.4 ncercri de compatibilitate i adiionale ................................................... 181 D.3.5 Conformitatea dispozitivelor...................................................................... 183 D.4 Sistemul de control i nregistrri asociat la PG........................................ 186 D.4.1 Caracteristici ............................................................................................. 186 D.4.2 Funcii ale data logger............................................................................... 187 D.4.2.1 Prezena legturii ntre PG i logger (doar dac logger nu e incorporat n PG) ........................................................................................................... 187 D.4.2.2 Prezena alimentrii logger (doar dac logger nu e incorporat n PG) ...... 187 D.4.2.3 Prezena alimentrii PG ............................................................................ 187 D.4.2.4 Prezena i continuitatea circuitului de declanare ................................... 187 D.4.2.5 Trepte de reglaj setate pe PG dup instalare ........................................... 187 D.4.2.6 Evenimente care au cauzat activarea PG................................................. 188 D.4.2.7 Evenimente care au cauzat emiterea comenzii de deblocare a DG ......... 188 D.4.2.8 Funcionalitatea releului ............................................................................ 188 D.4.2.9 Prezena circuitelor de curent ................................................................... 188 D.4.2.10 Prezena circuitelor de tensiune................................................................ 188 D.4.3 ncercri de funcionalitate ........................................................................ 189 D.4.4 Conformitatea dispozitivelor...................................................................... 189 ANEXA E..................................................................................................................... 191 Caracteristici ale Sistemului de Protecie de Interfa (SPI) ........................................ 191 E.1 Caracteristici ale sistemului de protecie de interfa (SPI)....................... 191 E.2 Traductori de msur (TT) ........................................................................ 191 E.3 Caracteristici ale proteciilor...................................................................... 191 9

D.2.4.2

E.3.1 Componena sistemului ............................................................................ 191 E.3.2 Protecia minimal de tensiune de linie..................................................... 192 E.3.3 Protecia maximal de tensiune de linie (59) ............................................ 192 E.3.4 Protecia minimal de frecven (81 ) .................................................... 193 E.3.6 Protecia maximal de tensiune homopolar (59 Vo) ............................... 193 E.3.7 Erori limite pentru mrimile de intervenie................................................. 194 E. 3.8 Consum i suprasarcin a circuitelor de tensiune de msur................... 194 E.3.9 Circuit de declanare ................................................................................ 194 E.3.10 Semnalizri ............................................................................................... 194 E.3.11 Teste......................................................................................................... 194 E.3.11.1 Teste funcionale ...................................................................................... 194 E.3.11.1.1 Precizri suplimentare pentru teste........................................................... 195 E.3.11.2 Teste de compatibilitate electromagnetic................................................ 195 E.3.11.3 Teste de compatibilitate cu mediul............................................................ 196 E.3.11.4 Teste de suprasarcin a circuitelor de msur i de alimentare ............... 196 E.3.12 Certificare ................................................................................................. 196 ANEXA F..................................................................................................................... 198 Puterea de scurtcircuit n punctul de racordare ........................................................... 198 ANEXA G .................................................................................................................... 200 Informaii de furnizat cu privire la funcionalitatea i la reglajele SPG ......................... 200 ANEXA H .................................................................................................................... 201 CONSTRUCIE PT ..................................................................................................... 201 ANEXA J ..................................................................................................................... 204 CONVENTIE DE EXPLOATARE................................................................................. 204 ANEXA K .................................................................................................................... 205 CONVENTIE DE EXPLOATARE................................................................................. 205 ANEXA L..................................................................................................................... 212 (Model scrisoare de trimis la clienti pentru a le comunica valoarea curentului homopolar si timpul de eliminare al acestuia)........................................... 212 ANEXA M .................................................................................................................... 213

10

REGULAMENT PRIVIND RACORDAREA UTILIZATORILOR LA REELE ELECTRICE DE NALT TENSIUNE I MEDIE TENSIUNE ALE SOCIETILOR DE DISTRIBUTIE DE ENERGIE ELECTRIC ENELPartea 1 Obiect, scop i definiii 1 Obiectul i scopul Normei Norma de fa are scopul de a defini criteriile tehnice pentru racordarea Utilizatorilor la reele electrice de distribuie de curent alternativ cu tensiune nominal mai mare de 1 kV pn la 110 kV. Soluiile tehnice indicate n documentul de fa reprezint regulile n materie care se utilizeaz la momentul actual. Soluii alternative fa de cele indicate aici, n msur s obin aceleai prestaii solicitate n ceea ce privete fiabilitatea i sigurana, pot fi aplicate, cu condiia s fie n prealabil supuse ateniei i acceptate de ctre ANRE. Instalaiile care fac obiectul Normei de fa trebuie s fie construite dup toate standardele i reglementarile n vigoare i n acest scop este suficient concordana cu normele i standardele Europene i Internaionale. 2 Domeniul de aplicare Norma de fa se aplic tuturor instalaiilor electrice aferente utilizatorilor serviciului de distribuie i de racordare la reelele de distribuie n continuare denumii Utilizatori ai reelei (Utilizatori). Utilizatorii reelei sunt proprietari de: instalaii de utilizare care includ consumatori racordati la reele de distribuie a energiei electrice de MT si JT; instalaii de utilizare care cuprind consumatori racordati la reele de distribuie a energiei electrice ENEL de IT (acestor instalaii li se aplic de asemenea regulile tehnice stabilite de ctre Gestionarul reelei de transport Naional (n continuare, Transelectrica) pentru aspectele care privesc dispecerizarea); instalaii de producere care cuprind uniti de producere nedispecerizabile racordate la reele de distribuie a energiei electrice ENEL. instalaii de producere care includ uniti de producere dispecerizabile racordate la reele de distribuie a energiei electrice (acestor instalaii li se aplic de asemenea regulile tehnice stabilite de ctre Transelectrica pentru aspectele referitoare la dispecerizare, msurare, programarea mentenanei, precum i aspecte referitoare la dispozitive de control i protecie)1; reele interne de utilizare dup cum sunt definite de dispoziiile ANRE n vigoare; reele de distribuiei interconectate (cu ali propietari).

