Capitolul 1.Descrierea elementelor de constructiePentru nivelul P avem aria anvelopei:[m2]

Pentru nivelul E1 avem aria anvelopei:[m2]

Pentru terasa si placa pe sol avem aria: [m2]

Se determina rezistentele pentru fiecare element din anvelopa:Perete exterior TIP 6Nr.

Materialdc

(m)(W/m,0C)(J/kg,0C)(kg/m3)

1Int. tencuial ipsos0,020,378401000

2Crmid tip 10,290,78701550

3Polistiren tip 10,050,044146020

4Ext. tencuial ciment0,020,938401800

[m2K/W] [m2K/W]

Teras cu strat termoizolant pe beton de pant structur i caracteristici(Tipul 3)

Nr.Materialdc

(m)(W/m,0C)(J/kg,0C)(kg/m3)

1Pietri0,040,79202000

2Hidroizolaie bituminoas0,010,178401050

3apa din mortar de ciment0,0250,9310001700

4Polistiren extrudat0,160,044146020

5Beton de panta(10-16cm)0,11,628402400

6Placa beton armat(8-14cm)0,11,748402500

[m2K/W] [m2K/W]

Placa peste solNr.Materialdc

(m)(W/m,0C)(J/kg,0C)(kg/m3)

1Sapa din ciment0,050,9310001700

2Strat termoizolant0,170,044146020

3Hidroizolatie0,020,178401050

4Placa din beton armat0,61,748402500

5Pietris0,10,79202000

[m2K/W] [m2K/W]

Capitolul 2Parametrii de calcul ai aerului exterior si interiorConfortul termic al unei incaperi este conditionat direct de catre parametrii climatici interiori. Scopul instalatiilor de ventilare si climatizare este de a asigura valorile parametrilor climatici cerute de catre beneficiari. Astfel, parametrii care vor fi reglati cu ajutorul instalatiilor de climatizare si ventilare sunt: temperatura interioara, umiditatea relativa si viteza curentilor de aer.2.1.Parametrii aerului exterior varaIn functie de localitate, avem pentru orasul Bucuresti: [C]em temperatura exterioar medie a lunii iulie, corespunztoare localitii n care este amplasat cldirea i gradului de asigurareAz amplitudinea oscilaiei zilnice a temperaturii exterioare[C] -temperatura exterioara de calcul vara (cf I5) -umiditarea relativa exterioara de calcul vara -continutul de vapori de apa al aerului umed exterior vara

In functie de si se citesc din diagrama h-x valorile pentru si : [%]-continutul de vapori de apa al aerului umed exterior vara [kJ/kg aer uscat]-entalpia aerului umed exterior varaIntensitatea radiaiei solare

Intensitatea radiaiei solare are o influen deosebit asupra aporturilor de cldur din exterior.

Valorile intensitii solare directe ID, difuze Id i globale I, se gsesc n tabelul de mai jos

TABEL VALORILE INTENSITII RADIAIEI SOLARE DIRECTE DIFUZE I GLOBALE N LUNA IULIE PENTRU DIFERITE ORIENTRI

LunaOrientareaOra zileiIDm,Idm

6789101112131415161718

Id5380103123136146147146136123103805359

23 IulieNordSuprafaaVerticalID533---------3535

a1a2ID453---------3454

I9883103123136146147146136123103839863

ESTEstID383568575498338144-------105

a1a2ID326483489423287122-------89

I3795635925464232681471461361231038053148

SudID--4115931635439435431615941--89

a1a2ID--3513526930133530126913535--76

I53801382584054474054474052581388053135

VestID-------144338498575568383105

a1a2ID-------12228742348848332589

I5380103123136146147268423546591563379148

Viteza vntuluiViteza vntului intereseaz pentru stabilirea poziiei relative dintre priza de aer proaspt i coul de evacuare n exterior a aerului viciat sau pentru amplasarea n zon a obiectivelor cu degajri mai importante de nociviti.Viteza vntului influeneaz schimbul de cldur convectiv cu exteriorul .

2.2.Parametrii aerului interior vara [C] [C] -temperatura interioara de calcul vara [C] -umiditatea relativa a aerului interior [C]

Din diagrama - se citeste valoarea lui dupa formula: si se rotunjeste: 50 [%]Din diagrama h-x se citesc in functie de si valorile pentru: [kJ/kg aer uscat]-entalpia aerului umed interior vara [g/kg aer uscat]-continutul de vapori de apa al aerului umed interior varaUmiditatea relativ a aerului servete, mpreun cu temperatura aerului interior la reprezentarea punctului de stare al aerului interior i are o influen deosebit asupra cofortului. Se mai pot calcula aporturile de cldur i degajrile de la unele surse interioare, se traseaz procesul complex de tratare i se dimensioneaz elementele agregatului de climatizare.

Viteza aerului interior, vi Viteza de micare a aerului interior accept valori care n corelaie cu temperatura aerului interior i starea de effort fizic elimin senzaia de curent constituind ipoteza principal pentru stabilirea vitezei n dispozitivele de introducere a aerului, deci implicit a determinrii suprafeelor lor.Pentru instalaiile de confort viteza aerului interior este cuprins ntre limitele:vi=0,20,3 m/svi=0,25 m/s

Temperatura medie de radiaie a suprafeelor delimitatoare, m

Este strns legat de gradul de vitrare i de izolare termic a elementelor de delimitare la exterior. O valoare mai apropiat de temperatura aerului interior, posibil prin reducerea gradului de vitrare la strictul necesar i o izolare termic ct mai bun duce la micorarea debitului de aer necesar pentru ventilare, deci la reducerea cheltuielilor de investiie i exploatare.

2.3.Parametrii aerului exterior iarnaDeoarece orasul Bucuresti se gaseste in zona climatica II , temperatura exterioara de calcul si continutul de vapori de apa al aerului umed vor avea valorile:

[C] -temperatura exterioara de calcul iarna [g/kg aer uscat]-continutul de vapori de apa al aerului umed exterior iarna

Din diagrama h-x se citesc in functie de si valorile pentru: [kJ/kg aer uscat]-entalpia aerului umed exterior iarna80 [%]-umiditarea relativa exterioara de calcul iarna

VntulVntul prezint o importan deosebit iarna. Viteza acestuia influieneaz direct necesarul de cldur pentru nclzirea aerului infiltrat, lundu-se n calcul conform STAS 1907-90 i la coeficientul superficial de schimb de cldur la exterior: e=23W/m2K.2.4.Parametrii aerului interior iarnaPentru valoarea temperaturii interioare iarna, se alege o valoare in intervalul:[C] Deoarece este vorba de o cladire de birouri, valoarea temperaturii interioare se alege de: [C] Umiditatea relativa a aerului umed este :50 [%] Din diagrama h-x , in functie de si se citesc valorile pentru: [kJ/kg aer uscat]-entalpia aerului umed interior iarna [g/kg aer uscat]-continutul de vapori de apa al aerului umed interior iarna

Viteza aerului interiorSe va adopta ca i n situaia de var: vi=0,25 m/s

Temperatura medie de radiaie a suprafeelor delimitatoare, m

Structura elementelor de delimitare a incintei, mai ales spre exterior, trebuie astfel aleas nct valoarea temperaturii medii de radiaie s se ncadreze n limitele de confort (n corelaie cu ti).VaraIarna

Parametriithxthx

Interiori2551105020397,550

Exteriori35.36812.535-15-130,880

Capitolul 3Determinarea necesarului de caldura de calcul pentru incaperile incalziteConform STAS 1907 se va realiza calculul necesarului de caldura pentru fiecare incapere utilizand formula: [W] -necesarul de caldura al incaperii T fluxul termic cedat prin transmisie corespunzator diferentei de temperatura dintre interiorul si exteriorul elementelor care delimiteaza incaperea i sarcina termica pentru incalzirea aerului rece patruns in interiorA- suma adaosurilorDeoarece aerul introdus in cladire va fi tratat in centrala de tratare a aerului, se va considera valoarea sarcinii termice pentru incalzirea aerului rece patruns in interior egala cu 0.[W]4.1.Fluxul termic cedat prin transmisie TFluxul termic cedat prin transmisie reprezinta suma pierderilor de caldura care au loc atat prin elementele de constructie care sunt in contact cu aerul pe ambele fete, cat si prin sol. [W] e pierderi de caldura prin elemente de constructie in contact pe ambele fete cu aerul s pierderi de caldura in sol [W]CM coeficient de corectie a fluxului termic [-]m coeficientul de masivitate termica al elementelor de constructie exterioare [-]A aria suprafetei fiecarui element de constructie [m2]i temperatura interioara conventionala de calcul [oC]e temperarura spatiilor exterioare incaperii considerate [oC]Ros rezistenta termica a elementului de constructie considerat [m2K/W]Pentru elementele de constructie lipsite de inertie termica (usi, ferestre) valoarea pentru coeficientul de masivitate termica se va considera: m=1,2 [-]Pentru elementele interioare de constructie (plansee, pereti interiori), coeficientul de masivitate termica va avea valoarea m=1 [-].Pentru peretii exteriori coeficientul de masivitate termica se va calcula in functie de indicele de inertie termica cu formula: [-]D indice de inertie termica [-] [-]Rs rezistenta termica a unui strat al elementului de anvelopas24 coeficient de asimilare termica pentru perioada oscilatiilor densitatii fluxului termic de 24 ore [W/m2K]

