Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 1
Technicaldatasheet
Hilti Firestop FoamCFS-F FX
Europeantechnical approvalETA No10 / 109
Issue 06 / 2010
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
2/16
Hilti Firestop Foam CFS-F FX
page 2 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Smoketight Sound insulation
Ordering
Order Description Package content Item Number
CFS-F FX incl. 1 mixing nozzle, instructions for use 00000000
Order Description Package content Item Number
MD2000 manual dispenser Manual dispenser with 1 foil pack holder 00000000
ED3500 cordless powered
dispenser kit
Dispenser, C7/24 charger, SFB 121 battery, 3 round brushes,
protective glasses, blow-out pump, 2 foil pack holders,packed in an impact-resistant plastic Hilti toolbox
00000000
ED3500 cordless powered dispenser
basic kit
Dispenser, 3 round brushes, protective glasses, blow-out pump,
2 foil pack holders, packed in an impact-resistant plastic Hilti toolbox
00000000
Firestop Foam
CFS-F FX
Fields of Application
Permanent restop seals in small and medium-sized openings
(optimum size range: 100 x 100 mm to 300 x 300 mm)
Cable trays, single cables, tied cable bundles, small conduits
Openings accommodating pipes and cablesPlastic pipes
Metal pipes (with combustible or non-combustible insulation)
(The seals must comply with ETA No 10 / 109.)
The European Technical Approval
(ETA) can be obtained via your
local Hilti contact.
Technical Data
CFS-F FX
Colour Red
Foil pack volume / foam yield 325 ml / 2.1 liters (freely foamed)Application temperature of
pack / Storage and transport
temperatures
+10C to +35C / +5C to +25C
Curing times Can be shaped afterapprox. 5 min.
Can be cut after approx. 10 min.
Reaction to re, classication
according to EN 13501-1
Class E
Temperature resistance
of the cured foam
30C to +60C
Shelf life 9 months (at 23C and stored
in a dry place)
At 23 C, 50% relative humidity
Features and Benets
3-phase technology with optimum application characteristics
(easily shapeable foam)
Easy installation without need for formwork or other aids
Easily applied using the ergonomically-designed Hilti dispensers
Safety rst: CFS-F FX complies with the requirements ofinternational re protection directives
Neat and tidy application
Very quick and easy to install a reliable restop seal with onlyone product
Easy subsequent installation of additional cables
Outstanding sound insulation properties thanks to exible foam
structure
Smoketightness and restopping with one system
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
3/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 3
Installation instructions
Clean the opening to be sealed.The materi-
al around the opening must be dry, in sound
condition and free from dust or grease.
Apply the restop foam in the opening to
be sealed. The mixed components of the
foam react and begin to expand approx. 30
seconds after application (at 23C). Fill the
opening completely with restop foam, inclu-
ding gaps between individual cables, etc.
NOTE:
It is generally best to begin in the middle of
the opening, building up the foam by working
from bottom to top. In openings with access
from only one side, begin at the rear and work
toward the front.
The foam will harden in the mixing nozzle du-
ring pauses (i.e. > 1 minute at 23C; > 20 se-
conds at 35C). The mixing nozzle must
then be changed.Release the pressure fromthe piston rod before changing the mixing
nozzle.
Use formwork made from an air-permeable
material (e.g. perforated cardboard)
when lling openings in ceilings.
The foam can be shaped or smoothed by
hand (if necessary) after approx. 5 minutes (at
23C). Wear protective gloves!After approx.
10 minutes (at 23C) the foam becomes hard
and it can then be cut.
NOTE:
After hardening, any projecting foam can be
trimmed o to the specied minimum depth.
Trimmed-o scraps of hardened foam can be
placed in the next opening and fresh foam ap-
plied around these.
Mount the installation identication
plate beside the correctly sealed opening,
if required.
Subsequent installation of cables or pipes
Additional cables or pipes can be installed in
the opening without diculty. Do not exceed
the approved maximum number and size of
cables or pipes.
1. The cable or pipe may be pushed directly
through the foam. Where necessary, use a
suitable tool (screwdriver or drill bit, etc.) to
make a hole in the foam before pushing the
cable or pipe through. Do not damage exis-ting cables.
2. Seal any remaining gaps carefully with
CFS-F FX
Check the foil pack holder for damage and
ensure that it functions correctly. Slide the foil
pack into the holder. Caution:Never use da-
maged foil packs and/or damaged or badly
soiled foil pack holders.