-

-

Norma de fa se aplic noilor racordri (aplicare integral); aplicarea acesteia la instalaiile Utilizatorilor existenti este reglementata de ctre ANRE.

1

n faza cererii de racordare, Utilizatorul are drept interfa pe Transelectrica. Ulterior, dup realizarea racordrii, n faza de exploatare, subiectul proprietar al instalaiilor de producere care cuprind uniti de producere dispecerizabile va avea raporturi i cu Distribuitorul. n acest scop, Regulamentul de Exploatare (prevzut n cadrul Contractului de Distributie) trebuie s fie redactat mpreun de Utilizator, de Distribuitor i de Transelectrica.

11

3 Definiii termeni n mod convenional, n continuarea textului Normei de fa, expresia n amonte identific circuitele inainte de punctul de racordare; respectiv, expresia n aval identific circuitele Utilizatorului aflate dupa punctul de racordare. n accepia prezentei Norme se aplic urmtoarele definiii. 3.1. Gol de tensiune Reducerea brusc a tensiunii de alimentare la o valoare ntre 90% i 1% din tensiunea nominal (declarat) urmat de o revenire a tensiunii, dup un scurt interval de timp. n mod convenional durata unui gol de tensiune este ntre 10 ms i 1 minut. Amplitudinea golului este definit ca diferena ntre valoarea minim efectiv, pe durata golului i tensiunea declarat. Variaiile de tensiune care nu conduc la o reducere a tensiunii sub 90% din tensiunea declarata nu se consider goluri de tensiune. Golul de tensiune poate afecta una sau mai multe faze i se numete unipolar, bipolar sau tripolar dac afecteaz respectiv una, dou sau trei faze. 3.2. Staia de Transformare (ST) Staie electric alimentat la T, prevzut cu cel puin un transformator T/MT dedicat reelei de distribuie. 3.3. Sarcini eseniale (referitoare la instalaiile de producere) Sarcini electrice asociate direct procesului de producere a energiei electrice al productorului i indispensabile continuitii aceluiai proces de producere a energiei electrice. 3.4 Sarcini privilegiate (referitoare la instalaii de producere) O parte din sarcinile electrice prezente n instalaie (n sensul prezentei Norme, n instalaia de producere) crora Utilizatorul intenioneaz s le garanteze o continuitate n mod deosebit. n caz de funcionare separat de reeaua electric de distribuie, sarcinile privilegiate sunt n mod obinuit alimentate de ctre instalaia de producie dup deschiderea ntreruptorului de interfa. Sarcinile privilegiate includ sarcinile eseniale. 3.5 Sarcini proprii Toate sarcinile electrice prezente n instalaia de producere a energiei electrice sau care sunt direct conectate la aceasta fr interpunerea reelei de distribuie. 3.6. Cablul de legtur Poriunea de cablu, complet echipat cu terminale, care leag n punctul de delimitare clemele din intrare ale Dispozitivului General al utilizatorului MT. A se vedea n acest sens i Figura 19. 3.7. Compatibilitate electromagnetic (CEM) Aptitudinea unui dispozitiv (echipament sau sistem) de a funciona n mediul su electromagnetic, fr s produc el nsui perturbaii electromagnetice intolerabile pentru orice ce se gsete n acest mediu. 3.8 Racordare Legtura la o reea a unei instalaii electrice pentru care exist, cel puin ntr-un punct, continuitatea n alimentare, fr interpunerea instalaiilor electrice ale terilor, cu aceeai reea. 3.9 Dispozitiv de control al paralelismului Automatizare care permite efectuarea legturii n paralel ntre reele sau ntre reea i generator. 3.10 Dispozitivul generatorului Echipament de manevr a crui deschidere (comandat de un sistem de protecie adecvat) determin separarea grupului de generare de reteaua de distributie.

12

3.11 Dispozitiv de Interfa Unul (sau mai multe) echipamente de manevr a crei/cror deschidere (comandat de un sistem de protecie adecvat) asigur separarea instalaiei de producere de reea, permind instalaiei de producere funcionarea n insul pentru sarcinile privilegiate. 3.12 Dispozitiv de manevra Echipament de manevr a crei deschidere (comandat de un sistem de protecie adecvat) asigur separarea unei celule ntregi a Utilizatorului de la reea. 3.13 Dispozitiv General al Utilizatorului (DG) Echipament de manevr i separare al crui deschidere (comandat de un Sistemul de Protecie Generala) asigur separarea ntregii instalaii a Utilizatorului de la reea. 3.14 Distribuitor Orice persoana care deine, sub orice titlu, o retea electric de distribuie i este titular a unei licene de distribuie prin care rspunde de operarea, asigurarea ntreinerii i, dac este necesar, dezvoltarea reelei de distribuie ntr-o anumit zon i, acolo unde este aplicabil, interconectarea acestuia cu alte sisteme, precum i de asigurarea capacitii pe termen lung a sistemului de a raspunde cererilor rezonabile privind distribuia energiei electrice. (Legea energiei electrice nr. 13/2007 cu modificrile i completrile ulterioare) 3.15 Exploatare Ansamblul de operaii (manevre) executate pentru asigurarea adaptrii continue la cerere a producerii, transportului, distribuirii i furnizrii de energie electric n condiii corespunztoare tehnico-economice i de siguran. (Ordinul 35/2002 Regulament de conducere i organizare a activitii de mentenan) Toate activitile care cuprind lucrrile necesare pentru a permite funcionarea instalaiei electrice. Aceste activiti cuprind domenii precum comutaia, comanda, controlul i ntreinerea precum i activitatea electric i neelectric. (SR EN 50110/1) 3.16 Sarcin de energie electric Cererea de energie electric pe care sistemul electric naional trebuie s o satisfac; prezint o evoluie n timp variabil, n cursul zilei, al lunii i al anului. 3.17 Flicker Impresia de jen vizual produs de o surs luminoas a crei luminozitate sau distribuie spectral variaz n timp datorit variaiei tensiunii de alimentare. Caracterizat i normat prin severitatea fliker-ului pe termen scurt (Pst), msurat pe o perioad de 10 minute cu aparate specializate, respectiv pe termen lung (Plt) calculat pe o perioad de dou ore (12 intervale de 10 minute). (Ord 28/2007 - Standard de performan pentru serviciul de distribuie a energiei electrice) 3.18 Funcionarea reelei n condiii excepionale Condiii de funcionare a reelei, aprute n funcionarea SEN care necesit reducerea consumului de energie electric pe zone de reea sau la nivelul SEN. 3.19 Funcionarea reelei n condiii normale de funcionare Condiii de funcionare a reelei, care permit realizarea acoperirii sarcinii, a generrii, a manevrelor n reea i eliminarea defectelor de ctre sistemul automat de protecie n absena unor condiii excepionale, determinate de influene exterioare sau de evenimente majore. (SR EN 50160) 3.20 Funcionare insularizat Funcionare stabil a unei pri de reea dup insularizare. Insularizare - msur de urgena care const n fracionarea reelei n subreele, fiecare dintre acestea pstrnd echilibrul ntre producere i sarcin pentru a funciona separat. (SR CEI 60050 603)