Indicele de inertie termica pentru pereti exteriori tip 6 [W/mK] [W/mK] [W/mK] [W/mK] [-] [-]Se determina coeficientul de masivitate termica: [-] [-]Indicele de inertie termica pentru terasa tip 3 [W/m2K] [W/m2K] [W/m2K] [W/m2K] [W/m2K] [W/m2K] [-] [-]Se determina coeficientul de masivitate termica: [-] [-]

Indicele de inertie termica pentru placa peste sol [W/m2K] [W/m2K] [W/m2K] [W/m2K] [W/m2K] [-] [-]Se determina coeficientul de masivitate termica: [-] [-]Etaj 2

Birou 1

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PereteS23,082,6135310,6923-5St0,94

FeS5,252,3512,33750,681,235762,0221

Planseu724,0618847,05880421,50,94

Rm

1919,773 7,68 1804

4,98

Birou 2

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PereteV22,452,6135302,21150St0,94

FeV3,122,357,3320,681,235452,85880

PE cortinaV63,219,20,771,2351185,8820228,160,94

PE cortinaN5,83,218,560,771,2351012,3645

PES12,492,06135567,7273-5

FES2,52,355,8750,681,235119,7816

Planseu954,0618187,1921Rm

3828,017 2,09 3678

7,22

Birou 3

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaV4,23,213,440,771,235733,09090St0,94

PE cortinaN3,143,210,0480,771,235548,07275

Planseu644,0618664,93510231,90,94

1946,099 4,17 1932

5,64

Birou 4

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaE5,223,224,410,771,2351331,4550St0,94

PEV30,1332,6135405,63650

FEV1,942,67510,3790,681,235167,66080422,60,94

FEN5,83,218,560,681,2351146,3535

PEN19,811,761351019,6325

PE cortinaS2,693,28,6080,771,235205,4182

Planseu1464,0618287,6847Rm

4563,84 3,24 4765

6,08

Birou 5

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaE2,833,29,0560,771,235493,96360St0,94

PE cortinaN3,063,29,7920,771,235534,10915

Planseu83,54,0618867,53250282,40,94

Rm

1895,605 5,21 1877

5,34

Birou 6

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaV2,833,29,0560,771,235493,96360St0,94

Planseu264,061851,231530115,20,94

Rm

545,1952 7,39 538

5,01

Birou 7

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaV5,23,216,640,771,235907,63640St0,94

Planseu254,061849,261080112,70,94

Rm

956,8974 4,12 950

5,66

Birou 8

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEE2,472,724,410,681,2351507,6760St0,94

FEE2,592,713,9860,681,235863,84120

PEE10,272,6135528,60290429,70,94

FEN2,572,68520,701350,681,235334,40645Rm

PEN19,782,61351018,0885 3,03

PE cortinaS33,29,60,771,235523,6364-5

Planseu964,0618189,16260

4965,4144724

6,22

Birou 9

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PereteE9,332,6135125,59620St0,94

FeE2,472,76,6690,681,235411,90880

Planseu184,0618211,7647089,60,94

Rm

749,2697 4,18 709

5,63

Birou 11

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FENE1,932,6855,182050,681,235320,06785St0,94

PENE9,72,6135130,57695

Planseu654,0618128,07880308,90,94

Rm

578,7235 18,68 596

4,56

Birou 12

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,22,6855,9070,681,235364,84415St0,94

PEN5,672,613576,326925

Planseu244,061847,290640109,90,94

Rm

488,4617 7,87 505

4,96

Birou 13

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,432,6856,524550,681,235402,98695St0,94

PEN10,692,6135143,90385

Planseu314,061861,083740132,70,94

Rm

607,9745 7,64 629

4,98

Birou 14

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,422,6856,49770,681,235401,32855St0,94

PEN6,142,613582,653855

Planseu254,061849,261080114,60,94

Rm

533,2435 7,52 551

4,99

Birou 15

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,422,6856,49770,681,235401,32855St0,94

PEN5,952,613580,096155

Planseu24,54,061848,275860113,80,94

Rm

529,7005 7,52 548

4,99

Birou 16

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,212,6855,933850,681,235366,50255St0,94

PEN6,222,613583,730775

Planseu24,54,061848,275860113,20,94

Rm

498,5091 7,95 515

4,95

Birou 17

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FENV1,842,6854,94040,681,235305,14245St0,94

PENV12,082,6135162,61545

Planseu304,061859,11330167,40,94

Rm

526,871 11,12 544

4,75

Birou 18

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEV2,462,6856,60510,681,235407,96210St0,94

PEV9,362,61351260

Planseu18,54,061836,45320161,10,94

Rm

570,4153 9,88 562

4,81

Birou 19

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

PE cortinaE4,773,215,2640,771,235832,58180St0,94

PEE13,593,228,2242,6135379,93850

FEV2,552,6856,846750,681,235422,88750

FEV2,462,6856,60510,681,235407,96210

PEV11,732,6135603,750740,40,94

FEN2,552,67540,92750,681,235661,13655

PEN47,12,61352424,2655

FES2,62,356,110,681,23598,7-5

FES6,62,3515,510,681,235957,9706-5

PES13,462,6135181,1923-5

Planseu2744,0618539,9015Rm

7130,347 3,63 6760

5,86

Birou 20

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FE S3,92,359,1650,681,235566,0735-5St0,94

PES6,872,613592,480770

Planseu554,0618108,37440207,20,94

Rm

766,9287 9,45 720

4,84

Birou 22

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FE E2,72,356,3450,681,235391,89710St0,94

PEE8,112,6135109,17310

Planseu254,061849,261080113,40,94

Rm

550,3312 7,21 543

5,03

Birou 23

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FE E3,82,358,930,681,235551,55880St0,94

PEE15,592,6135209,86540

Planseu384,061874,876850153,80,94

Rm

836,3011 6,44 826

5,12

Birou 24

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FE E2,62,356,110,681,235377,38240St0,94

PEE10,282,6135138,38460

Planseu314,061861,083740133,00,94

Rm

576,8507 8,07 569

4,94

Birou 25

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FENV5,32,3512,4550,681,235769,27945St0,94

PENV13,482,6135181,46155

FEV4,22,359,870,681,235609,61760

PEV4,562,613561,384620400,60,94

Planseu784,0618153,6946Rm

1775,438 7,90 1752

4,96

Birou 26

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN3,232,357,59050,681,235468,8250St0,94

PEN3,72,613549,807690

Planseu31,54,061862,068970125,40,94

Rm

580,7017 7,56 573

4,99

Birou 27

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN3,252,357,63750,681,235471,72790St0,94

PEN4,422,613559,50

Planseu264,061851,231530116,10,94

Rm

582,4595 6,98 575

5,05

Birou 28

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN4,552,3510,69250,681,235660,41910St0,94

PEN4,982,613567,038460

Planseu344,061866,995070139,40,94

Rm

794,4527 6,14 785

5,17

Birou 29

elementorientarel[m]h[m]S[mp]R'[mpk/W]mt[K]Qt[W]AoAcCmQ[W]

FEN2,62,356,110,681,235377,38240St0,94

PEN5,732,613577,134620

Planseu244,061847,29064067,90,94

Rm

501,8076 4,74 497

5,46

CAPITOLUL 4CALCULUL BILANULUI TERMIC DE VAR

Instalaia de climatizare este conceput pentru a menine n interior o anumit temperatur i umiditate relativ constant.Pentru aceasta este nevoie s se determine sarcina termic i de umiditate vara.Sarcina termic de var,denumit i sarcina de rcire,reprezint fluxul maxim de cldur ce trebuie evacuat din ncpere.Ca rezultat al acestui bilan, rezult sarcina termic de var, care n modul cel mai general se poate scrie astfel :QV=Qap+QdegQap= reprezint aporturile de cldur din exterior prin elementele ineriale, vitrate i de la ncperile vecine,n W;Qdeg= reprezint degajrile de cldur de la sursele interioare (oameni,iluminat),n W;Qap= QFE+QPE+Qi [W] QFE= reprezint fluxul termic ptruns din exterior prin elementele neineriale(ferestre),n W;QPE= reprezint fluxul termic ptruns din exterior prin elementele ineriale(perei,acoperiuri),n W;Qi= reprezint fluxul termic ptruns prin elementele de delimitare interioar de la ncperile vecine,n W.