Remove the cap. Screw the mixing nozzle
all the way onto the foil pack and tighten it
securely.Check that the black mixing element
is in place inside the nozzle! Do not use dama-
ged mixing nozzles. Do not, under any circum-
stances, modify or tamper with the mixing
nozzle. The foil pack should only be used to-
gether with the mixing nozzle supplied. A new
mixing nozzle must be used with each new foil
pack.
Insert the holder containing the foil pack
into the dispenser:Press the release button
on the dispenser, pull the piston rod back as
far as it will go and then insert the holder con-
taining the foil pack into the dispenser.
The foil pack opens automatically when dis-
pensing begins. Never pierce a hole in the foil
pack! This will cause the system to malfunc-
tion.
Discard the unevenly mixed initial quantity:
The foam dispensed by the rst stroke of the
dispenser must be discarded, e.g. in the emp-
ty outer packaging material.
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
4/16
Hilti Firestop Foam CFS-F FX
page 4 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Penetration seal (A) /services (C) Classication
E = Integrity
I = Insulation
Seal depth (tA)
(mm)
Other criteria
Description
Cable
|Cabletray
Small sheathed cables 21 mm
Tied cable bundle 100 mm
EI 120 200 Minimum distances:min S1 = 0 mm (cable tray to seal edge)
min S2 = 50 mm (cable to cable tray)
min S2 = 33 mm (cable to cable bundle)
min S2 = 0 mm (cable to cable)
Framing details see specic drawingsbelow.
EI 60 ; E 120 112
All sheathed cables 80 mm EI 90 ; E 120 200
EI 60 ; E 120 150
Steel conduit 16 mm EI 120 U/U 200EI 90 U/U; E 120 112
Plastic conduit 16 mm EI 120 U/U 112
Blankopening Blank, no services EI 120 200
Cable penetration
Flexible wall | Rigid wall
Cable, cable bundle in flexible wall, rigid wall
Cables on cable tray in flexible wall, rigid wall
exible wall
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 112 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal andany stud, and the cavity must be lled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
rigid wall
exible wall rigid wall
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
5/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 5
E
tE
A
tA
E1
Blank opening in flexible wall, rigid wall
Aperture framing, seal frames
exible wall rigid wall
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
6/16
Hilti Firestop Foam CFS-F FX
page 6 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Penetration seal (A) /services (C) Classication
E = Integrity
I = Insulation
Seal depth (tA)
(mm)
Other criteria
Description
Cable|Cabletray
Small sheathed cables 21 mm
Tied cable bundle 100 mm,
single cable 21 mm
EI 120 250 Minimum distances:
min S1 = 0 mm (cable tray to seal edge)
min S2 = 50 mm (cable to cable tray)min S2 = 33 mm (cable to cable bundle)
min S2 = 0 mm (cable to cable)
EI 60 150
All sheathed cables 80 mm EI 60; E 120 150
Medium sheathed cables 21 50 mm EI 120 250
Large sheathed cables 80 mm EI 90; E 120 200
EI 60; E 120 150
Conduits|Tube
s Steel conduit 16 mm EI 120 U/U 150
Steel and plastic conduits 16 mm
Cable penetration
Floor
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid oors (E) (concrete, minimum density 2200 kg/m3), minimum thickness 150 mm (tE).
Cable, cable bundle in floor Framing floor
Cables tray in floor
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
7/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 7
Penetration seal (A) /
services (C)
Pipe insulation (D) Classication
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
Metalpipe
Steel pipe
33.7 mm (dc)
(pipe wall thickness
2.6 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)tD = 30 mm / LD = 500 mm
EI 120 C/U 150 Minimum distances:min S1 = 0 mm
(between pipe and seal edge)
min S2 = 0 mm
(linear arrangement)min S2 = 40 mm
(in a cluster)
Steel pipe
33.7 114.3 mm (dc)(pipe wall thickness
2.6/3.6 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)tD = 40 mm / LD = 500 mm
Steel pipe
33.7 114.3 mm (dc)
(pipe wall thickness2.6/3.6 14.2 mm (tc))
Combustible insulation
(synthetic rubber
Armaex)tD = 19 mm / LD = 500 mm
EI 90 C/U; E 120 150 Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETACFS-B (A2))
Copper pipe
28 88.9 mm (dc)
(pipe wall thickness
1.0/2.0 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
EI 60 C/U; E 120 150
Combustible insulation(synthetic rubber
Armaex)
tD = 19 mm /LD = 500 mm
EI 60 C/U ; E 120 150 Installed with 2 layers HiltiFirestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
Plasticpipe
PVC-U pipe (EN 1452-1,DIN 8061/8062) 50 mm(dc) (pipe wall thickness
3.7 5.8 mm (tc))
EI 120 U/C 150 Minimum distances:min S1 = 30 mm(between pipe and seal edge)
min S2 = 55 mm
(between pipes)PE pipe (EN 1519-1, DIN
8074/8075) 50 mm (dc)(pipe wall thickness
2.9 4.6 mm (tc))
Pipe penetration
Flexible wall | Rigid wall