13

3.21 Gestionarul reelei electrice de transport (RET - Transelectrica) Orice persoan care deine, sub orice titlu, o reea electric de transport i este titular a unei licene de transport prin care rspunde de operarea, asigurarea ntreinerii i dac este necesar, dezvoltarea reelei de transport ntr-o anumit zon i, acolo unde este aplicabil, interconectarea acesteia cu alte sisteme electroenergetice, precum i de asigurarea capacitii pe termen lung a sistemului de a acoperii cererile rezonabile pentru transportul energiei electrice. (Legea energiei electrice nr. 13/2007 cu modificrile i completrile ulterioare) 3.22 Factor de nesimetrie a tensiunii ntr-o reea trifazat, exprim gradul de nesimetrie, fiind definit prin raportul (n procente) ntre valorile efective ale componentelor de secven invers sau homopolar i componenta de secven direct a tensiunii. (SR CEI 60050 - 604) 3.23 Grup generator Ansamblu de masini rotative care permit transformarea energiei mecanice sau termice n energie electric. (SR CEI 60050 602) 3.24 Instalaie de producere Ansamblul mainilor, circuitelor, serviciilor auxiliare, echipamentelor i eventualelor sarcini pentru generarea energiei electrice. 3.25 Instalaie de autoproducere n accepia prezentei Norme, instalaia de autoproducere este o instalaie special de producere. 3.26 Instalaie de cogenerare n accepia prezentei Norme, instalaia de cogenerare este o instalaie special de producere combinat a energiei electrice i termice. (Ordinul 35/2004 Codul tehnic RET revizia 1 Ordinul 20/2004) 3.27 Instalaie de utilizare (sau de Utilizator) Instalaie electric a utilizatorului n aval de punctul/punctele de delimitare. n cazul mai multor puncte de delimitare se consider o singur instalaie de utilizare, numai dac instalaiile din aval aferente fiecrui punct de delimitare sunt legate electric ntre ele prin reele ale Utilizatorului prin excepie, sursele de iluminat public sau alte sacini distribuite, de acelai tip i ale aceluiai Utilizator, racordate la un circuit de joas tensiune din postul de transformare sau dintr-o cutie de distribuie, se pot considera o singur instalaie de utilizare. (HG 90/2008 Regulament privind racordarea utilizatorilor la reelele electrice de interes public) 3.28 Instalaie Consumator Ansamblul mainilor, circuitelor, echipamentelor destinate utilizrii energiei electrice. 3.31 Instalaie de racordare Instalaia electric realizat ntre punctul de racordare la reeaua electric de interes public i punctul de delimitare dintre instalaiile ENEL i instalaiile Utilizatorului. Instalaia de racordare cuprinde i grupul de msurare a energiei electrice, inclusiv n cazurile de excepie, cand punctul de msurare este diferit de punctul de delimitare (vezi Fig. 16). (HG 90/2008 Regulament privind racordarea utilizatorilor la reelele electrice de interes public) 3.33 ntreruperea alimentrii Situaie n care tensiunea n punctul de racordare este mai mic dect 1% din tensiunea declarat (contractual) n punctul de delimitare. ntreruperea este definit ca fiind: ntrerupere lung dac are o durat mai mare de 3 min, ntrerupere scurt dac are o durat mai mare de 1 s i 3 min., ntrerupere tranzitorie daca durata este de maxim 1 s.

14

3.34 Limite admisibile pentru perturbaiile provocate de receptoarele Utilizatorului Limita maxim de emisie de perturbaii n reea, permis Utilizatorului racordat la acea reea. 3.35 Nivel de compatibilitate Nivelul unei perturbaii electromagnetice specificate, utilizat ca nivel de referin pentru coordonare, la stabilirea limitelor de emisie i de imunitate. (SR 60050 -161) 3.36 Nivel de emisie Nivelul unei perturbaii electromagnetice date, emis de un anumit dispozitiv, aparat sau sistem. (SR 60050 -161) 3.37 Nivel de emisie transferat Limita maxim a valorii de perturbaie electromagnetic ce se poate transfera la o reea cu un anumit nivel de tensiune din reele cu alte niveluri de tensiune. 3.38 Planificarea operaional a RED Activitate constnd n planificarea de ctre ENEL, pe diferite orizonturi de timp (anual, semestrial, lunar) a schemei normale de funcionare a RED din autoritatea sa de decizie, a schemei de funcionare pe diferite orizonturi de timp (lunar, anual, etc) cu respectarea standardului de performan pentru distribuia energiei electrice. Utilizatorii RED trebuie s furnizeze la solicitarea ENEL, date tehnice necesare pentru planificarea dezvoltrii i conducerea prin dispecer, n conformitate cu prevederile din Codul Tehnic RED. (Codul tehnic RED - Ord 128/2008) 3.39 Puterea maxim posibil a unei uniti (a unei centrale) Puterea electric maxim realizabil ntr-o unitate (centrala) n regim continuu, avnd toate componentele n stare de funcionare. (SR CEI 60050 602) 3.40 Puterea aprobat a unei uniti (a unei centrale) Puterea activa (aparenta) maxima sau simultana pe care utilizatorul o poate absorbi sau evacua prin instalaia de racordare la reeaua electric pentru care se emite avizul tehnic de racordare.