3.1 Aporturi de cldur din exterior i de la ncperile vecine3.1.1. Aporturi de cldur prin ferestre :Pentru calculul fluxului termic ptruns prin ferestrele ncperii se precizeaz: -dimensiunile ferestrei: 1.94x2.67; 2.55x2.68; 2.47x2.70; 2.59x2.70; 2.59x2.70; 2.20x2.685; 2.43x2.685; 1.84x2.685; 2.50x2.28; 6.50x2.28; 3.80x2.28; 2.70x2.28; 3.80x2.28; 2.60x2.28; 5.30x2.28 [m]; -tipul ferestrei: fereastr dubl cu ram cu un geam termoizolant i un geam obinuit la o distan de 2-4 cm;:coeficient m pentru ferestre protejate la interior -pereti cortina- coeficient m pentru ferestre neprotejate sau protejate la exterior Fluxul termic se calculeaz cu relaia:QFE= QI+QT [W] QI= ct*f*m*(c p*Si*ID+S*Idmax) [W] QT= SSF*kFE*(te-ti) [W] Unde :QI= este fluxul termic cauzat de radiaia direct i difuz,n W;QT= fluxul termic datorat diferenei de temperatur dintre exterior i interior,n W;ct= coeficient functie de tipul tamplariei (pentru ferestre cu rama de aluminiu), ct=1.15f= factor solar, depinde de calitatea geamului si a ecranarii ferestrei;Pentru ferestre: f= 0.35Pentru pereti cortina f=0.58m= coeficient de acumulare termica, care depinde de tipul elementului de modul de ecranare al ferestrei, de orientare, de ora de calcul si masivitatea elementului de constructie. Coeficientul mediu de asimilare termica al cladirii are in cazul de fata valoarea cuprinsa in intervalul 4,5-10,5 [W/m2K]

.!!!!!!!!!! ANEXA PT PCcp =0,94 pentru climat impur-coeficient de puritateSi= suprafaa nsorit a ferestrei, care se calculeaz cu relaia:Si=(H-hu)*(B-bu) [m2]B,H= limea respectiv nlimea ferestrei, n [m]bu,hu= limea respectiv nlimea umbrei n planul ferestrei,n [m]:bu=c1* 1 [m]hu=c2* 2[m]1, 2= retragerile ferestrelor in raport cu planul fatadei;c1,c2= coeficienti de umbrire pentru detereminarea suprafetelor, functie de orientarea ferestrei ANEXAS= suprafaa total a ferestrei,n [m2];Uf= coeficient global de transfer de caldura al ferestrei, functie de coeficentul de emisie e( 60% x puterea totala instalata12 16 -> 40% x puterea totala instalata16 18 -> 60% x puterea totala instalata18 20 -> 80% x puterea totala instalata

Astfel, vom avea urmatoarele valori ale degajarii de caldura de la sursele de lumina:Birou u 891011121314151617181920

1518,4518,4518,4518,4518,4345,6345,6345,6345,6518,4518,4691,2691,2

2684684684684684456456456456684684912912

3460,8460,8460,8460,8460,8307,2307,2307,2307,2460,8460,8614,4614,4

41051,21051,21051,21051,21051,2700,8700,8700,8700,81051,21051,21401,61401,6

5601,2601,2601,2601,2601,2400,8400,8400,8400,8601,2601,2801,6801,6

6187,2187,2187,2187,2187,2124,8124,8124,8124,8187,2187,2249,6249,6

7180180180180180120120120120180180240240

8121,32121,32121,32121,32121,3280,8880,8880,8880,88121,32121,32161,76161,76

9123,48123,48123,48123,48123,4882,3282,3282,3282,32123,48123,48164,64164,64

11468468468468468312312312312468468624624

12172,8172,8172,8172,8172,8115,2115,2115,2115,2172,8172,8230,4230,4

13468468468468468312312312312468468624624

14172,8172,8172,8172,8172,8115,2115,2115,2115,2172,8172,8230,4230,4

15223,2223,2223,2223,2223,2148,8148,8148,8148,8223,2223,2297,6297,6

16180180180180180120120120120180180240240

17176,4176,4176,4176,4176,4117,6117,6117,6117,6176,4176,4235,2235,2

18176,4176,4176,4176,4176,4117,6117,6117,6117,6176,4176,4235,2235,2

19216216216216216144144144144216216288288

20133,2133,2133,2133,2133,288,888,888,888,8133,2133,2177,6177,6

22180180180180180120120120120180180240240

23396396396396396264264264264396396528528

24180180180180180120120120120180180240240

25273,6273,6273,6273,6273,6182,4182,4182,4182,4273,6273,6364,8364,8

26223,2223,2223,2223,2223,2148,8148,8148,8148,8223,2223,2297,6297,6

27561,6561,6561,6561,6561,6374,4374,4374,4374,4561,6561,6748,8748,8

28226,8226,8226,8226,8226,8151,2151,2151,2151,2226,8226,8302,4302,4

29187,2187,2187,2187,2187,2124,8124,8124,8124,8187,2187,2249,6249,6

4.3.3.Degajarile echipamentelor de birou parterSe iau in considerare urmatoarele echipamente de birou:2 retroproiectoare1 videoproiector6 plottere158 laptopuri4 copiatoare digitale98 imprimante inkjet5 copiatoare de mare viteza

22.4 [kW]

Degajarea de cldur a echipamentului de birouNr.Tip echipamentDegajarea de cldur maxim

1Calculator100 400 W

2Ploter75 W

3Imprimant de birou cu de jet cerneal50 W

4Copiator de mare vitez300-400 W

5Retroproiector250 W

6Videoproiector200 W

7Laptop90 W

Capitolul 5Calculul sarcinii termice de varaIn urma calculelor, se stabileste sarcina termica de vara pentru fiecare birou. Astfel, sarcina termica de vara, Qv, se va calcula cu formula:Qv=Q ap+ Q deg [KW]Qap- reprezinta suma aporturilor de caldura calculate conform metodoligiei;Q deg-reprezinta suma degajarilor de caldura de la sursele interioare calculate conform metodologiei.Degajarile de caldura de la sursele interioare se vor lua in considerare in conformitate cu orarul de functionare al incaperii. In cazul nostru, avand o cladire cu mai multe incaperi climatizate, sarcina termica de vara a cladirii se se va determina prin insumarea orara a sarcinilor termice rezultate a incaperilor, sarcina de racire a cladirii fiind valoarea maxima rezultata.

Tabel centralizator

Birou 1891011121314151617181920

Q aporturi ferestre Sud603,7133786,55971304,7481555,6491719,1391673,5691452,671880,3272589,5868915,7151844,6235402,5219780,6647

Q aporturi pereti Sud85,43385,43389,127496,5162106,4449118,2208129,9967140,3872148,2378153,5485156,3193157,012155,8575

Q degajari oameni525525525525525525525525525525525525525

Q degajari iluminat518,4518,4518,4518,4518,4345,6345,6345,6345,6518,4518,4691,2691,2

Q degajari eb900900900900900900900900900900900900900

Q aporturi inc. inv106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904106,6904

Q aporturi terasa249,12250,56255,6264,96277,2291,6306,72321,84334,08344,16349,92352,08350,64

TOTAL2988,3573172,6433699,5663967,2154152,8743960,683766,6783219,8452949,1953463,5143400,9533134,5043510,0534152,874

Birou 2891011121314151617181920

Q aporturi ferestre Vest218,3856227,4445239,2951247,8159273,6255336,5603553,2131715,6879800,007808,4009682,5869475,2603439,0687

Q aporturi perete cortina Vest1899,8161809,6381757,3751730,9581868,2682692,9824170,5535297,8565861,3085927,9965069,5973540,5973404,427

Q aporturi perete cortina Nord1261,5031219,9651172,4791179,9391211,8991241,9931207,4621162,91098,2751273,481430,031071,4581005,673