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 150 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal andany stud, and the cavity must be lled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
Metal pipe, mineral wool insulation in flexible wall, rigid wall
exible wall rigid wall
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
8/16
Hilti Firestop Foam CFS-F FX
page 8 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Metal pipe, combustible insulation in flexible wall, rigid wall
Plastic pipe in flexible wall, rigid wall
exible wall
exible wall
rigid wall
rigid wall
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
9/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 9
Penetration seal (A) /
services (C)
Pipe insulation (D) Classication
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
Metalpipe
Steel pipe
33.7 mm (dc)
(pipe wall thickness2.6 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 30 mm / LD = 500 mm
EI 120 C/U 150 Minimum distances:
min S1 oor = 20 mm
(between pipe and seal edge)min S2 oor = 15 mm
(linear arrangement)
min S2 oor = 20 mm
(in a cluster)
Steel pipe
33.7 114.3 mm (dc)
(pipe wall thickness
2.6/3.6 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)
tD = 40 mm / LD = 500 mm
Steel pipe
114.3 168 mm (dc)(pipe wall thickness 3.6
14.2 / 14,0 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)tD = 40 mm / LD = 500 mm
EI 120 C/U 150
Steel pipe
33.7 114.3 mm (dc)(pipe wall thickness
2.6 3.6 mm (tc))
Combustible insulation
(synthetic rubberArmaex)
tD = 19 mm / LD = 500 mm
EI 120 C/U 150 Installed with 2 layers Hilti
Firestop Bandage CFS-B onboth sides (according to ETA
CFS-B (A2))
Copper pipe
28 88.9 mm (dc)(pipe wall thickness
1.0/2.0 14.2 mm (tc))
Mineral wool
(Rockwool RS 800)tD = 40 mm / LD = 500 mm
EI 120 C/U 150 Installed with 2 layers Hilti
Firestop Bandage CFS-B onboth sides (according to ETA
CFS-B (A2))
Combustible insulation
(synthetic rubber
Armaex)
tD = 19 mm /LD = 500 mm
EI 90 C/U; E 120 150 Installed with 2 layers Hilti
Firestop Bandage CFS-B on
both sides (according to ETA
CFS-B (A2))
Plasticpipe
PVC-U pipe (EN 1452-1,
DIN 8061/8062)
50 mm (dc)(pipe wall thickness
3.7 5.6 mm (tc))
EI 120 U/C 150 Minimum distances:
min S1 = 50 mm
(between pipe and seal edge)min S2 = 65 mm
(between pipes)
PVC-U pipe (EN 1452-1,
DIN 8061/8062)
50 mm (dc)
(pipe wall thickness
3.7 mm (tc))
EI 120 U/C 150
PE pipe (EN 1519-1, DIN
8074/8075) 50 mm (dc)(pipe wall thickness
2.9 4.6 mm (tc))
EI 120 U/C 150
Pipe penetration
Floor
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid oors (E) (concrete, minimum density of 2200 kg/m3), minimum thickness 150 mm (tE).
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
10/16
Hilti Firestop Foam CFS-F FX
page 10 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Metal pipe with mineral wool insulation in floor
Metal pipe, combustible insulation in floor
Plastic pipe in floor
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
11/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 11
Penetration seal (A) /
services (C)
Pipe insulation (D) Classication
E = Integrity
I = Insulation
Minimum seal
depth (tA) (mm)
Other criteria
Description
Mixedpenetration|cable|bundle|tray|metal|plasticpipe
All sheathed cables 80 mm(e.g. power, control, signal,
telecommunication, data,
optical bre cables)Tied cable bundle ( 100 mm),maximum diameter of single
cable 21 mm
EI 60 / E 120 150 Cable support constructionperforated metal cable tray
minimum distances:
min S1 = 0 mm(cable to seal edge)min S2 = 35 mm
(between cable and pipe)
min S1 = 0 mm (between metal
pipe and seal edge)min S2 = 0 mm (between metal
pipe and linear arrangement)
min S2 = 40 mm(cluster arrangement)
min S1 = 30 mm (between
plastic pipe and seal edge)
min S2 = 55 mm (betweenplastic pipe and metal pipe)
Steel conduits or tubes
16 mm
Steel pipe 33.7 114.3 (dc)(pipe wall thickness
2.6/3.6 14.2 mm)
Mineral wool(Rockwool RPS 800)
tD = 40 mm / LD = 500 mm
Copper pipe
28 88.9 mm (dc)(pipe wall thickness
1.0/2.0 14.2 mm)
Mineral wool
(Rockwool RPS 800)tD = 40 mm / LD = 500 mm
Steel pipe
33.7 114.3 mm (dc)(pipe wall thickness2.6/3.6 14.2 mm)
Combustible insulation
(synthetic rubberArmaex)tD = 19 mm /LD = 500 mm
Installed with 2 layers Hilti
Firestop Bandage CFS-B onboth sides (according to ETACFS-B (A2))
Copper pipe
28 88.9 mm (dc)
(pipe wall thickness1.0/2.0 14.2 mm)
Combustible insulation
(synthetic rubber
Armaex)tD = 19 mm /LD = 500 mm
PE pipe (EN 1519-1,
DIN 8074/8075) 50 mm (dc)
(pipe wall thickness (tc)
2.9 4.6 mm)
PVC-U pipe (EN 1452-1,
DIN 8061/8062) 50 mm (dc)
(pipe wall thickness (tc)
3.7 5.6 mm)
Mixed penetration
Flexible wall | Rigid wall | Floor
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Flexible walls / Drywalls (E), minimum thickness 150 mm (tE) with timber or steel studs lined on both faces with minimum
2 layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal andany stud, and the cavity must be lled with minimum 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1.