Se consemneaz n avizul tehnic de racordare i este luata in considerare la dimensionarea instalaiei de racordare a utilizatorului respectiv (HG 90/2008 Regulamentprivind racordarea utilizatorilor la reelele electrice de interes public) 3.41 Puterea cerut de reea Putere care trebuie furnizat reelei pentru acoperirea consumului. 3.42 Puterea nominal Puterea aparent maxim la care un generator sau un transformator pot funciona cu continuitate n condiii specificate. 3.43 Programarea operaional a funcionrii RED Activitate care permite programarea pe un orizont de timp (anual, semestrial, lunar) de ctre ENEL a schemei de funcionare a RED din autoritatea sa de decizie i a modului de echilibrare producere-consum, cu respectarea parametrilor tehnici de calitate i siguran. (terminologie ANRE) 3.44 Limita de proprietate Punct ntre reea i instalaia Utilizatorului pentru racordare, unde are loc separarea proprietii ntre Enel i Utilizator. 3.45 Punct de delimitare Locul n care instalaiile Utilizatorului se delimiteaz ca proprietate de instalaiile operatorului de reea (vezi Fig. 16 pentru T i Fig. 19 pentru MT). (HG 90/2008 Regulament privind racordarea utilizatorilor la reelele electrice de interes public)

15

3.46 Punct de racordare (la RED) Punctul fizic din reeaua electric la care se racordeaz un Utilizator (vezi Fig.16). (HG 90/2008 Regulament privind racordarea utilizatorilor la reelele electrice de interes public) 3.47 Variaia tensiunii Cretere sau descreterea tensiunii, determinat n mod normal, de variaia sarcinii. (SR EN 50160) 3.48 Variaia rapid de tensiune Variaie singular rapid a valorii efective a tensiunii, ntre dou niveluri consecutive, care au rmas stabile pentru un interval de timp definit, dar nespecificat (de exemplu 200 ms). (SR EN 50160) 3.49 Reea (reea de distribuie, reea de distribuie public) Reea electric de distribuie: reea electric cu tensiunea de linie nominal pn la 110 kV inclusiv. Reea electric de interes public: reea electric la care sunt racordai cel puin doi utilizatori. (Codul tehnic al RED - Ord 128/2008) 3.50 Reea de nalt Tensiune (T) Sistem cu tensiune nominal de 110 kV inclusiv (niveluri de tensiune superioare nu sunt tratate n Norma de fa). (Ord 28/2007 - Standard de performan pentru serviciul de distribuie a energiei electrice) 3.51 Reea Foarte nalt Tensiune (FT) Sistem cu tensiunea nominal ntre faze peste 110 kV. 3.52 Reea Joas Tensiune (JT) Sistem cu tensiunea avnd valoarea efectiv nominal cel mult egal cu 1 kV. (SR EN 50160) 3.53 Reea n insul Poriunea din reeaua electric neconectat la restul reelei electrice de distribuie publica. 3.54 Reea MT Sistem cu tensiunea avnd valoarea efectiv nominal peste 1 kV i mai mic de 110 kV. (SR EN 50160) 3.55 Reea planificat Structurarea reelei de distribuie dup cum rezult din activitatea de planificare definit la 3.38. 3.56 Refuz de sarcin Stare de funcionare a unui grup de generare, care, dup o decuplare de la reea datorat evenimentelor externe, continu s alimenteze propriile servicii auxiliare, astfel nct s poat efectua n cel mai scurt timp cu putin reintrarea n paralel cu reeaua. 3.57 Reanclanare automat rapid Reanclanare automat unipolar sau tripolar a unui ntreruptor care are loc dup un interval de timp de ordinul secundelor dup o declanare ca urmare a unui defect. (SR CEI 60050 604) 3.58 Servicii auxiliare de reea Ansamblul de echipamente auxiliare specifice unitii care sunt indispensabile funcionrii acesteia (ex. Mori, pompe de circulaie, ventilatoare). (SR CEI 60050-602)

16

3.59 Servicii auxiliare generale Ansamblu de echipamente auxiliare comune pentru grupul generator i pentru ntreaga central. (SR CEI 60050-602) 3.60 Serviciul de reglare a frecvenei Aciune de meninere a frecvenei la 50 Hz prin echilibrul ntre puterea debitat n reea, puterea absorbit i pierderi. 3.61 Serviciul de reglare al tensiunii Aciune de meninere a tensiunilor n nodurile reelei n limite specificate. 3.62 Sistem de Protecie General (SPG) Sistem de protecie asociat Dispozitivului General, compus din: traductoare de curent (i, dac sunt prevzui, traductoare de tensiune) cu conectrile aferente la relee de protecie; relee de protecie cu alimentarea aferent; circuite de declanare a ntreruptorului2.

