    MTM 17-33 kW UNIVERSAL OIL-FIRED HEATER

    OPERATING MANUAL

    --

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    2/11

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    3/11

    6. Design of the controller

    Fig. l.Block diagram of the controller of MTM17-33 universal oil-fired heater.

    Designations:

    T40 bimetallic sensor of furnace temperature

    T100 bimetallic safety sensor ( STB )

    OVF overflow safety device

    MP pump

    MW fan

    KB keyboard

    D1 furnace overheating indicator

    D2 overflow tank overfilling indicator

    D3 furnace on/off indicator

    7. Installation of the heater

    Familiarize with applicable local regulations. Position the furnace on a flat concrete base.

    Level the heater. In order to check whether the heater is levelled, place the furnace pan in the lower part

    of the combustion chamber and pour a small amount of diesel oil on it.

    The oil should spread accurately in the middle of the pan.

    Mount the draught stabiliser on the pipe coming out from the combustion chamber in order to ensure

    stable draught inside the pipe during the heater operation.

    In order to ensure the optimal draught, install a vertical chimney pipe ( not made of aluminium) which is

    at least 6 meters long, smooth and resistant to high temperature.

    Check leakproofness of all connections, seal them with insulation tape if necessary.

    Make sure that the combustion pan is located centrally in the combustion chamber.

    Place the deflector inside the combustion chamber (the edging in the middle of the deflector should bedirected upward) and mount an afterburner cylinder on it.

    Check the mains voltage (220-240V/50Hz) and connect the furnace to power supply, neither the fan nor

    the pump should start automatically as the furnace has not been switched on yet and no heat has been

    produced.

    CONTROLLER

    MODULE

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    4/11

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    5/11

    8. Description of the heater operation

    Control panel

    The controller of MTM 17-33 universal oil-fired furnace is equipped with an adjusting knob and two push-

    buttons which enable the user to control the heater operation and with three diodes which signal operating

    statuses of the heater.

    Fig.3. View of the front panel of the control module of the universal oil-fired heater.

    The following states characterize the heater operation:

    Stop the heater is ready for start-up

    Firing up initial stage of the heater operation

    Operation proper operation of the heater

    Extinguishing switching the heater off

    Overheating emergency switch-off

    Tank overflow emergency switch-off

    The heat generation process involves combustion of gas which is produced by oil heated to a high

    temperature. The heater connected to the mains is in the readiness state (Stop) and no heat is produced,

    neither the fan nor the pump is operating. When Startpush-button is pressed, the green diode lights up and thefurnace goes to the firing upphase. After the furnace is heated to the temperature of 40C, the contacts of the

    thermostat placed next to the combustion chamber are closed and the oil supply pump and the air supply fan

    are switched on. Due to smaller oil demand of unheated furnace, the heater will operate at the lowest power

    level for at least 30 minutes. During this period the pump supplies approximately 1.7 litre of oil to the furnace.

    After thirty minutes of operation, the power of the heater can be regulated using the power adjustment

    knob located on the controller's panel. During operation of the heater at the highest power level, about 3.3 litre

    of oil is supplied to the furnace.

    The heater is switched off by pressing Stop push-button on the control panel.

    The heater is switched off at the moment of pressing the push-button. The exhaust fan operates until the

    furnace temperature is lower than 35 C (Extinguishing). When a temperature lower than 35C is reached, the

    furnace returns to Stop phase.

    The furnace may be switched off automatically in the following cases:

    - overheating of the combustion chamber

    - overflow

    Furnace overheating

    indicator (STB thermostat)

    Overflow indicator of

    overflow pan

    Furnace operation

    indicator

    Furnace breaker switchFurnace power

    adjustment

    Furnace switch-

    key

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    6/11

    The overheatingsignal is generated by the bimetallic sensor located near the fan. Opening of the contacts

    signals that the threshold temperature is exceeded. The control system switches off the pump (the pump

    operation indicator (green diode) is extinguished); the overheating status is signalled by the red diode which

    lights up on the control panel. The exhaust fan operates until the furnace temperature drops below 35C. When

    a temperature lower than 35C is reached, the furnace returns toStop phase.

    After switching to Stopphase (and even after switching off and then again switching on the power supply)

    the overheating signal is still on. This enables the user to determine the cause of switching off the furnace.