Rigid walls (E) (concrete, aerated concrete or masonry, minimum density of 650 kg/m3), minimum thickness 112 mm (tE).
Hilti Firestop Foam CFS-F FX may be used to form penetration seals of maximum opening size 400 x 400 mm (w x h) in:
Rigid oors (E) (concrete, minimum density of 2200 kg/m3), minimum thickness 150 mm (tE).
Mixed penetration
exible wall rigid wall oor
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
12/16
Hilti Firestop Foam CFS-F FX
page 12 Hilti Firestop Foam CFS-F FX | Issue 06/2010
Charecteristics Assessment of charecteristics Norm, standard, test
Health and the environment
Air permeability(gas thightness)
p 50 Pa 0.0007 q/A [m3/(h x m2)]
(174 mm thickness of layer)
p 250 Pa 0.0007 q/A [m3/(h x m2)]
Permeability regarding gases N2,
CO2, CH4: tested
EN 1026
Dangerous substances below any respective occupationalexposure limits as far as such limits exist
Material safety data sheet
Safety in use
Resistance to impact / movement /
Mechanical resistance and stability /
Adhesion
Soft body impact: Energy 1200 Nm
Hard body impact: Energy 10 Nm
EOTA Technical Report
TR001, A1
fulllls requirements of zones Type I, II, III
and IV
maximum opening 400 x 400 mm
Protection against noise
(Air borne sound insulation)
Rw(C; Ctr) = 47 (1; 6) dBDn,e,w(C; Ctr) = 54 (0; 5) dB
EN ISO 140-3EN ISO 20140-10
EN ISO 717-1
Durability and serviceability Category Y2 (suitable for penetration seals
intended for use at temperatures between 20 C and + 70 C) no exposure to rain
or UV
EOTA Technical Report TR024
ETAG 026-2
May be coated with acrylic dispersion, alkyd
resin, polyurethan / acrylic and epoxy resin)
Reaction to re Class E EN 13501-1
Characteristics of CFS-F FX
Additional Attributes
Hilti Firestop products are comprehensively tested and individually tailored to
the technical requirements of a buildings mechanical and electric installations.
In addition to their superior behaviour in passive re protection, Hilti Firestopproducts also meet the requirements in building technology that continue to gain
signicance and also help the designer and installer in meeting these additional
requirements. The assessment of tness for use has been made in accordance
with EOTA ETAG No 026 Part 2.
Service
With more than 20 years of experience worldwide, Hilti is one of the leading suppliers of
firestop systems. We actively help you manage your firestop projects better by providing:
Quick engineering judgements
Extensive technical literature
On-site training and demonstration
Sophisticated jobsite logistics
Assurance of conformity with specific application requirements
International network of Hilti firestop specialists
Our network of experienced sales representatives, field engineers, firestop specialists
and customer service representatives is just a phone call away (use the local toll-free
Hilti number).
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
13/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 13
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
14/16
Hilti Firestop Foam CFS-F FX
page 14 Hilti Firestop Foam CFS-F FX | Issue 06/2010
-
8/10/2019 ASSET_DOC_2412696_APC_RAW - Fise Tehnice Sistem Etansare Hilti
15/16
Hilti Firestop Foam CFS-F FX
Hilti Firestop Foam CFS-F FX | Issue 06/2010 page 15
-