3.63 Staie electric Parte a unui sistem electroenergetic, situat pe un anumit amplasament i care conine, n principal, extremitiile liniilor de transport sau de distribuie, echipamentul electric de comutaie i de comand, cldiri i transformatoare. O staie conine, n general, dispozitive de protecie i de comand ale reelei (de ex. Proteciile prin relee). (SR CEI 60050 -601) 3.64 Serviciul de ntrerupere a sarcinii (DAS) Serviciul furnizat de unitile de consum dispecerizabile, racordate la reea, cu obligaia de racordare ale terilor, echipate n fiecare punct individual de absorbie, cu echipamente de deconectare a sarcinii conforme specificaiilor tehnice definite de ctre Transelectrica i n care se pot dispune decuplri de sarcin prin modalitile definite de ctre Transelectrica nsui. 3.65 Sistem cu neutrul legat direct la pmnt Sistem n care, n caz de contact direct la pmnt a unei faze, tensiunea la pmnt a fazelor neafectate, excluznd perioada tranzitorie, nu depete n nici un punct 80% din tensiunea nominal ntre faze. 3.66 Tensiune armonic Tensiune sinusoidal a crei frecven este egal cu un multiplu ntreg al frecvenei fundamentale a tensiunii de alimentare. Tensiunile armonice pot fi evaluate: individual prin amplitudinea lor relativ (Ub) raportat la tensiunea fundamental U1 n care b este rangul armonicei. global, de exemplu, prin factorul total de distorsiune THD, calculat pe baza urmtoarei relaii:

unde ub este raportul dintre amplitudinea componentei armonice i amplitudinea componentei fundamentale.

2

n accepia prezentei Norme, SPG nu include DG. Una sau mai multe funcii ale SPG pot fi ndeplinite de un dispozitiv unic (SPG integrat).

17

3.67 Tensiune de exploatare declarat (tensiune declarat) Tensiunea de exploatare declarat este n mod normal tensiunea nominal a sistemului Un. Dac, printr-un acord ntre Distribuitor i Utilizator, se furnizeaz n punctul de delimitare o tensiune diferit de cea nominal atunci tensiunea de exploatare declarat este aceast tensiune stabilit prin acord. 3.68 Utilizatorul reelei Utilizator de retea electrica: productor, operator de transport i de sistem, operator de distribuie, furnizor, consumator de energie electrica, racordai la o reea electrica. (Cod Tehnic RED Ord ANRE 128/2008) 3.69 Consumator (de energie electrica) Persoana fizic sau juridic ce cumpr energie electric pentru consumul propriu i eventual, pentru un subconsumator racordat la instalaiile sale. (Codul tehnic al RET revizia 1 Ordinul 20/2004) 3.70 Consumator nedispecerizabil Toi consumatorii care nu intr n definiia Consumatorilor dispecerizabili. 3.71 Consumator dispecerizabil Consumator care, n concordan cu cerinele contractuale, i reduce sarcina sau este ntrerupt fie prin aciunea direct a Transelectrica, fie prin aciunea Consumatorului, la cererea Transelectrica. (Ordinul 35/2004 Codul tehnic RET revizia 1 Ordinul 20/2004) Uniti de consum ale cror programe de consum sunt relevante, innd cont de sarcina acestora i de limitele de capacitate de transport, n vederea previzionrii de ctre Transelectrica a necesarului de resurse pentru dispecerizare. 3.72 Grup electric (generator) Ansamblu de echipamente (de regul rotative) destinat producerii de energie electric prin transformarea unei alte forme de energie. (Codul tehnic al RED - Ord 128/2008) Ansamblu de instalaii electrice, pentru producerea de energie electric, racordate la reele de distribuie i prin intermediul liniilor directe sau reelelor interne de utilizare astfel nct debitrile de energie electric corespunztoare unui ansamblu s fie msurabile n mod autonom. Unitile reversibile de generare i absorbie sunt considerate uniti de producere. 3.73 Grup dispecerizabil Grupul generator care poate fi programat pe piaa angro i a crui putere se incadreaz n urmtoarele categorii: Grupuri generatoare hidroelectrice cu putere mai mare de 10 MW; Grupuri generatoare termoelectrice cu putere mai mare de 20 MW; (Codul tehnic al RED - Ord 128/2008).

Uniti de producere cu puterea global a grupurilor de generare asociate mai mare de 10 MW 3.74 Grup nedispecerizabil Toate Unitile de producere care nu intr n definiia 3.73.

18

Partea 2 Caracteristici ale Utilizatorilor, ale reelelor, ale criteriilor pentru alegerea nivelului de tensiune i ale schemelor de racordare la reelele T i MT 4 Caracteristici ale Utilizatorilor i clasificarea acestora Utilizatorii racordai direct la reeaua de distribuie T i MT sunt subieci care exploateaz: instalaii de producere; instalaii de utilizare; reele interne de utilizare, dup definiiile ANRE; reele de distribuie (n cadrul consolidrii i interconectarii ntre reele de distribuie).

n accepia regulilor tehnice de racordare, n mod special paragrafele 7 i 8, Utilizatorii reelei de distribuie se clasific n: Utilizatori activi (Productori). Din aceast categorie de Utilizatori fac parte instalaiile care conin orice main (rotativ sau static) care convertete orice form de energie util n energie electric n curent alternativ prevzut pentru a funciona n paralel (i tranzitoriu) cu reeaua. Utilizatori pasivi (Consumatori). Din aceast categorie fac parte toate instalaiile care nu intr n definiia precedent.

-

4.1 Instalaia de utilizare n accepia prezentei Norme, instalaiile Utilizatorilor pot fi caracterizate dup urmtoarele criterii: putere; sensibilitatea echipamentelor a sarcinilor la calitatea alimentrii; perturbaii emise n reea; continuitate in alimentare.

-

Aceste criterii, care nu sunt limitative, au scopul de a caracteriza, n manier simplificat, instalaiile de utilizare n raport cu cerinele lor minime i cu factorii care le influeneaz. 4.1.1 Sensibilitatea echipamentelor n functie de parametrii de calitate a energiei electrice Instalaiile Utilizatorilor pot fi mprite n funcie de sensibilitatea privind continuitatea serviciului n urmtoarele dou categorii: aparate insensibile; aparate sensibile.

Aparatele pot fi sensibile n functie de parametrii de calitate a energiei electrice (ntreruperi ale alimentrii) i la diferitele caracteristici ale tensiunii, cum sunt: - goluri de tensiune; variaii de tensiune; supratensiuni; variaii de frecven; armonici; nesimetrie a tensiunii .