Q aporturi ferestre Sud240,9079337,3843571,4426691,6736774,0048742,1903630,7505365,4169205,815686,5585788,9905348,81065123,1964

Q aporturi pereti Vest97,992594,691793,041393,247694,89899,8492108,5138120,4792134,7139149,5675162,1518169,5786171,8479

Q aporturi pereti Sud10,69310,69311,155412,080213,322914,796816,270717,571218,553819,218519,565319,65219,5075

Q aporturi terasa328,7330,6337,25349,6365,75384,75404,7424,65440,8454,1461,7464,55462,65

Q degajari oameni1425142514251425142514251425142514251425142514251425

Q degajari iluminat684684684684684456456456456684684912912

Q aporturi eb1450145014501450145014501450145014501450145014501450

Q aporturi i. inv26,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,37209

TOTAL7643,3717615,7897767,417890,6878187,148870,49310448,8411461,9311916,8412304,6911499,999603,2789439,74312304,69

Birou 3891011121314151617181920

Q aporturi perete cortina Vest352,7966293,1286270,7046276,4165300,88551819,8542485,0392997,9243382,5393631,3783490,529667,0744560,9773

Q aporturi perete cortina Nord682,9516660,4638634,7557638,7946656,0968672,3894653,6951629,5701594,5834639,6758755,2084580,065544,4508

Q ap terasa221,44222,72227,2235,52246,4259,2272,64286,08296,96305,92311,04312,96311,68

Q degajari oameni450450450450450450450450450450450450450

Q degajari iluminat460,8460,8460,8460,8460,8307,2307,2307,2307,2460,8460,8614,4614,4

Q aporturi eb860860860860860860860860860860860860860

Q aporturi i. inv171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672171,1672

TOTAL3199,1553118,283074,6283092,6983145,354539,8115199,7415701,9416062,4496518,9416498,7443655,6673512,6756518,941

Birou 4 891011121314151617181920

Q aporturi ferestre Vest196,9794151,5073112,879388,648284,24121904,40451410,4841791,2961980,5821994,3641692,63240,1555172,1957

Q aporturi perete cortina Est2182,7322305,3132273,7742018,3541776,0761476,9591224,813980,0843829,296736,6054662,4608614,2806584,6464

Q aporturi fereastra Nord970,6604929,3261877,2736853,654857,068830,0344787,777718,1783642,367814,67691083,687716,6397424,8965

Q aporturi perete cortina Sud374,5493797,86931073,1621328,9171538,811615,691511,3631234,792742,5179273,0896220,7695198,0676192,9668

Q aporturi pereti Vest146,965142,0146139,5394139,8488142,324149,7496162,7444180,6896202,0382224,315243,1884254,3268257,7302

Q aporturi pereti Nord57,261656,683257,454459,382462,6666,901671,721676,541681,168885,79690,230493,50894,8576

Q degajari oameni1125112511251125112511251125112511251125112511251125

Q degajari iluminat1051,21051,21051,21051,21051,2700,8700,8700,8700,81051,21051,21401,61401,6

Q aporturi eb2700270027002700270027002700270027002700270027002700

Q aporturi i. inv26,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,37209

TOTAL8831,7199285,2859436,6549391,3779363,7529595,9129721,0759533,7549030,1429031,4198895,5387369,956980,2659721,075

Birou 5891011121314151617181920

Q aporturi perete cortina Est1216,9731283,0781259,8751102,757363,8042289,0076227,1944169,4027137,5776124,7681122,0127133,3329154,707

Q aporturi perete cortina Nord1334,231290,2971240,0731247,9641281,7661313,5951277,0741229,9421161,5921232,1431292,9121133,2281063,651

Q degajari oameni600600600600600600600600600600600600600

Q degajari iluminat601,2601,2601,2601,2601,2400,8400,8400,8400,8601,2601,2801,6801,6

Q aporturi eb1720172017201720172017201720172017201720172017201720

Q aporturi i. inv192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776192,1776

Q aporturi terasa288,91290,58296,425307,28321,475338,175355,71373,245387,44399,13405,81408,315406,645

TOTAL5953,4915977,3325909,7515771,3785080,4224853,7554772,9564685,5684599,5874869,4194934,1124988,6544938,7815977,332

Birou 6891011121314151617181920

Q aporturi perete cortina Vest254,7286221,7065195,456179,4604187,0679776,09181161,9741459,7421603,9971610,4091363,754401,1669254,1432

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat187,2187,2187,2187,2187,2124,8124,8124,8124,8187,2187,2249,6249,6

Q aporturi eb520520520520520520520520520520520520520

Q aporturi i. inv50,694850,694850,694850,694850,694850,694850,694850,694850,694850,694850,694850,694850,6948

Q aporturi terasa89,9690,4892,395,68100,1105,3110,76116,22120,64124,28126,36127,14126,62

TOTAL1327,5831295,0811270,6511258,0351270,0631801,8872193,2292496,4562645,1322717,5842473,0091573,6021426,0582717,584

Birou 7891011121314151617181920

Q aporturi perete cortina Vest416,8512362,8121319,8544293,6784306,1277563,82621710,792305,0492635,6332710,2782344,912656,4905415,8932

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat180180180180180120120120120180180240240

Q aporturi eb520520520520520520520520520520520520520

Q aporturi i. inv50,1165426,3720948,18898167,986835,1779547,7070937,8765436,6236235,3707151,562248,1889826,3720950,11654

Q aporturi terasa86,58788,759296,25101,25106,5111,75116119,5121,5122,25121,75

TOTAL1478,4681401,1841381,7931478,6651362,5561577,7832720,1673318,4233652,0043806,343439,6011790,1131572,763806,34

Birou 8891011121314151617181920

Q aporturi ferestre Est1271,0221377,2571377,5031235,708430,4138351,7812286,0587223,2705186,3023166,6456154,3248152,2743157,5597

Q aporturi ferestre Est1305,0241397,6091388,9271224,147430,4138351,7812286,0587223,2705186,3023166,6456154,3248152,2743157,5597

Q aporturi ferestre Nord839,8961804,1302759,0901738,6525741,6066718,2149681,6502621,4276555,8294622,1032928,5948620,0963367,6558

Q aporturi pereti cortina Sud482,5814596,2913974,92141156,1251277,2761242,8031083,411677,1974480,6828291,0635278,7566140,0433303,6837

Q aporturi pereti Est52,993257,51262,030866,138868,911771,068472,91774,354875,587276,203476,408875,895374,8683

Q aporturi pereti Nord59,578258,976459,778861,784865,19569,608274,623279,638284,452689,26793,880897,29198,6952

Q degajari oameni900900900900900900900900900900900900900

Q degajari iluminat121,32121,32121,32121,32121,3280,8880,8880,8880,88121,32121,32161,76161,76

Q aporturi eb560560560560560560560560560560560560560

Q aporturi i. inv26,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,37209

Q aporturi terasa332,16334,08340,8353,28369,6388,8408,96429,12445,44458,88466,56469,44467,52

TOTAL5950,9476233,5486570,7436443,5294991,1094761,3094460,9313895,5313581,8493478,53760,5433355,4473275,6756570,743

Birou 9891011121314151617181920

Q aporturi fereastra Est1002,5371058,9381037,368894,1044140,9853104,561175,0170848,4074435,5582733,9908939,7594155,7981979,17287

Q aporturi prin pereti Est48,916853,08857,259261,051263,610865,601667,30868,635269,772870,341670,531270,057269,1092

Q degajari oameni150150150150150150150150150150150150150

Q degajari iluminat123,48123,48123,48123,48123,4882,3282,3282,3282,32123,48123,48164,64164,64

Q aporturi eb380380380380380380380380380380380380380

Q aporturi i. inv48,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,18898

Q aporturi terasa62,2862,6463,966,2469,372,976,6880,4683,5286,0487,4888,0287,66

TOTAL1815,4021876,3351860,1961723,065975,5651903,5717879,5141858,0116849,3601892,0415899,4396956,7044978,7711876,335

Birou 11891011121314151617181920

Q aporturi fereastra Nord-Est703,0242540,9487236,668890,2545172,7287556,6965246,0083734,5345427,6191123,3368124,752531,0805246,17141

Q aporturi prin pereti Nord-Est64,11367,840571,120773,804576,339279,172182,00584,837987,372689,310990,503790,8019171,6313

Q degajari oameni600600600600600600600600600600600600600

Q degajari iluminat468468468468468312312312312468468624624

Q aporturi eb1195119511951195119511951195119511951195119511951195

Q aporturi i. inv167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868167,9868