    In order to clear the overheating signal and return to normal operation, wait until the furnace is cooled

    down (the fan is switched off) and press the push-button placed on the bimetallic sensor housing. Then, press

    Startpush-button. The diode which signals overheating will extinguish. The furnace may be restarted.

    The overflowsignal is generated by the mechanical sensor placed under the overflow tank. The opening of

    the contacts signals overfilling of the tank. At the same time, the pump is switched off. The pump operation

    indicator (green diode) extinguishes and the relevant red diode lights up in order to indicate overfilling. The

    exhaust fan operates until the furnace temperature drops below 35C. After reaching a temperature lower than

    35C, the furnace returns to Stopphase. Empty the overflow tank and press Start push-button. The diode which

    signals overflowing (red diode) will extinguish. The furnace may be restarted.

    Fig.4. Arrangement of the heaters protections:1. Thermostat on the combustion chamber

    2. Protection against overheating

    3. Overflow protection

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    7/11

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    8/11

    DO NOT!!! disconnect the heater from the mains when the fan is in operation! Wait until the furnace is cooled

    down. The furnace is switched off automatically. Remember that after the heater is switched off, the pan

    made of cast iron still maintains a higher temperature for some time (depending on ambient temperature)

    and the furnace must not be fired up again until the pan is completely cooled down!

    DO NOT!!! throw the hot pan into snow and do not pour cold water on it in order to accelerate cooling down.

    Otherwise, due to a large temperature difference, the hot pan will break and become useless!!!

    Fig.5. Design of the heater

    1.

    Combustion chamber base

    2.

    Deflector

    3.

    Combustion chamber

    4. Cylinder

    5.

    Fuel tank6. Pump and controller

    7.

    Oil supply conduit

    8.

    Furnace chamber cover

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    9/11

    Fig.6. Combustion chamber

    Maintenance

    The heater requires little maintenance activities. The observance of manufacturers recommendations

    concerning maintenance will ensure failure-free and safe operation of the heater:

    - clean the furnace pan and other elements of the combustion chamber (cylinder, deflector and cover)

    daily,

    - confirm that the overflow tube is not blocked (the tube in the lower part of the combustion chamber,

    directly over the overflow pan), clean it if necessary,

    - clean the combustion chamber base (the element under the furnace pan) at least once a week,

    - confirm that the air inlet openings in the bottom and the top part of the combustion chamber are not

    covered,

    - at least once a week, clean the conduit supplying oil onto the furnace pan, the maximum time of

    operation without cleaning the furnace pan is about 7-14 hours (depending on type of oil used for

    combustion),

    - during the heating season, clean the fuel tank and the oil pump filter,

    - if the furnace is to be out of operation for a longer period of time, thoroughly clean the combustion

    chamber and the daily tank and protect them against corrosion by coating them with a thin film of oil.

    PERIODICAL MAINTENANCE SURVEYS ARE RECOMMENDED TO BE PERFORMED BY AN

    AUTHORIZED SERVICE

    CHAMBER COVER

    CYLINDER

    DEFLECTOR

    RING

    CHAMBER JACKET

    OVERFLOW TUBE

    FURNACE PAN

    CHAMBER BASE

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    10/11

    10. Troubleshooting

    In case of failure of the heater, the below list may help in identifying the failure. Usually, the defect can be

    rectified easily. The most frequent causes of failures are enumerated below. The digits signify possible causes of

    failures. The order of the digits indicates probability of failure occurrence.

    ATTENTION:Before starting any activities, pull the plug out of the mains socket.

    DEFECT CAUSE

    The pump does not start and the pump operation indicator lamp does not light up 6-3-7

    The flame is put off and the pump is still in operation 2-5-9-10-12

    The combustion chamber emits rumbling noise. 10-11-12

    There is soot in the combustion chamber and in the chimney. 8-9-10-11-12

    Unburnt oil remains on the combustion plate. 8-9-11-12 or there is too

    much diesel oil at the start-up.

    No. CAUSE REMEDY

    1Lack of power supply Check whether the plug is in the socket and check

    the fuses

    2 Water or deposit in the tank Clean the tank and the filter

    3 The pump motor cannot be switched on Check the STB and the overflow protection

    4

    The motor and the pump do not work Fuel is too dense or too cold. Dissolve it with diesel

    oil

    Check the pump operation control thermostat and

    replace it if necessary.

    Check the motor and see whether the pump is not

    dirty inside.