O list a aparatelor sensibile este prezentat n Tab.1. Aceasta nu este exhaustiva.

19

Tabelul 1 Echipamente sensibile FENOMEN CONSIDERAT Goluri de tensiune: V 30% VN (a) t 60 100 ms ECHIPAMENT SENSIBIL Aparate electronice digitale de control de proces sau maini de calcul n general Acionri cu vitez variabil (electronic de putere) n plus fa de ceea cele de mai sus cderea dispozitivelor electromecanice (relee auxiliare, teleruptori) Motoare i maini electrice Bobine de contoare Becuri cu incandescen Instalaii de iluminat Aceleai aparate de la (a) i (b) Componente electronice att de control ct i de putere Supratensiuni de impuls Motoare, cabluri i maini electrice n general Linii transmisie date i semnale la un nivel de putere sczut Aparate electronice de control Condensatori Releu de protecie Receptoare industriale de puteri mici. Motoare i maini rotative Transformatoare Cabluri electrice Nesimetrii i dezechilibre Motoare electrice i maini rotative n general Deteriorare a circuitelor electronice Proast funcionare a sistemelor de control i de elaborare a datelor Supranclzire i deteriorare condensatori Actionari intempestive ale releului de protecie Proast funcionare a sistemelor de control i de transmisie a datelor Creterea pierderilor la motoare, transformatoare i cabluri i implicit supranclzirea acestora Supranclzire CONSECINE Opriri i/sau anomalii ale proceselor/mainilor Intervenii ale proteciilor electronicii de putere Oprire global a tuturor utilitilor Scurtarea duratei de via a izolaiei n caz de reducere, ncetinire sau oprire a motoarelor electrice: aceleai consecine ca la (a) i (b) Strapungerea izolatiei

Goluri de tensiune: V 30% VN t 60 100 ms (b) Supratensiuni de lung durat Variaii lente de tensiune V = 10% VN

Tranzitorii de comutare (puni convertoare, tehnici chopper)

Armonici

4.1.2 Aparate perturbatoare Aparate pot fi mprite n funcie de perturbaiile emise n reea n urmtoarele categorii: - sarcini neperturbatoare; - sarcini distorsionante (sarcini neliniare printre care acionarea cu viteze variabile, becuri, convertoare statice, aparate electrocasnice, cuptoare cu arc, aparate de sudur, transformatoare, motoare, etc.); - sarcini fluctuante (aparate de sudur, motoare de capacitate mare pornite direct n mod repetat n timp, racordarea transformatoarelor, etc.). O list ne exhaustiv a aparatelor perturbatoare este prezentat n Tab.2.

20

Tabelul 2 Aparate perturbatoare APARATE PERTURBRI GENERATE SQ FT VT AR FS RE nclzire cu rezisten Cuptoare casnice - Microunde - infraroii Cuptoare industriale - cu inducie - HF - UHF - Plasm - arc Aparate de sudur - cu rezisten - cu arc Motoare - asincrone (ex. pentru compresoare) - cu viteze variabil Transformatoare Convertori - c.a./c.c. - c.a./c.a. i ciclu- convertoare Electroeroziune Becuri cu descrcare Televizoare Radiologie (1) (1) (1) (2) (3)

(3)

Legenda SQ = nedisimetrii i dezechilibre FT = fluctuaii de tensiune (flicker) VT = variaii de tensiune AR = armonici FS = frecvene anormale RE = radioemisie (1) monofazate (2) la conectare, cnd puterea echipamentului nu este mai mic n raport cu cea de scurtcircuit a reelei (3) cu control electronic

Toate sarcinile prezente in instalaia Utilizatorului, dac sunt perturbatoare, trebuie s respecte Normele CEI care reglementeaz perturbaiile conduse i induse n reeaua la care acestea sunt legate, n scopul de a nu cauza degradarea calitii serviciului reelei. Perturbaiile maxime care pot fi emise n reea sunt alocate de ctre ENEL innd cont de marjele disponibile n zona de reea interesat i privesc: variaii de tensiune (lente i rapide); fluctuaii de tensiune (flicker); armonici; dezechilibru al fazelor.

Pentru definirea acestor mrimi, referina este Norma SR EN 50160. Pentru criteriile de evaluare, un punct efectiv de referin tehnic (chiar dac nu exhaustiv pentru toate

fenomenele menionate mai sus) este reprezentat de rapoartele tehnice CEI TR 61000-

21

3-6 pentru armonici, CEI TR 61000-3-73 pentru fenomenele de flicker i variaii rapide i CEI TR 61000-3-13 pentru dezechilibre. 4.1.3 Utilizatori ntreruptibili Se numesc Utilizatori ntreruptibili acei Utilizatori care la solicitarea furnizorului i diminueaz puterea absorbit sau accept deconectarea contra unei compensaii/reduceri tarifare stabilite de comun acord cu furnizorul. (HG 1007/2004 Regulament de furnizare a energiei electrice la consumatori) Instalaie de comand i achiziie de date (Arhitectura de control) prevede c Utilizatorul ntreruptibil trebuie s se doteze cu o legtur pentru transmisia de date ntre propriul sediu industrial i Transelectrica, n general cel mai apropiat. n plus, n sediul industrial este instalat o main de teleoperaiuni, denumit Unitate Periferic de Decuplare Sarcini (UPDC) care achiziioneaz msura sarcinii deservite n timp real i pe aceea a ntregului sediu industrial, precum i alte informaii auxiliare i pune n practic comanda de deconectare la ordinul provenit din slile de comand ale Transelectrica. 4.2 Instalaii de producere n sensul prezentei Norme, instalaiile de producere a energiei sunt clasificate numai n raport cu puterea i perturbaiile emise n reea. 4.2.1 Puterea Puterea efectiv a instalaiilor de producere influeneaz alegerea nivelului de tensiune al racordrii la reelele de distribuie. 4.2.2 Instalaii de producere perturbatoare Instalaiile de producere pot fi catalogate n funcie de perturbaiile emise n reea n urmtoarele categorii: instalaii neperturbtoare; instalaii conectate prin dispozitive distorsionante (de exemplu instalaii conectate prin convertori statici); instalaii cu producere fluctuant.