Q aporturi terasa224,9226,2230,75239,2250,25263,25276,9290,55301,6310,7315,9317,85316,55

TOTAL3423,0243265,9762969,5262834,2462830,3052674,1052679,92684,9092691,5782854,3342862,1433026,7193121,343423,024

Birou 12891011121314151617181920

Q aporturi fereastra Nord349,032344,7842335,2523332,8249338,1948330,3975316,0167290,4611260,9209199,0622291,454273,5729153,2482

Q aporturi prin pereti Nord17,255717,081417,313817,894818,882520,160721,613223,065724,460125,854527,190828,178528,5852

Q degajari oameni150150150150150150150150150150150150150

Q degajari iluminat172,8172,8172,8172,8172,8115,2115,2115,2115,2172,8172,8230,4230,4

Q aporturi eb500500500500500500500500500500500500500

Q aporturi i. inv35,1779535,1779535,1779535,1779535,1779535,1779535,1779535,1779535,1779535,1779535,1779535,1779535,17795

Q aporturi terasa83,0483,5285,288,3292,497,2102,24107,28111,36114,72116,64117,36116,88

TOTAL1307,3061303,3641295,7441297,0181307,4551248,1361240,2481221,1851197,1191197,6151293,2631334,6891214,2911334,689

Birou 13891011121314151617181920

Q aporturi fereastra Nord385,3061380,6233370,1065367,4306373,3611364,7547348,8798320,6679288,0563224,5891323,9868302,0144169,1752

Q aporturi prin pereti Nord28,096227,812428,190829,136830,74532,826235,191237,556239,826642,09744,272845,88146,5432

Q degajari oameni225225225225225225225225225000

Q degajari iluminat468468468468468312312312312468468624624

Q aporturi eb750750750750750750750750750750750750750

Q aporturi i. inv47,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,70709

Q aporturi tereasa107,26107,88110,05114,08119,35125,55132,06138,57143,84148,18150,66151,59150,97

TOTAL2011,3692007,0231999,0542001,3542014,1631857,8381850,8381831,5011806,431680,5731784,6271921,1931788,3962014,163

Birou 14891011121314151617181920

Q aporturi fereastra Nord385,3168380,8537370,5268367,9765373,993365,4262349,5678321,3441288,6843223,5043323,9307302,3518169,1895

Q aporturi prin pereti Nord26,789426,518826,879627,781631,299431,299433,554435,809437,974240,13942,213643,74744,3784

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat172,8172,8172,8172,8172,8115,2115,2115,2115,2172,8172,8230,4230,4

Q aporturi eb750750750750750750750750750750750750750

Q aporturi i. inv37,8765437,8765437,8765437,8765437,8765437,8765437,8765437,8765437,8765437,8765437,8765437,8765437,87654

Q aporturi prin terasa86,58788,759296,25101,25106,5111,75116119,5121,5122,25121,75

TOTAL1684,2831680,0491671,8331673,4351687,2191626,0521617,6991596,981570,7351568,821673,3211711,6251578,5941711,625

Birou 15891011121314151617181920

Q aporturi fereastra Nord385,3168380,8537370,5268367,9765373,993365,4262349,5678321,3441288,6843223,5043323,9307302,3518169,1895

Q aporturi prin pereti Nord26,789426,518826,879627,781629,31531,299433,554435,809437,974240,13942,213643,74744,3784

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat223,2223,2223,2223,2223,2148,8148,8148,8148,8223,2223,2297,6297,6

Q aporturi eb750750750750750750750750750750750750750

Q aporturi i. inv36,6236236,6236236,6236236,6236236,6236236,6236236,6236236,6236236,6236236,6236236,6236236,6236236,62362

Q aporturi prin terasa84,7785,2686,97590,1694,32599,225104,37109,515113,68117,11119,07119,805119,315

TOTAL1731,71727,4561719,2051720,7421732,4571656,3741647,9161627,0921600,7621615,5771720,0381775,1271642,1071775,127

Birou 16891011121314151617181920

Q aporturi fereastra Nord352,031347,9488338,51336,1773341,6722333,8446319,3558293,5704263,733200,0822294,0426276,226154,5738

Q aporturi prin pereti Nord18,829818,639618,893219,527220,60521,999823,584825,169826,691428,21329,671230,74931,1928

Q degajari oameni225225225225225225225225225225225225225

Q aporturi terasa84,7785,2686,97590,1694,32599,225104,37109,515113,68117,11119,07119,805119,315

Q degajari iluminat180180180180180120120120120180180240240

Q aporturi eb750750750750750750750750750750750750750

Q aporturi i. inv35,3707135,3707135,3707135,3707135,3707135,3707135,3707135,3707135,3707135,3707135,3707135,3707135,37071

TOTAL1646,0021642,2191634,7491636,2351646,9731585,441577,6811558,6261534,4751535,7761633,1551677,1511555,4521677,151

Birou 17891011121314151617181920

Q aporturi fereastra Nord-Vest97,5422684,5447165,9943457,3043652,2414548,61439217,274452,0078610,7804708,2066672,043133,0095100,373

Q aporturi prin pereti Nord-Vest61,571759,821659,344360,139862,04964,912868,890374,77782,572991,323499,7557105,1651107,3925

Q aporturi terasa103,8104,4106,5110,4115,5121,5127,8134,1139,2143,4145,8146,7146,1

Q degajari oameni300300300300300300300300300300300300300

Q degajari iluminat176,4176,4176,4176,4176,4117,6117,6117,6117,6176,4176,4235,2235,2

Q aporturi eb635635635635635635635635635635635635635

Q aporturi i. inv51,562251,562251,562251,562251,562251,562251,562251,562251,562251,562251,562251,562251,5622

TOTAL1425,8761411,7291394,8011390,8061392,7531339,1891518,1271765,0471936,7162105,8922080,5611606,6371575,6282105,892

Birou 18891011121314151617181920

Q aporturi fereastra Vest125,367896,4269971,8421656,4202753,61543534,5309847,7311083,8391203,1851212,8631026,324152,8473109,5942

Q aporturi prin pereti Vest45,362543,834543,070543,16643,9346,22250,23355,77262,361569,237575,06378,50179,5515

Q aporturi terasa64,0164,3865,67568,0871,22574,92578,8182,69585,8488,4389,9190,46590,095

Q degajari oameni150150150150150150150150150150150150150

Q degajari iluminat176,4176,4176,4176,4176,4117,6117,6117,6117,6176,4176,4235,2235,2

Q aporturi eb500500500500500500500500500500500500500

Q aporturi i. inv48,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,1889848,18898

TOTAL1109,3291079,231055,1771042,2551043,3591471,4671792,5632038,0952167,1762245,122065,8861255,2021212,632245,12

Birou 19891011121314151617181920

Q aporturi perete cortina Est7974,2528566,8498580,6457747,9591762,6321401,3731102,738823,3772669,2629606,6848592,2956645,3706746,6345

Q aporturi ferestre Vest671,105695,2512728,2744752,2625829,67071136,1921758,2862226,822458,122474,7432103,6081447,514805,2084

Q aporturi ferestre Nord2618,6032507,0932366,6682302,9482312,1592239,2292125,2291937,4681732,9482258,872921,4391933,3181146,266

Q aporturi fereastra Sud1090,2741364,6152230,6842637,6642897,0362835,4542479,491524,21081,0631537,0121419,378677,6158530,0594

Q aporturi pereti Vest57,142555,217754,255354,375655,33858,225263,277870,255278,555987,217594,555898,8866100,2099

Q aporturi pereti Nord100,178199,1662100,5154103,8884109,6225117,0431125,4756133,9081142,0033150,0985157,8564163,5905165,9516

Q aporturi terasa948,04953,52972,71008,321054,91109,71167,241224,781271,361309,721331,641339,861334,38

Q degajari oameni2025202520252025202520252025202520252025202520252025

Q degajari iluminat216216216216216144144144144216216288288

Q aporturi eb2450245024502450245024502450245024502450245024502450

Q aporturi i. inv26,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,37209

TOTAL18176,9718959,0819751,1119324,7913738,7313542,5913467,1112586,1812078,6913141,7213338,1511095,539618,08219751,11

Birou 20891011121314151617181920

Q aporturi fereastra Sud454,2705662,4846860,40221048,0061201,3211268,0241193,739985,3559632,925880,5819695,649571,5478480,9248

Q aporturi pereti Sud31,37631,37632,732835,446439,092843,417647,742451,558454,441656,39257,409657,66457,24