    Check the STB and the overflow protection

    5The fuel conduit is blocked; oil returns to the

    tank through the return conduit

    Clean the fuel conduit or replace it, if necessary

    6The pump operation control thermostat has not

    reached the right temperature

    Wait until the furnace cools down and restart it

    Replace the thermostat

    7 Overflow protection is full Clean

    8The safety thermostat (STB) does not operate

    correctly or does not operate at all

    Reset the thermostat

    Replace it

    9 Insufficient combustion air inflow

    Clean the openings of the furnace chamber Check proper operation of the fan

    10

    Improper draught Check whether the chimney pipe is installed in

    accordance with the instructions entitled

    Installation of the chimney pipe

    Check leakproofness of the chimney system

    Clean it, if necessary

    11Chimney draught is too strong or too variable Install the chimney draught stabiliser and adjust it

    to minimum 2 mm W.C. (19.6Pa).

    12

    Chimney draught is too weak Check all the connections

    Decrease the number of bends

    Extend the chimney

    Insulate the chimney pipe outside the building

    See all the information regarding the flue contained

    in the manual.

  • 8/9/2019 Generator Aer Cald Pe Ulei Uzat Functionare Prin Vaporizare MTM 17 33 KW 1000 m3 h Fisa Tehnica

    11/11

    LIST OF PARTS OF MTM 1733 HEATER

    1733.001FAN

    1733.002AIR SUPPLY FLAP

    1733.003MAINS CONDUIT WITH A PLUG

    1733.004COMBUSTION CHAMBER HOUSING

    1733.005CONTROL THERMOSTAT SHIELD1733.006COMBUSTION CHAMBER MADE OF STAINLESS STEEL

    1733.007CONTROLLER PANEL

    1733.008CONTROLLER HOUSING

    1733.009CONTROL THERMOSTAT

    1733.010MOTOR HOUSING

    1733.011FUEL FILLER CAP

    1733.012FUEL FILLER FILTER

    1733.013FUEL PUMP MOTOR

    1733.014FUEL PUMP BRACKET

    1733.015FUEL TANK DRAIN VALVE

    1733.016

    FUEL TANK WITHOUT COVER AND DRAIN VALVE1733.017FEED PIPE TEE (FEED PIPE + RETURN PIPE + PIPE TEE)

    1733.018FUEL PUMP DRIVE SHAFT

    1733.019FUEL PUMP

    1733.020FUEL PUMP FILTER

    1733.021FEED PIPE WITH PIPE UNION

    1733.022HEATER BASE (LEGS + TANK GUIDES + SCREWS)

    1733.023DEFLECTOR OF TANK HOUSING

    1733.024TANK SHIELD

    1733.025COMBUSTION CHAMBER BASE

    1733.026OVERFLOW PROTECTION

    1733.027

    COMBUSTION CHAMBER PAN MADE OF CAST IRON1733.028TANK HOUSING

    1733.029OVERFLOW MICROSWITCH

    1733.030COMBUSTION CHAMBER RING

    1733.031COMBUSTION CHAMBER DEFLECTOR MADE OF CAST IRON

    1733.032STAINLESS COMBUSTION CHAMBER CYLINDER

    1733.033STAINLESS COMBUSTION CHAMBER COVER

    1733.034CHIMNEY DRAUGHT REGULATOR

    1733.035BACK COVER OF COMBUSTION CHAMBER

    1733.036FAN HOUSING

    1733.037FAN SHIELD

    1733.038

    STB THERMOSTAT1733.039STB THERMOSTAT SHIELD

    1733.040ELECTRONIC PLATE OF CONTROLLER

    1733.041PADDLE FOR COMBUSTION CHAMBER CLEANING

    1733.042SMALL CULVERT

    1733.043LARGE CULVERT

    1733.044FIRE-RESISTANT CONDUCTOR 5X1 LENGTH 2.6M

    1733.045 - FIRE-RESISTANT CONDUCTOR 3X1 LENGTH 1.2M

    1733.046 - FIRE-RESISTANT CONDUCTOR 3X1 LENGTH 0.9M

    1733.047SUPPLY FUEL CONDUIT MADE OF RUBBER

    1733.048OVERFLOW FUEL CONDUIT MADE OF RUBBER

    1733.049RUBBER FUEL CONDUIT OF PUMP FILTER