O lista nelimitativa a instalaiilor de producere perturbtoare este prezentat n Tab.3. Tabelul 3 Instalaii de producere perturbatoare INSTALAII DE PRODUCERE Instalaii eoliene conectate prin: generatoare asincrone generatoare asincrone cu dubl alimentare generator sincron + convertor static c.a./c.a. Instalaii conectate prin generatoare asincrone Instalaii conectate prin convertori: - c.c./c.a. - c.a./c.c. c.c./c.a.Legenda SQ = Dezechilibre FT = Fluctuaii de tensiune (flicker) VT = variaii de tensiune AR = armonici FS = frecvene anormale RE = radioemisie

PERTURBAII GENERATE SQ FT VT AR FS RE

3

Pentru variaiile rapide, este n studiu o metod pentru evaluarea acestora bazat pe compararea ntre puterea de scurtcircuit n nodul de racordare i puterea disponibil la Utilizator. Anexa F conine cteva valori informative extrase din acest studiu.

22

Reele de distribuie Utilizatorii, n cazul retelelor interconectate pot fi proprietari de: staii de transformare racordate la reele T ale altui Distribuitor; poriuni de reea de distribuie MT ENEL racordate la reele de distribuie MT ale distribuitorilor sau alti proprietari ; poriuni de reea de distribuie T ENEL racordate la reele de distribuie T ale altor distribuitori sau alti proprietari.

4.4

23

5 Caracteristicile reelelor n continuare se descriu caracteristicile principale ale reelelor de distribuie; aceste caracteristici trebuie s fie luate n considerare la racordarea Utilizatorilor la reea. 5.1 Caracteristicile reelelor de T

5.1.1 Caracteristici structurale 5.1.1.1 Niveluri de tensiune i frecven Reeaua T este constituit din seciuni cu tensiune nominal (Un) mai mare de 35 kV i mai mic sau egal cu tensiunea de110 kV la o frecven nominal (fn) de 50 Hz. 5.1.1.2 Starea neutrului Reelele de T cu tensiune nominal (Un) 110 kV au neutrul legat efectiv la pmnt. Reelele de T cu tensiuni nominale mai mici pot fi exploatate cu diferite stri ale neutrului. 5.1.1.3 Curent de scurtcircuit trifazat maxim n scopul dimensionrii echipamentelor Valoarea curentului de scurtcircuit care se ia n calcul la alegerea echipamentelor trebuie s fie comunicat de ctre ENEL Consumatorului. 5.1.1.4 Curent de scurtcircuit monofazat maxim n scopul dimensionrii prizei de pmnt Valoarea curentului de scurtcircuit monofazat care se ia n calcul la dimensionarea prizei de pmnt trebuie s fie comunicat de ctre ENEL Consumatorului. 5.1.1.5 Curent de scurtcircuit trifazat maxim n punctul de racordare Valoarea maxim a curentului de scurtcircuit trifazat simetric n punctul de racordare comunicat de ENEL la cererea Utilizatorului. Aceast valoare trebuie s fie calculat conform Normei SR EN 60909-0, n schema normal de functionare a reelei i cu generare maxim. 5.1.1.6 Curent de scurtcircuit trifazat minim n punctul de racordare Valoarea minim a curentului de scurtcircuit trifazat simetric n punctul de racordare comunicat de ENEL la cererea Utilizatorului. Aceast valoare trebuie s fie calculat conform Normei SR EN 60909-0, n structura normal de exploatare a reelei i cu generare minim. 5.1.1.7 Curent de scurtcircuit trifazat minim convenional n punctul de racordare Valoarea minim convenional a curentului de scurtcircuit trifazat simetric n punctul de racordare trebuie s fie comunicat de ctre ENEL la cererea Utilizatorului. Aceast valoare trebuie s fie calculat conform Normei SR EN 60909-0, n structura de reea N-1 (care prevede indisponibilitatea componentei sistemului electric linie, generator, transformator de interconectare - care are influena major asupra valorilor totale ale curenilor de scurtcircuit n punctul examinat) i cu generare minim. Deci calculul curenilor i puterilor de scurtcircuit minime se efectueaz n condiiile normale de exploatare, considernd a fi n funciune numai o parte din parcul de generare disponibil (situaie de generare minim n gol de sarcina) i presupunnd sursa de tensiune echivalent n punctul de scurtcircuit egal cu 100% din tensiunea nominal. n plus, calculul nodurilor individuale ale reelei trebuie efectuat ulterior cu ipoteza c o component a sistemului electric nu este disponibil. n cazul n care instalaia examinat este exploatat n anten calculul curentului i puterii de scurtcircuit minim n nod se efectueaz raportnd regula de mai sus la primul nod de alimentare n amonte care dispune de cel puin dou legturi active cu restul reelei.