Q degajari oameni450450450450450450450450450450450450450

Q aporturi terasa190,3191,4195,25202,4211,75222,75234,3245,85255,2262,9267,3268,95267,85

Q degajari iluminat133,2133,2133,2133,2133,288,888,888,888,8133,2133,2177,6177,6

Q aporturi eb890890890890890890890890890890890890890

Q aporturi i. inv50,1165450,1165450,1165450,1165450,1165450,1165450,1165450,1165450,1165450,1165450,1165450,1165450,11654

TOTAL2199,2632408,5772611,7022809,1692975,4813013,1082954,6982761,6812421,4832723,192543,6752465,8782373,7313013,108

Birou 22891011121314151617181920

Q aporturi fereastra Est925,4752978,2035959,3988829,5294772,8513645,5145537,915433,0214367,6024325,9796291,1219265,7351247,1133

Q aporturi prin pereti Est50,722855,04859,373263,305265,959368,023669,79371,169272,348872,938673,135272,643771,6607

Q aporturi terasa86,58788,759296,25101,25106,5111,75116119,5121,5122,25121,75

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat180180180180180120120120120180180240240

Q aporturi eb495495495495495495495495495495495495495

Q aporturi i. inv47,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,7070947,70709

TOTAL2010,4052067,9592055,2291932,5421882,7681702,4951601,9151503,6481443,6581466,1251433,4641468,3361448,2312067,959

Birou 23891011121314151617181920

Q aporturi fereastra Est1314,9531393,8441373,91203,841096,433915,7701763,1111614,2933521,4834462,4393412,9982377,0013350,6074

Q aporturi prin pereti Est81,579688,53695,4924101,8164106,0851109,4052112,251114,4644116,3616117,3102117,6264116,8359115,2549

Q degajari oameni300300300300300300300300300300300300300

Q aporturi terasa131,48132,24134,9139,84146,3153,9161,88169,86176,32181,64184,68185,82185,06

Q degajari iluminat396396396396396264264264264396396528528

Q aporturi eb635635635635635635635635635635635635635

Q aporturi i. inv73,2472473,2472473,2472473,2472473,2472473,2472473,2472473,2472473,2472473,2472473,2472473,2472473,24724

TOTAL2932,263018,8683008,542849,7442753,0652451,3232309,4892170,8652086,4122165,6372119,5522215,9042187,173018,868

Birou 24891011121314151617181920

Q aporturi fereastra Est890,9403941,3577922,6612796,3583744,1802621,5717517,9672416,9675353,9757313,895280,3263255,8745237,9346

Q aporturi prin pereti Est56,605261,43266,258870,646873,608775,912477,88779,422880,739281,397481,616881,068379,9713

Q aporturi terasa107,26107,88110,05114,08119,35125,55132,06138,57143,84148,18150,66151,59150,97

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat180180180180180120120120120180180240240

Q aporturi eb520520520520520520520520520520520520520

Q aporturi i. inv61,1036261,1036261,1036261,1036261,1036261,1036261,1036261,1036261,1036261,1036261,1036261,1036261,10362

TOTAL2040,9092096,7732085,0741967,1891923,2431749,1381654,0181561,0641504,6581529,5761498,7071534,6361514,982096,773

Birou 25891011121314151617181920

Q aporturi fereastra Nord-Vest 530,6784609,4264619,5668653,6256678,1032687,6844689,14351158,2491511,781723,5111618,4351186,472739,718

Q aporturi fereastra Vest527,3036551,0062581,3021602,9646666,2276876,65631384,5141764,0291954,0881970,1231674,6561153,971638,4449

Q aporturi prin pereti Nord-Vest64,474262,641662,141862,974864,97467,972872,137878,30286,465495,6284104,4582110,1226112,455

Q aporturi terasa269,88271,44276,9287,04300,3315,9332,28348,66361,92372,84379,08381,42379,86

Q degajari oameni600600600600600600600600600600600600600

Q degajari iluminat273,6273,6273,6273,6273,6182,4182,4182,4182,4273,6273,6364,8364,8

Q aporturi eb1195119511951195119511951195119511951195119511951195

Q aporturi i. inv26,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,3720926,37209

TOTAL3487,3083589,4863634,8833701,5773804,5773951,9864481,8485353,0125918,0266257,0755871,6015018,1574056,656257,075

Birou 26891011121314151617181920

Q aporturi perete cortina Sud481,4669523,7859863,74081032,521147,4421104,33945,151558,6458336,79385,5976895,8849257,53777125,5587

Q aporturi terasa112,45113,1115,375119,6125,125131,625138,45145,275150,8155,35157,95158,925158,275

Q degajari oameni300300300300300300300300300300300300300

Q degajari iluminat223,2223,2223,2223,2223,2148,8148,8148,8148,8223,2223,2297,6297,6

Q aporturi eb860860860860860860860860860860860860860

Q aporturi i. inv34,0214234,0214234,0214234,0214234,0214234,0214234,0214234,0214234,0214234,0214234,0214234,0214234,02142

TOTAL2011,1382054,1072396,3372569,3412689,7892578,7762426,4222046,7421830,4141658,1691671,0561708,0841775,4552689,789

Birou 27891011121314151617181920

Q aporturi perete cortina Sud572,3707732,03821214,3881448,2511604,4831561,6341361,173850,1491593,4633316,289302,9155152,1803237,9467

Q degajari oameni225225225225225225225225225225225225225

Q aporturi t124,56125,28127,8132,48138,6145,8153,36160,92167,04172,08174,96176,04175,32

Q degajari iluminat561,6561,6561,6561,6561,6374,4374,4374,4374,4561,6561,6748,8748,8

Q aporturi eb420420420420420420420420420420420420420

Q aporturi i. inv36,3344936,3344936,3344936,3344936,3344936,3344936,3344936,3344936,3344936,3344936,3344936,3344936,33449

TOTAL1939,8652100,2532585,1222823,6652986,0172763,1682570,2672066,8041816,2381731,3031720,811758,3551843,4012986,017

Birou 28891011121314151617181920

Q aporturi perete cortina Sud667,9405871,62081461,4581746,9761935,0371891,1121656,5351043,916742,3142307,4358294,4367147,9207231,2864

Q degajari oameni300300300300300300300300300300300300300

Q degajari iluminat226,8226,8226,8226,8226,8151,2151,2151,2151,2226,8226,8302,4302,4

Q aporturi terasa83,0483,5285,288,3292,497,2102,24107,28111,36114,72116,64117,36116,88

Q aporturi eb560560560560560560560560560560560560560

Q aporturi i. inv49,6346549,6346549,6346549,6346549,6346549,6346549,6346549,6346549,6346549,6346549,6346549,6346549,63465

TOTAL1887,4152091,5752683,0922971,7313163,8713049,1472819,612212,031914,5091558,591547,5111477,3151560,2013163,871

Birou 29891011121314151617181920

Q aporturi perete cortina Sud360,2051482,246806,0164968,24051079,3391040,085893,0294536,7757331,327152,322151,847180,30389140,8309

Q degajari oameni225225225225225225225225225225225225225

Q degajari iluminat187,2187,2187,2187,2187,2124,8124,8124,8124,8187,2187,2249,6249,6

Q aporturi terasa83,0483,5285,288,3292,497,2102,24107,28111,36114,72116,64117,36116,88

Q aporturi eb420420420420420420420420420420420420420

Q aporturi i. inv37,0091337,0091337,0091337,0091337,0091337,0091337,0091337,0091337,0091337,0091337,0091337,0091337,00913

TOTAL1312,4541434,9751760,4261925,772040,9481944,0941802,0781450,8651249,4961136,2511137,6961129,2731189,322040,948

Cap 6Calculul sarcinii termice de iarnaSarcina termic pentru nclzirea de la temperatura exterioar la temperatura interioar a aerului infiltrat prin neetaneitile uilor i ferestrelor i a aerului ptruns la deschiderea acestora Qi, se determin cu relatia:Qi=Q deg-QpQdeg- reprezinta suma degajarilor de caldura de la sursele interioare;Qp- perezinta pierderea de caldura a incaperii, calculata cu temepratura interioara de iarna, in conformitate cu metodologia indicata in STAS 1907/1/1997, cu exeptia necesarului de caldura pentru aerul infiltrat.Pentru incaperile de locuit unde aerul proaspat este introdus cu temepratura interioara cu cea interioara, nu se va lua in considerare decat necesarul de caldura prin transmisie.Sarcina termica de iarna poate fi pozitiva atunci cand incaperea va trebui racita, iar negativa, atunci cand incaperea va trebui incalzita.Q degajari

QomQilQ e.bQ necQi

Birou 1525864900180452,84039

Birou 275011402410367851,71238

Birou 34507685601932-538,461

Birou 41125175227004765-64,1728

Birou 56001002270018771923,956

Birou 6225312520538362,8623

Birou 7150300250950-400,355

Birou 8900202,25604724-3163,2

Birou 9150205,8380709-75,8687

Birou 1160078011255961519,002

Birou 1215028828050569,12179

Birou 13225780420629406,4629

Birou 14225288750551567,6629

Birou 15225372750548613,3266

Birou 16225300750515609,7681

Birou 17300294635544538,4496

Birou 18150294500562235,0048

Birou 19202536024506760-2105,24

Birou 20450222890720731,2531

Birou 2222532884955431820,689

Birou 23300660635826438,6001

Birou 24225300520569325,9709

Birou 2560045611951752271,3724

Birou 26300372560573472,9083

Birou 27225936420575537,8246

Birou 28300378560785263,6228

Birou 29225312420497303,5478

Capitolul 7Bilantul de umiditate pentru vara [kg/s] [kg/s] -degajarea de umiditate a unei persoane N-numarul de persoane din incapere-degajarile de umiditate de la oameni [kg/s pers]ql-degajarea de caldura latenta a omuluihv-entalpia vaporilor de apa la [kJ/kg] temperatura corpului umantom-temperatura corpului uman [kJ/kg]

In functie de tipul de activitate, s-a ales valoarea pentru degajarea de caldura latenta a omului de: [W/pers] munca usoara ,birouri

Bilantul de umiditate pentru iarnaDeoarece destinatia cladirii este de cladire de birouri, se considera ca valoarea degajarilor de umiditate ramane constanta.

Capitolul 8Calculul debitului de aer de ventilareDebitul de aer se va stabili in functie deocuparea umana si de emisiile de substante poluante.8.1.Calculul debitului de aer proaspat pentru situatia de vara Se determina parametrii pentru punctul C care reprezinta starea aerului conditionat. [C] [kJ/kg aer uscat] [%]Se va determina debitul de aer proaspat pentru fiecare birou cu relatia: N=numarul de persoane din incapere [m3/h/pers]A=aria pardoselii fiecarui birou [m2] [m3/hpers]Astfel, pentru parter, vom avea urmatoarele valori ale debitului de aer proaspat:NpS[m2]Dp [m3/h]

Birou 1772266

Birou 21095370

Birou 3664231

Birou 415146559

Birou 5883,5305

Birou 6326108

Birou 722582

Birou 81296421

Birou 9217,1572

Birou 11865282

Birou 1222480

Birou 13365157

Birou 14324105

Birou 15331114

Birou 16325107

Birou 17424,5131

Birou 18224,581

Birou 19272741020

Birou 20655219

Birou 22325107

Birou 23438148

Birou 24331114

Birou 25878298

Birou 26431,5140

Birou 27326108

Birou 28434143

Birou 29324105

Cladirea de birouri va fi defalcata in doua parti. Pe fiecare parte va fi determinat debitul de aer proaspat, astfel incat se vor alege centralele de tratare a aerului cu debitul necesar de introducere reprezentand suma debitelor pe birourile aferente fiecari parti ale cladirii.

Capitolul 9Alegerea agregatelor de tratare a aeruluiCentralele de tratare a aerului se amplaseaza astfel incat sa fie cat mai aproape de incaperea sau incaperile deservite, pentru a avea pierderi pe traseu cat mai mici. De asemenea centralele se amplaseaza astfel incat zgomotul produs de aceasteaa sa nu produca disconfort.Agregatele de tratare a aerului se aleg pe baza proceselor trasate in diagrama h-x. Pentru tratarea aerului s-au ales 2 agregate prevazute cu camere de amestec si care functioneaza in solutia aer-aer si care functioneaza cu 100% aer proaspat. Centrala (1) de tratare a aerului in solutia numai aer, model 1 AHU IV PRODUKT Flexomix vehiculeaza un debit de aer proaspat de 5600 mc/h si prezinta urmatoarele componente: ventilator, recuperator in placi, filtru de praf, baterie de racire, baterie de incalzire camera de umidificare izoterma, ventilator.Centrala (2) de tratare a aerului in solutia numai aer model 1 AHU IV PRODUKT Flexomix vehiculeaza un debit de aer proaspat de 6200 mc/h si prezinta urmatoarele componente: ventilator, camera de amestec ( recuperator de caldura), baterie de incalzire filtru de praf, baterie de racire, baterie de incalzire, camera de umidificare izoterma, ventilator.Centralele vor fi amplasate la parterul cladirii, neavand un nivel de zgomot mare.Fisele tehnice ale centralelor se vor gasi in anexa.

Capitolul 10Alegerea gurilor de aspiratie/introducere/transfer si a ventiloconvectoarelorGurile de introducere si de aspiratie se vor amplasa in plafonul fals, fiind conectate la instalatia de aer prin intermediul plenumurilor.10.1. Alegerea gurilor de introducerePentru determinarea numarului de guri de introducere se va tine cont de debitul de refulare pe anemostat (aprox 100 m3/h) si se va urmari ca bataia jetului sa asigure o viteza a aerului in planul de lucru de maxim 0,2 m/s. In functie de necesarul de aer vehiculat in fiecare incapere, s-au ales anemostatele de la FRANCE AIR model DAU03, racordate cu plenum model PFU 41+ AC( plenum cu racord axial). Fisele tehnice ale anemostatelor de refulare se gasesc in anexa.10.2. Alegerea gurilor de aspiratieGurile de aspiratie se vor alege intr-un numar mai mic decat cel al gurilor de introducere deoarece debitul evacuat reprezinta 90% din debitul total introdus . Pentru a evita scurtcircuitarea intre gurile de introducere si cele de evacuare, fapt ce ar duce la neventilarea incaperii respective, gurile de aspiratie nu se vor amplasa pe aceeeasi axa cu gurile de introducere. Am ales guri de aspiratie din catalogul Lindab, model LKA+MBA (plenum de racordare). Am ales modelul de guri de aspiratie in functie de debitul necesar de aspirat din fiecare birou, atfel incat nivelul de zgomot sa nu depaseasca 34 db si pierderea de presiune sa nu depaseasca 40 de PA. Am amplasat gurile de aspiratie in vecinatatea usilor. Fisele tehnice ale gurilor de aspiratie se gasesc in anexa.

10.3. Alegerea gurilor de transferGurile de transfer se aleg astfel incat sa asigure evacuarea restului de 10% din debitul de aer proaspat din fiecare birou. Gurile de transfer se amplaseaza deasupra usilor dintre coridorul de trecere si birouri. Am ales guri de transfer din catalogul France Air, modelul GAV 91, in functie de debitul de aer ce trebuie transferat. Fisa tehnica a gurilor de gasesc in anexa.

NpS[m2]Dp [m3/h]DeextrasD transferat

Birou 1772266239 27

Birou 21095370333 37

Birou 3664231208 23

Birou 415146559503 56

Birou 5883,5305275 31

Birou 632610897 11

Birou 72258273 8

Birou 81296421379 42

Birou 9217,157264 7

Birou 11865282254 28

Birou 122248072 8

Birou 13365157141 16

Birou 1432410595 11

Birou 15331114103 11

Birou 1632510796 11

Birou 17424,5131118 13

Birou 18224,58173 8

Birou 19272741020918 102

Birou 20655219197 22

Birou 2232510796 11

Birou 23438148133 15

Birou 24331114103 11

Birou 25878298268 30

Birou 26431,5140126 14

Birou 2732610897 11

Birou 28434143129 14

Birou 2932410595 11

10.4. Alegerea ventiloconvectoarelorPentru zona de birouri sistemul ales este un sistem cu ventiloconvectoare cu 4 conducte (tur-retur apa rece, tur-retur apa calda), ceea ce permite o mare flexibilitate in functionare deoarece fiecare ventiloconvector functioneaza independent. Circuitele de apa calda si de apa racita sunt separate. Am ales ventiloconvectoare de pardoseala tip Hegoa Silence, din catalogul France Air, in functie de sarcina termica de vara Qv corespunzatoare fiecarui birou. Valoarea sarcinii termice de vara se va imparti la un coeficient de corectie de 0.84, corespunzator fiecarui tip de VCV. Vom dimensiona numai instalatia de apa racita a ventiloconvectoarelor. Nivelul de zgomot al ventiloconvectoarelor alese nu depaseste 34 db.BirouQv [W]Srac VCV [KW]Model VCVNr. VCV