24

5.1.1.8 Curent de defect monofazat n punctul de racordare i timpul de eliminare a defectului Valoarea curentului de defect monofazat (dup cum este definit n 5.1.1.4) i timpul de eliminare a defectului trebuie s fie comunicate de ctre ENEL Utilizatorului cu ocazia cererii de racordare i de fiecare dat cand survin modificari, dup cum este detaliat n 7.5.5. Valorile maxime ale curenilor de defect monofazat trebuie s fie calculate conform Normei SR EN 60909-0 i, mpreun cu timpul de eliminare a defectului, permit dimensionarea i verificarea eficacitii prizelor de pmnt, n conformitate cu prevederile Normei SR HD 637 S1. Timpul de eliminare a curentului de defect la pmnt trebuie s fie calculat n conformitate cu prevederile Normei SR HD 637 S1. Priza de pmnt a Utilizatorului, n funcie de schema de racordare adoptata, trebuie s fie dimensionat astfel nct curentul de defect de punere la pmnt de mai sus s nu creeze tensiuni de atingere i de pas mai mari dect valorile admisibile precizate n Norma SR HD 637 S1, corelate cu timpul de eliminare a defectului (Anexa L). 5.1.1.9 Nivel de inere al izolaiei Nivelurile minime de inere ale izolaiei aplicate n instalaia Utilizatorului pentru racordare trebuie s fie comunicate de ctre ENEL i trebuie s fie conforme cu prevederile Normelor SR EN 60071-1 i SR EN 60071-2. 5.1.2 Caracteristici de exploatare 5.1.2.1 Funcionarea reelei Nivelurile de tensiune ale reelelor de T sunt determinate de structura si de exploatarea RET, n funcie de prezena staiilor FT/T i a unitilor de generare, precum i de reglementrile cu privire la aceste uniti i staii. Aadar aceste valori sunt determinate de ctre Transelectrica i reproduse ntr-un document corespunztor care este actualizat periodic. n acest document sunt redate nivelurile minime i maxime ale valorii tensiunii efective n urmtoarele condiii n care se poate afla exploatarea sistemului electric: pentru 95% din timp n condiii de exploatare normale; pentru 100% din timp n condiiile de exploatare normale sau de defect; n condiii de urgen sau de restabilire.

-

Pentru punctele de racordare individuale, ENEL trebuie s comunice Utilizatorului valoarea medie a valorii efective a tensiunii (tensiune declarat) i a domeniului de variaie aferent, precum i valoarea frecvenei cu domeniul de variaie aferent. Frecvena de exploatare a reelei n condiii normale este de 50 Hz ( 1%). n funcionarea reelei n condiii de urgen sau de restabilire (insul) valorile de frecven pot varia n domeniul 50 Hz +4/ - 6%. 5.1.2.2 Eliminarea defectelor Sistemul de protecie al reelei este structurat i coordonat astfel nct s opereze eliminarea selectiv a defectului n timpi corelati cu timpii proprii echipamentelor de manevr i ai sistemelor de protecie conform nivelului tehnologic actual. n acest caz, proteciile adoptate de ENEL nu au scopul de a proteja instalaiile Utilizatorului; prin urmare protecia acestor instalaii este exclusiv n grija Utilizatorului.

25

n plus, dup cum este evideniat de Norma SR EN 637 S1, releele de protecie ale reelelor de T (protecii de distana, protecii difereniale de linie, protecii maximale de curent, etc.) plasate de-a lungul circuitelor electrice nu au rolul s asigure protecia mpotriva atingerilor directe. n general, aceste protectii care realizeaz ntreruperea automat a circuitelor nu sunt adecvate pentru protecia contra atingerilor directe. 5.1.2.3 Automatizari de reea Reeaua poate fi dotat cu automatizari cum sunt: reanclanri rapide uni/tripolare i/sau reanclanri temporizate tripolare, cu eventual control al paralelismului/sincronismului; automatizarea secvenelor de manevr; sisteme de teledeclansare (att a sarcinii ct i a grupurilor generatoare); descrcarea de sarcin (DASU,DASF).

Controlul suprasarcinii este de regul gestionat n diferite faze de exploatare n timp real a reelei. 5.1.3 Calitatea serviciului Calitatea serviciului poate fi definit n relaie cu: continuitatea serviciului; calitatea tensiunii.

Prin continuitatea serviciului se nelege respectarea parametrilor privind ntreruperea programata sau neprogramata a furnizrii energiei electrice, iar prin calitatea tensiunii se intelege respectarea parametrilor privind caracteristicile tensiunii ca de exemplu frecvena, amplitudinea i forma de und. Calitatea serviciului este msurat prin indicatori care se bazeaz pe prezena, amplitudinea i frecvena tensiunii n reelele Utilizatorilor. 5.1.3.1 Continuitatea serviciului Intreruperile neprogramate care trebuie verificate se disting n : - intreruperile lungi (durata > 3 min) - intreruperi scurte (1s < durata > 3 min) - intreruperi tranzitorii (durata 1 s) 5.1.3.2 Calitatea tensiunii Caracteristicile tensiunii care pot fi luate n consideraie sunt urmtoarele: frecvena ; amplitudinea i variaia tensiunii la frecvena de reea; goluri de tensiune; variaii rapide ale tensiunii; supratensiuni; tensiuni armonice; flicker; dezechilibru de tensiune.

n scopul evitrii daunelor in instalaiile proprii, cauzate de distorsiunile armonice sau nesimetriile prezente n reea, Utilizatorul cnd este necesar, are datoria de a adopta msuri adecvate (de exemplu s instaleze protecii suplimentare) care s separe propria instalaie de reea la depirea limitelor setate de Utilizator. Intervenia acestor protecii, n cazul

26

Productorilor, trebuie s fie stabilit de comun acord cu ENEL (i/sau Transelectrica pentru uniti de producere dispecerizabile). 5.1.4 Supravegherea reelelor de distribuie ENEL garanteaz funcionarea reelelor, n limitele capacitatilor reelelor respective. ENEL este responsabil de supravegherea reelelor, de mentenana acestora i de sigurana persoanelor n limitele stabilite de legile i normele tehnice n vigoare. Supravegherea reelelor de distribuie include supervizarea strii instalaiilor, executarea manevrelor i asistena tehnic de urgen. Manevrele (n regim normal de exploatare, de urgen i de asigurare a conditiilor de securitate) sunt executate, n mod automat i manual, prin sisteme de telecontrol sau prin asisten la faa locului a instalaiilor i sunt concordate ntre ENEL i Transelectrica. Pentru necesitile de exploatare ale reelelor de distribuie, criteriile pe baza crora se executa manevrele de conectare i deconectare ale instalaiilor de producere cu putere mai mic de 10 MW i ale instalaiilor de utilizare racordate direct la reelele de distribuie de T sunt stabilite ntre ENEL i Utilizator, n timp ce pentru instalaiile de producere cu putere mai mare de 10 MW ENEL treb