138211,7HS 2.33

2121202,08HS 2,37

359502,3HS 3.33

484571,2HS 1.38

556871,7HS 2.34

625822,8HS 3.31

736112,3HS 3.32

862451,2HS 1.36

918142,3HS 3.31

1132001,2HS 1.33

129571,2HS 1.31

1315912,08HS 2.31

1415521,7HS 2.31

1516012,08HS 2.31

1615141,7HS 2.31

1719632,3HS 3.31

1826092,8HS 3.31

19142161,7HS 2.310

2027472,3HS 2.32

2219811,7HS 3.31

2328872,3HS 2.32

2419902,3HS 3.33

2558842,3HS 3.33

2624861,7HS 2.32

2728771,7HS 2.32

2829401,7HS 2.32

2916902,08HS 2.31

Capitolul 11Dimensionarea geometrica a conductelor de aer de introducere si aspiratieTubulatura de aer folosita este circulara rigida, din otel zincat, cu lungimea standard de 3m. Am ales tubultaura din catalogul AIR TRADE CENTER. Tronsoanele se prind cu ajutorul mansoanelor de conectare. Racordurile de la plenumurile anemostatele de refulare si de la gurile de aspiratie canalele de aer s-a facut cu tubulatura flexibila. Dimensionarea canalelor de aer s-a facut pe baza metodei vitezei descrescatoare, incepand cu cel mai dezavantajat consumator. Dimensionarea s-a facut pe baza aceleasi metode pentru fiecare tronson de aer. Avantajul acestei solutii il reprezinta nivelul de zgomot redus si posibilitatea reglarii debitului de aer.Centrala 1CMDCRefulareCentrala 1

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 1593,1600,0260,0120,1251252,110

1,00093,1600,0262,5000,0120,1251252,110

2,000186,3200,0523,0000,0180,1501502,930

3,000372,6400,1043,5000,0310,2002003,297

4,000558,9600,1553,5000,0490,2502503,165

5,0001425,9400,3964,0000,0990,3553554,004

6,0001730,9200,4815,0000,0990,3553554,860

7,0002612,9200,7266,0000,1260,4004005,779

72612,9200,7266,0000,1260,4004005,779

Birou1

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 188,6600,0252,0000,0120,1251252,008

19,00088,6600,0252,0000,0120,1251252,008

18,000265,9800,0742,5000,0310,2002002,353

Birou 2

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 492,5000,0262,0000,0120,1251252,095

21,00092,5000,0263,0000,0120,1251252,095

20,000185,0000,0513,0000,0180,1501502,909

17,000370,0000,1033,5000,0310,2002003,273

Birou 3

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 1077,0000,0212,0000,0120,1251251,744

23,00077,0000,0212,0000,0120,1251251,744

22,000231,0000,0642,0000,0310,2002002,044

16,000601,0000,1672,5000,0780,3153152,143

15,000866,9800,2413,0000,0780,3153153,092

Birou 5

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 19101,6600,0282,0000,0120,1251252,302

25,000101,6600,0282,0000,0180,1501251,599

24,000304,9800,0853,0000,0310,2002002,698

5,0001425,9400,3965,0000,0990,3553554,004

6,0001730,9200,4815,0000,0990,3553554,860

Birou 8

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 50105,2500,0292,0000,0180,1501501,655

14,000105,2500,0292,0000,0180,1501501,655

13,000210,5000,0582,5000,0250,1801802,299

124210,1172,5000,0490,2502502,384

Birou7

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 2182,0000,0232,0000,0120,1251501,857

27,00082,0000,0233,0000,0120,1251501,857

Birou 9

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 2672,0000,0202,0000,0120,1251251,631

28,00072,0000,0203,0000,0120,1251251,631

11,000575,0000,1603,5000,0490,2502503,255

Birou 6

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 20108,0000,0302,0000,0120,1251252,446

26,000108,0000,0303,0000,0120,1251252,446

10,000683,0000,1904,0000,0490,2502503,867

Birou 11

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 2794,0000,0262,0000,0120,1251252,129

31,00094,0000,0262,5000,0120,1251252,129

30,000282,0000,0782,5000,0310,2002002,495

Birou 29

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 30105,0000,0292,0000,0180,1501501,651

32,000105,0000,0292,0000,0180,1501501,651

29,000387,0000,1082,5000,0490,2502502,191

9,0001070,0000,2973,0000,0620,2802804,829

Centrala 2

Birou 12

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 3380,0000,0222,0000,0120,1251251,812

1,00080,0000,0222,0000,0120,1251251,812

Birou 28

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 3171,5000,0202,0000,0120,1251251,619

4,00071,5000,0202,0000,0120,1251251,619

3,000143,0000,0402,0000,0200,1601601,977

2223,0000,0622,5000,0250,1801802,435

Birou 13

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 3478,5000,0222,0000,0180,1501501,235

5,00078,5000,0222,0000,0180,1501501,235

6,000157,0000,0442,0000,0250,1801801,715

Birou 27

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 36108,0000,0302,0000,0180,1501501,699

7,000108,0000,0302,0000,0180,1501501,699

8,000488,0000,1363,0000,0490,2502502,763

Birou 14

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 37105,0000,0292,0000,0180,1501501,651

9,000105,0000,0292,0000,0180,1501501,651

Birou 26

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 3870,0000,0192,0000,0120,1251251,585

11,00070,0000,0192,0000,0120,1251251,585

10,000140,0000,0392,0000,0180,1501502,202

12,000733,0000,2043,0000,0780,3151282,614

Birou 15

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 40114,0000,0322,0000,0120,1251252,582

13,000114,0000,0323,0000,0120,1251252,582

14,000847,0000,2353,0000,0780,3153153,021

Birou 16

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 41107,0000,0302,0000,0120,1251252,423

15,000107,0000,0303,0000,0120,1251252,423

16,000954,0000,2653,0000,0990,3553552,679

Birou 25

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 4399,0000,0282,0000,0180,1501501,557

24,00099,0000,0282,0000,0180,1501501,557

23,000198,0000,0552,5000,0250,1801502,162

22,000297,0000,0833,0000,0310,2002002,627

Birou 24

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 45114,0000,0322,0000,0180,1501501,793

21,000114,0000,0323,0000,0180,1501501,793

20,000411,0000,1143,0000,0490,2502502,327

Birou 18

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 5181,0000,0232,0000,0120,1251251,834

35,00081,0000,0233,0000,0120,1251251,834

34,00081,0000,0233,5000,0990,3553550,227

Birou 20

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 53110,0000,0312,0000,0180,1501501,730

33,000110,0000,0312,0000,0180,1501501,730

32,000220,0000,0612,5000,0310,2002001,946

31,000301,0000,0843,50,0990,3553550,845

Birou 22

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 48107,0000,0302,0000,0180,1501501,683

30,000107,0000,0302,0000,0180,1501501,683

27,000408,0000,1134,0000,0990,3553551,146

Birou 17

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 5066,0000,0182,0000,0120,1251251,495

28,00066,0000,0183,0000,0120,1251251,495

29,000132,0000,0372,0000,0200,1601601,825

27540,0000,1504,5000,0990,3553551,516

Birou 23

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 4774,0000,0212,0000,0120,1251251,676

26,00074,0000,0213,0000,0120,1251251,676

25,000148,0000,0413,0000,0200,1601602,046

19,000688,0000,1915,0000,0990,3553551,932

18,0001099,0000,3056,0000,0990,3553553,086

17,0002053,0000,5707,0000,1260,4004004,540

CMDC

tronsonD an (m3/h)D an (m3/s)Viteza impusaSect (m2)h mCanal [mm]V reala

AN -> 61102,0000,0282,0000,0180,1501501,604

41,000102,0000,0282,0000,0180,1501501,604

40,000204,0000,0572,5000,0250,1801802,228

39,000612,0000,1703,0000,0620,2802802,762

36,0001020,0000,2833,0000,0990,3553552,864

34,0001101,0000,3063,0000,0990,3553553,091

31,0001320,0000,3674,0000,0990,3553553,706

27,0001427,0000,3964,0000,0990,3553554,007

27'1558,0000,4335,0000,0990,3553554,375

19,0001706,0000,4745,0000,0990,3553554,790

18,0002118,0000,5886,0000,0990,3553555,947

17,0003073,0000,8547,0000,1260,4004006,796

CT61461,7079,0000,1960,55008,699